Short answer: hash marks in a numeric field mean the field cannot render its tag value, and the fault sits in one of 3 places: the runtime tag connection, the tag address and data type, or the numeric format pattern. Work them in that order. A ping and a successful download prove reachability and engineering access, which are the first 2 of the 3 layers a value crosses; the runtime connection is the third, and only its failure draws hashes. When every value on every screen turns to ###### at once, start at the shared runtime connection, because that is the cause in most cases. When only the largest values break, go straight to the format pattern: a field set to s999.99 cannot hold -1234.56. Until the number returns, treat each hashed field as an unknown value and confirm any interlocked limit at the PLC before you act on it.
What the pattern of hashes tells you
Look at which fields fail before you touch anything. The failure pattern sorts the 3 causes for you and points at the layer to test:
- Every PLC-backed value on every screen: the shared runtime connection is down. The alarm list will hold a connection event naming that connection.
- One screen, or one group of tags: the address or data type behind that group. Compare one failed tag with one working tag before editing anything.
- Only large magnitudes or long decimals: the format pattern. A pattern holding 3 integer digits draws hashes for any value that needs 4.
- Internal memory tags render, PLC tags show hashes: the acquisition path. The screen, the field and the renderer are all healthy.
- Reads return but an operator write shows hashes: the write range or a write-specific event. Check the attempted value against its permitted range first.
One deciding test covers the fourth row: point the field at an internal tag. If it renders, the field and its width are fine, and the fault sits upstream in the tag path.
Ping, download and runtime are three different layers
A value on screen crosses 3 layers, and the failed layer is usually the one you have not tested. Reachability: ping proves the panel and PLC pass packets between them, on a healthy plant LAN with a round trip under 10 ms. Engineering access: a download and go online prove your programming software talks to each device. Runtime acquisition: the panel's own configured connections read each tag on its cycle, typically 100 ms to 1 s, the cycle values the engineering software offers per tag.
Hash marks mean the third layer failed, and the first two can both pass while it does. The common packages configure the engineering connection and the runtime connection separately, so a project downloads cleanly while its runtime entry points at an old PLC address or a stopped connection. Check the runtime entry by name, not the entry the download used. Communication failures that survive a successful ping are common enough to have their own checklist.
The runtime connection: check it first
One connection usually serves every tag on the panel, which is why a connection fault hashes hundreds of fields at once. Open the alarm or event display. The runtime logs a connection event for each failed read, and the text names the tag and its connection. In the tag table, the affected connection shows flagged, marked red, for as long as the link is down. Then fix it in this order:
- Match the runtime connection's PLC address and protocol to the running controller. After an address change on the PLC, engineers often update the download entry and miss the runtime entry, which keeps the old address.
- Synchronize the HMI tags with the PLC tags, so addresses and types match the loaded program in one step.
- Re-download the project and watch the event list. Connection events stop within one acquisition cycle, usually under 1 s, of the link returning.
When the panel serves several PLCs or drives, count the devices against its connection budget for the HMI panel as well; a panel carries a limit on how many devices its connections serve. A link that drops only while one machine section runs points at cabling or interference, so move the check to the hardware side.
The tag address and data type
When one group fails while the rest of the panel renders, compare a failed tag with a working one. Go online in the PLC and read the live value first: that gives you the real magnitude, sign and type to match against. Open the failed field's tag and check its address against the variable in the running program; a renamed or relocated variable leaves the tag pointing at an address the PLC no longer serves.
Check the data type next. A 32-bit PLC integer, spanning -2,147,483,648 to +2,147,483,647, mapped onto a 16-bit HMI tag that tops out at +32,767 loses range or fails to transfer cleanly. The fast fix is the synchronize function: select the failed tags and synchronize them with the PLC tags, which pulls the address and type across together. Re-download, and the group returns on the next cycle. Rounding at the field is presentation, and it never repairs a wrong address.
The format pattern cannot hold the digits
When only the biggest values break, read the field's format pattern. In the convention the common engineering packages use, each 9 reserves one display digit and s reserves a sign position. The platform reference states the behavior plainly: the pattern 999.9 holds 3 integer digits and 1 decimal, and it shows 123.456 as 123.5, rounding the excess fractional digit.
A worked example from a position axis: the tag reads -1234.56 mm at full travel, and the field's pattern is s999.99.
