Short answer: question marks mean the terminal received no usable data for those tags, and the fix lives in the HMI's startup options, not in the PLC. Set the startup choice that lets a loading application replace the stored communications configuration to No, re-enter the controller's IP path, and restart once. It is a 5-minute job that leaves the control program untouched. The screen, the tags and the analog input card are almost never at fault when every controller-backed field goes blank at once. Work down the checks in the order you meet them on site: what the marks mean, whether your laptop visit caused them, the boot hang at the alarm stage, the address faults, the fix, and the follow-up that keeps it fixed.
What do question marks on an HMI screen mean?
A question mark in a field means the terminal drew that field without a usable value — the tag's data never arrived from the controller. The graphics and the touch keep working, so the marks are a communications symptom rather than a failed analog card or a scaling fault.
Check the scope before touching anything. One ? among live neighbours points at that single reference, usually a retyped or deleted tag. Every controller-backed field blank on every screen points at the one dependency they share: the application's path to the controller. A screen of marks on one terminal while its twin runs fine points at that terminal's configuration alone.
The pattern in front of you sorts the causes fast:
- Every controller-backed field, on every screen: the shared data path failed — the application's stored controller path or the network between them.
- One field among live neighbours: that reference is wrong, through an edited, deleted or mistyped tag.
- Marks plus a boot hang at the alarm stage: the application's saved communications configuration is the likely cause; the startup section below sorts it.
- Controller answers a laptop while the terminal shows marks: the fault sits in the terminal's own settings, because the network and the controller are proven good.
- Marks start when a new device joins the network: spend 2 minutes on the duplicate-address test.
- A live number that is simply wrong: that is scaling, a different fault, with its own section near the end.
Marks differ from a row of hash marks, which means the value arrived but the field is too narrow to show it — a formatting fix covered in hash marks in HMI numeric fields. A terminal that never talked after a fresh install starts from a different page too; the likely causes of an HMI not communicating with its PLC opens with commissioning faults instead of a sudden loss like this one.
Can connecting a laptop to the switch break the HMI?
Connecting an engineering laptop to browse the controller program changes nothing stored in the terminal. The visit alone cannot produce the question marks — what it proved instead is that the controller and the switch path are healthy, which narrows the fault to the terminal's own configuration.
Two settings live inside the terminal, and mixing them up wastes an afternoon. Its own Ethernet address — say 192.168.1.50 with mask 255.255.255.0 — identifies the terminal on the plant network. The application's communication configuration is a separate entry that names the controller supplying the tags, say 192.168.1.10. A terminal with the right address can still carry an application aimed at the wrong controller.
Prove the network while the marks are still on screen. From the laptop, ping the controller address: replies in under 1 ms across the same switch confirm the controller is up and reachable. The default ping on a Windows laptop sends 4 packets over 4 s, and silence past that timeout means nothing answers for that address — the fault drops to the network layer instead. Change one thing per test and note each result, because a fix that arrives by accident is a fault you cannot explain away later.
Why does the HMI hang at Starting Alarms on boot?
A boot that stops at the alarm stage has already loaded the operating system and the runtime. The stall sits in the step that connects tags and starts the alarm system — an application and configuration fault, not a dead touchscreen or a failing power supply. A healthy boot clears the alarm stage in well under 1 min; give a stall 5 min at most before you call it a hang.
The exact wording is evidence, so photograph it before any restart. This terminal family reports the stage as "Starting Alarms. Please wait …". Another power cycle reloads the same application with the same stored configuration, which reproduces the identical stall — the diagnosis confirming itself. Record the stage and the message, then leave the power alone.
Alarm handling has its own documented faults on old software: the vendor's knowledgebase records an alarm fault in FactoryTalk View 5.10, fixed by a vendor patch, that misbehaves at startup. Compare the installed version against the vendor's patch list while the fault is fresh, and take updates only from the vendor.
Which startup setting erases the PLC path on every boot?
The culprit is the startup choice that lets a loading application overwrite the terminal's stored communications configuration. Set to replace, every application load restores the controller path saved inside the runtime file — often an address from the development bench that the plant network has never used.
