If you inherit a panel where every RTD cable shield lands on the 24 VDC negative bus, decide from two measurements and one drawing. Leave the wiring as built when the RTD card's connection diagram names DC common as its shield or reference terminal. Back that with the meter: DC negative under about 1 V to earth, measured under load. The termination is then the textbook one, because the shield sits on the zero-signal reference potential of the measuring circuit. Move the drain wires to the instrument-earth bar when DC common floats, when the drawing names chassis or earth, or when the offset runs a volt or more and swings with load. A shield landed on both grounds turns that offset into current: 0.5 V across the 2.5 Ω of a drain and its bond is 0.2 A, all day. Measure first, read the diagram second, move wires last.
What the readings tell you
Six patterns cover nearly every RTD panel you will open. Match the pattern to the cause before anyone lifts a wire.
- Stable readings around the clock — the termination is probably doing its job. Read the card's diagram and take the offset measurement anyway, because a quiet day hides coupling that shows up only under load.
- Jumps when a starter, drive or solenoid switches — shield current is sharing impedance with the measurement reference. Expect to find the drain and a load return in the same duct, or on the same negative terminal.
- Drifts with plant load — DC negative carries return current and the reference rides it, so the reading tracks the load.
- Drifts overnight, settles by morning — a floating DC common. Leakage and cable capacitance charge and discharge, and the offset to earth wanders with them.
- One channel noisy, its neighbours clean — that one cable is grounded at both ends, usually by a bonded gland or a strap in the field junction box.
- Everything noisy after a rewiring — the drains were moved to a bar with no defined bond to the card's reference.
Why DC negative can be the correct reference
Neither termination wins on its label; the card's measurement circuit decides. The instrumentation grounding texts compress the rule to one line: connect the shield to the zero-signal reference potential of the circuit, the point the signal is measured against. A DC negative bus is a power return that happens to carry that reference, and difference between a neutral and earth is worth ten minutes before you trust any return bus to be quiet.
The connection diagrams in RTD input card manuals land the drain wire on a shield or common terminal at the module connector. One card's wiring insert goes further: for a 2-wire RTD, land the third lead on module common, because that common is where the card measures from. When the card's reference lives on DC common, the shield belongs there too.
The user manual for a widely used PLC RTD input card adds the second rule: ground the foil shield and drain wire at one end only, then wrap and insulate the far end. One end gives coupled charge a path into the reference. The insulated far end keeps the shield from completing a loop through the structure, the same one-end rule VFD control cable shields follow.
The choice is forgiving on an RTD because the span is small and the card rejects what is common to both leads. A Pt100 on the IEC 60751 characteristic reads 100 Ω at 0 °C and 138.5 Ω at 100 °C, so the full span is 38.5 Ω. At 0.25 mA excitation that span is 9.6 mV. Even 1 µA of coupled shield current across a 2.1 Ω drain develops about 2 µV, which works out to 0.02 °C on the display. RTD inputs shrug off a shield on a healthy DC negative for exactly this reason.
The two buses only look identical on a DC meter. A straight conductor runs about 1 µH per metre [0.3 µH per ft], so 33 ft [10 m] of wire out to a remote earth bar is roughly 10 µH, about 6 Ω at 100 kHz against 0.21 Ω of DC resistance. A long, thin instrument-earth connection can be the worse path at switching frequency, next to the short, wide common bus the card already sits on.
Where a correct-looking termination goes wrong
Ordered by how often each one shows up in the field:
- A second ground at the field end. The drain was wrapped at the card but strapped in the sensor head or junction box, or a bonded gland made the contact. Any DC-negative-to-earth offset now drives a loop, and which end to ground decides whether the shield helps or hunts.
- A floating DC common. The bus the shields land on wanders against earth as leakage and capacitance come and go. Large floating DC systems pick up a soft ground sooner or later; until they do, the shield rides a moving node.
- A shared return. The drain landed on a negative terminal that also feeds coils or a drive control supply, so every switching event modulates the measuring reference. Even 10 mV of transient landing differentially reads as about 104 °C at 0.25 mA excitation (10 mV ÷ 0.25 mA = 40 Ω; 40 Ω ÷ 0.385 Ω/°C ≈ 104 °C).
- An instrument-earth bar nobody traced. The label says instrument ground; the meter says volts from earth, because the bond conductor is missing or corroded. What a real bond looks like is in the guide to enclosure grounding and bonding.
The first and last are five-minute meter checks. The middle two are the conditions the worked example separates.
Worked example: one loop, four numbers
The inputs are a hypothetical loop. Swap in your card's excitation current and your measured offset before acting:
-
Cable: 330 ft [100 m] of 18 AWG shielded RTD cable, at 6.4 Ω per 1000 ft, so the drain alone is 2.1 Ω
-
Bond path: 0.4 Ω of bus and bond from the drain terminal to earth
-
Module excitation: 0.25 mA, the value to read from the card's wiring insert
-
Offset: DC negative to earth, 0.5 V measured under load
-
Field end: drain wrapped and insulated at the sensor head, per the manual
-
Current driven by the offset: with one end terminated, the DC loop is open, so I ≈ 0 A. The 0.5 V stands across an insulator and drives nothing. The wiring earns its keep as built.
-
If a second ground is added at the head: I = 0.5 V ÷ (2.1 Ω + 0.4 Ω) = 0.2 A, continuous. The loop dissipates 0.2 A × 0.2 A × 2.5 Ω = 0.1 W, so a faintly warm drain is a real finding, and the current comes and goes with whatever moves the offset.