- s reserves 1 sign position.
- 999 reserves 3 integer digits, so the largest magnitude the pattern holds is 999.99.
- 99 reserves 2 fractional digits.
- The value needs 1 sign + 4 integer digits + 1 point + 2 decimals.
The pattern holds 3 integer digits and the value needs 4, so the field draws ###### instead of -1234.56. Widen the pattern to s9999.99 and the same field renders the value on the next cycle. The pattern decides, not the on-screen box: widening the drawn field only helps once the pattern has the digits. Set every pattern from the tag's full engineering range, negative limit included, rather than from the value you expect on a good day.
Prove the fix and keep the values visible
Three checks close the job. First, the field shows the same value you read online in the PLC, matching to the pattern's last digit, so 0.01 with 2 decimals reserved. Second, the alarm list stays clear of connection events across a full 8 h run. Third, stop the connection deliberately once: an event should appear within one acquisition cycle, typically 100 ms to 1 s, which proves the display announces the next failure by name instead of hiding it behind hashes.
Three habits keep it fixed. Set each numeric pattern from the tag's minimum and maximum, sign included, while you build the screen. Synchronize tags after every PLC program change, before the download. Record the runtime connection settings with the panel's documentation, so the next engineer updates the right entry when an address changes.
When to replace the panel and re-house it
If the event list stays clean, the pattern fits the value and hashes persist, the fault is in the hardware. A display that reboots when operators touch it points to static discharge, and that failure has its own diagnosis and fix. A panel due for replacement, or one sitting where spray and splash hit the bezel, belongs in a stainless HMI housing: a gasketed rear cover, VESA 100 mounting at the back, and a front seal around the installed display, manufacturer rated IP65-type with the display installed (dust-tight, protected against water jets from a 6.3 mm nozzle at 12.5 L/min) and not UL listed.
Housings cover displays from 7 to 23.8 in; a 10.4 in panel PC, for example, fits this 10.4 in stainless HMI housing. Every housing is built to order and delivered in 10 business days, and the stainless HMI housings section lists all the display sizes. If you cut the mounting hole in a door yourself, check the cutout dimensions to verify first before the first chip; the cutouts, glands and HMI windows guide carries the fundamentals.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 10.4" HMI enclosure | 304 stainless | 10.2 x 12.44 x 3.6 in | IP65-type front seal with the display installed, manufacturer rated; not UL listed |
| 23.8" HMI enclosure | 304 stainless | 15.91 x 24.96 x 4.02 in | IP65-type front seal with the display installed, manufacturer rated; not UL listed |
| 10.1" HMI enclosure | 304 stainless | 8.72 x 12.66 x 3.48 in | IP65-type front seal with the display installed, manufacturer rated; not UL listed |
Questions
Do hash marks on every field mean the HMI lost the network?
Usually not. Ping proves packets pass between panel and PLC, typically with a round trip under 10 ms on a healthy plant LAN, and a download proves engineering access; those are 2 of the 3 layers a value crosses. Hash marks come from one of 3 causes, and the runtime tag connection is the first to check. Open the alarm list: a connection event per failed read names the faulty connection directly.
Why do only my largest process values show hashes?
The format pattern ran out of digits. Each 9 in a pattern reserves one digit, so s999.99 holds values from -999.99 to +999.99. A value of -1234.56 needs 4 integer digits and the pattern reserves 3, so the field draws hashes. Widen the pattern to s9999.99 and set it from the tag's full range, negative limit included. A 32-bit signed tag spans -2,147,483,648 to +2,147,483,647, so size the pattern from that, not from one good day.
Internal tags display fine but PLC tags show hashes, so what does that prove?
It proves the screen, the field and the renderer are healthy, because an internal tag needs no PLC read. The fault sits in the acquisition path, where the panel reads each tag on its cycle, typically every 100 ms to 1 s. Check the event logged for the failed reads, match the runtime connection's address to the running PLC, and synchronize the tags so address and data type match the loaded program.
How do I prove the fix holds?
Two checks on the first pass. The field matches the value you read online in the PLC to the pattern's last digit, 0.01 with 2 decimals reserved. The alarm list stays clear of connection events across an 8 h run. Then close the loop with the deliberate-stop test described in the body: an event appears within one acquisition cycle, usually under 1 s, which proves the display announces the next failure by name.