The terminal manual documents the choice in plain sight: on this family it is the Replace RSLinx Communications button, and the same setting sits under Terminal Settings > Startup Options. Answering Yes at a load prompt accepts the path stored in the runtime file, which can point at an old bench address or even request an address by DHCP. Answering No keeps the configuration already working on the terminal. One prompt, two very different outcomes — read it every time instead of clicking through.
Worked example, with assumed addresses: the controller sits at 192.168.1.10 and the terminal at 192.168.1.50, both static on a 255.255.255.0 subnet — a /24 with 254 usable device addresses. The runtime file was built on a bench network, so its saved path says 10.10.10.10. With the startup choice set to replace, every boot restores 10.10.10.10, and every controller-backed field draws ?. Set the choice to No, type 192.168.1.10 as the controller path, and restart once: the fields draw numbers again. The addresses here are example values, so read the real ones from the address register before you type anything.
The same symptom wears different clothes on other software. A copied SCADA project shows marks for its own reasons, documented step by step in FactoryTalk View SE project copy shows question marks: the fix; a machine terminal follows the startup-choice path above.
Is it DHCP or a duplicate IP address?
Both faults are real and each takes 2 minutes to rule out, but neither is the likeliest cause of a sudden loss. A DHCP address can move at every lease renewal — commonly 24 h on default server settings, with the client typically attempting renewal at half the lease, 12 h in — while a duplicate address makes the link intermittent rather than dead.
Run the duplicate test with the power switch, not the software. Power the terminal down, then ping its address — 192.168.1.50 in the example — from the laptop. A reply within the default 4 s timeout means a different device is answering for that address, so re-address one of the two devices. Then read the terminal's network settings for the assignment method: a static entry survives every restart, while a DHCP entry moves at the next lease renewal.
Settle both faults the same way: static addresses on a network dedicated to the machines, plus a written register at the panel with one line per device — address, mask, assignment. A /24 holds 254 devices, so the register stays one page long.
How do you fix it without editing the PLC program?
Fix it from the terminal's own configuration screens in about 5 minutes: record the settings, set the communications-replacement choice to No, re-enter the controller's IP path and restart once. The control program stays untouched because the fault lives in the terminal's stored configuration.
- Record first. Photograph the ? screens and the exact boot message, and write down the terminal's address, mask and application name.
- Confirm the controller address. Read it from the working engineering connection — the same address the laptop reached, 192.168.1.10 in the example.
- Set the choice to No. Open the startup options — Terminal Settings > Startup Options on this family — and set the communications-replacement choice so loads keep the stored configuration.
- Re-enter the complete path. Type the controller address plus any routing the application needs; on a flat /24 machine network, the address alone is the whole path.
- Restart once and watch. The boot should clear the alarm stage without hanging, and the fields should draw numbers within 2 s of the screen loading.
- Back it up. Save the corrected application and configuration through your site's normal backup process, so the stored copy matches the working terminal.
One controlled restart is the whole test. A row of power cycles proves nothing new, and it turns a 5-minute fix into an afternoon.
How do you stop it coming back after the next download?
Set the saved runtime's stored path to match the plant network and the fault cannot return, because then every future download and the terminal agree.
Write the addresses where the next person will find them — a line inside the door beats a shared drive nobody opens:
| Device | Address | Mask | Assignment |
|---|---|---|---|
| Controller | 192.168.1.10 | 255.255.255.0 | static |
| HMI terminal | 192.168.1.50 | 255.255.255.0 | static |
| Engineering laptop | 192.168.1.99 | 255.255.255.0 | static while connected |
Correct the saved runtime in the development software too, so the next download writes the same good path the terminal already holds. Keep the startup choice at No on every terminal in the plant. Deploying to a different terminal later is the one case where answering Yes makes sense: the saved file is then exactly the configuration you meant to load.
When is it the analog input instead of the HMI?
A wrong reading is a different fault from question marks: the field shows a live number that is simply incorrect, so scaling is where you look. Set the raw minimum and maximum from the card's documentation chart and the engineering values to the process span — 4-20 mA against 0-400 GPM.