-
What current in the reference costs: 1 mV of differential noise at 0.25 mA is 1 mV ÷ 0.25 mA = 4 Ω of apparent resistance, and 4 Ω ÷ 0.385 Ω/°C ≈ 10.4 °C on the display.
-
The 1 V bench line, with its basis: a healthy bonded return sits at tens of millivolts — 3 A over 10 ft [3 m] of 12 AWG (1.6 Ω per 1000 ft) drops about 50 mV. A full volt means ohms where the bond should be, and 1 V across the same 2.5 Ω accidental loop would already drive 0.4 A.
Decision for the example: diagram names DC common, offset 0.5 V under load, field end insulated — keep the wiring and write the termination on the loop diagram.
The checks, in order
Thirty minutes with a meter and the card manual settles it. The cabinet-wide version of the same meter work is in control signal ground loop checks for a cabinet.
- Read the card's connection diagram. Find the terminal it names for the shield or drain: common, shield, or chassis/earth. Mark the page you relied on.
- Measure DC negative to earth at the panel bus, loads running. Tens of millivolts is a bonded system. A volt or more that swings with load means a missing bond or a load riding the reference.
- Measure shield to earth at the sensor head. Near 0 Ω means the field end is grounded, the second ground of cause 1. A correctly insulated drain reads open circuit.
- Trace the instrument-earth bar. Follow its conductor to the panel ground. One conductor, gland-tight, or you own a labelled wire instead of a reference.
- Compare the temperature trend with the load. A timestamped trend against starter events separates coupling from a real process change.
Lock off and prove dead before you open a gland or lift a termination at the head.
The fix for each finding
Each row ends in a wiring action, and the first row is the most common answer: nothing to move.
| What you find | What it means | What to do |
|---|---|---|
| Diagram names DC common; offset under the 1 V bench line; field end insulated | As designed | Leave it and note the termination on the loop diagram |
| Offset 1 V or more, swings with load | Bond missing, or a load rides the measuring common | Restore the DC-negative-to-earth bond at the supply; give the drain its own bus if it shares a loaded terminal |
| DC common floats by volts | The shield references a wandering node | Move the drains to the instrument-earth bar, one end only |
| Diagram names chassis or earth | The card was designed for an earthed shield | Move the drains to the instrument-earth bar |
| Shield reads 0 Ω to earth at the head | Second ground | Tape and insulate the field end; replace a bonded metal gland entry with an insulated one |
Keeping it right at the next build
Record two numbers at commissioning: the DC-negative-to-earth offset under load, and the shield-to-earth resistance at one sensor head. A loop that read 50 mV at handover and 0.6 V a year later has a corroding bond, and you find it on a trend instead of during a shutdown.
Name the reference terminal for every analog shield on the loop diagram, so the next rewiring starts from the card instead of from guesswork. Inside the box, give the analog drains their own terminal row or a small bus and keep their duct run away from the 24 VDC load returns. The rail and duct spacing that leaves room for this is in the backplate and DIN rail layout guide, the separation rules for the runs are in instrument signal cable enclosure layout, and the choice between an earth bar and a stud for a row of panel earth cables is its own decision with its own article.
When the job is a new box from us, list the shield bus and the terminal rows on the drawing for custom stainless enclosures and factory cutouts, so the rail and duct are drawn around them. We build to the approved drawing and deliver in 10 business days, counted from your approval of it.
When the panel deserves more than a rewiring
The shield-on-DC-negative question bites hardest where signals get weaker than an RTD. A 4-20 mA receiver measuring across a 250 Ω resistor sees 1-5 V for the span, so 1 mA of coupled shield current is 0.25 V, about 6 % of span, with no sensor resistance to dilute it. If the cabinet takes RTDs today and analog current or voltage inputs next year, plan an isolated instrument-earth bar, a dedicated shield terminal row, and duct segregation from the start.
Size the box for that hardware rather than for the module count alone: the enclosure selector sorts by environment, listing and DIN module count, then carries the result into a quote. Ground offsets between analog references sharing one cabinet are their own subject, covered in analog output ground offset inside a grounded enclosure. Order the shield row, the spare rail and the duct while the loop count still fits the space.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 6 × 6 × 4 in | 304 stainless | 6 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 8 × 6 × 4 in | 304 stainless | 8 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 10 × 8 × 4 in | 304 stainless | 10 x 8 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Is an RTD cable shield on DC negative wrong?
It is the correct termination when both conditions hold: the RTD card's wiring diagram names DC common as the shield or reference terminal, and DC negative measures under about 1 V to earth at the panel bus under load. The shield then sits on the zero-signal reference the card measures against. Check those two things and leave the wiring alone.
Why ground a shielded RTD cable at one end only?
Two grounds and any offset between them make a loop: 0.5 V across the 2.5 Ω of a 330 ft drain wire and its bond drives 0.2 A of continuous current, which warms the drain and moves the reading. So ground the foil shield and drain wire at one end only, then wrap and insulate the far end.
How much does 1 mV of noise move a Pt100 reading?
At 0.25 mA excitation, 1 mV of differential noise is 4 Ω of apparent resistance, and the IEC 60751 Pt100 characteristic moves 0.385 Ω per °C, so the error is about 10.4 °C. At 1 mA excitation the same millivolt is 2.6 °C. Shield current landing in the measurement reference reads as temperature, which is why the reference bus matters.
Should I bond DC negative to earth to make the shield termination standard?
Treat that as a change to the DC power system, not a wiring tidy-up. A floating 24 VDC supply may be floating by design, and bonding it reroutes every return current in the plant. When the card drawing names DC common and the offset is under about 1 V, leave the system as built. If DC common floats by several volts, move the drain wires to the instrument-earth bar instead.