Each card family scales its counts differently, so the raw range comes from that chart; a 12-bit card, for instance, spans 0-4095 counts over its input range. The engineering range is your process span. For the example line, a 0-400 GPM flow on a 4-20 mA transmitter reads half-scale at 12 mA: (12 - 4) / (20 - 4) = 0.5, and 0.5 × 400 GPM = 200 GPM. At 4 mA the screen should read 0 GPM, at 20 mA it should read 400 GPM. Check one point against a loop meter and the scaling is proven. Scaling never produces question marks: a broken or out-of-range signal still shows a number or raises a channel fault, while an empty field means the value never arrived at all.
When should the terminal or the enclosure be re-specified?
Question marks are a data fault, so swapping hardware rarely fixes them; re-specify only when the terminal fails for a second, physical reason. A terminal that stumbles on cold damp mornings fails for moisture rather than a path problem, and condensation inside an outdoor HMI covers it.
Two checks earn their keep before any order. A terminal that keeps losing its configuration after power interruptions points at its supply, so measure the supply feeding the panel before blaming software. A terminal that misbehaves on a schedule — cold mornings, washdown weeks — fails for a physical reason no path change will touch.
When replacement is the right call, the housing decision comes with it. Our stainless HMI housings are 304 stainless with a gasketed rear cover, cut for the exact display you choose, from 7 in to 23.8 in, delivered in 10 business days — counted from your order, or from your approval of the drawing when the housing is configured for your display. The front seal is IP65-type once the display is installed, and it is a manufacturer rating, not UL listed.
Keep the rating through the swap: the cutouts, glands and HMI windows guide covers the cable entries, and rear wiring protection for HMIs covers the wiring behind the gasketed cover. For a display that needs its own front plate or an unusual cutout, the 3D enclosure builder produces the drawing you approve before anything is cut. Opening a live panel to swap hardware is lockout work: switch off, lock off and prove the panel dead before reaching past the glands.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 7" HMI enclosure | 304 stainless | 7.43 x 9.96 x 3.7 in | IP65-type front seal with the display installed, manufacturer rated; not UL listed |
| 23.8" HMI enclosure | 304 stainless | 15.91 x 24.96 x 4.02 in | IP65-type front seal with the display installed, manufacturer rated; not UL listed |
| 10.1" HMI enclosure | 304 stainless | 8.72 x 12.66 x 3.48 in | IP65-type front seal with the display installed, manufacturer rated; not UL listed |
Questions
Will a factory reset of the terminal clear the question marks?
It can, but it is the long way round. A reset wipes the application, and reloading the old runtime file restores the same saved path that caused the fault in the first place. Fix the startup choice and the controller path first, keep the corrected backup, and reset only when the terminal itself is unstable.
How long does the fix take at the terminal?
About 5 minutes once you know the menus: record the settings, set the communications-replacement choice to No, re-enter the controller's IP path, restart once and watch the boot clear the alarm stage. Budget 30 minutes the first time while you find the startup options and write the address register.
Should the HMI and the PLC addresses be static or DHCP?
Static, on a network dedicated to the machines. A DHCP lease commonly runs 24 h on default server settings, and a path entered as an IP address stops working the day the address moves. Where DHCP cannot be avoided, set a reservation so the device keeps the same address at every renewal.
Can a stuck key or a USB stick cause the boot hang?
Yes, but it stops the boot earlier than the alarm stage. A pressed touchscreen, a stuck key on keyed models or an unseated USB device halts the boot in the operating-system or calibration stage, before the runtime loads. Remove every USB device, relieve any pressure on the screen and retest; a stall that reaches the alarm message is an application fault.
What raw range do I enter for a 4-20 mA analog input?
Take it from the card's documentation chart, because each family scales its counts differently — a 12-bit card spans 0 to 4095 counts. Then set the engineering range to your process span, for example 4 mA as 0 GPM and 20 mA as 400 GPM. Check one mid-scale point with a loop meter before you trust it.