Space cable gland hole centers at least 1.5 times the larger gland's wrench-flat width apart. Two M40 glands need about 70 mm [2.75 in] on center; two M20s need 36–41 mm [1.4–1.6 in]. Two hex bodies that clear each other on a CAD sketch meet on the real wall. Once they touch, you cannot torque either locknut, and neither seal is worth anything. The fix is cheap on paper and expensive on a cut wall: measure the flat, multiply by 1.5, and mark the centers before the first hole is drilled. This article gives the rule and its basis, the distance below which the bodies physically overlap, the layout and cutting sequence for a stainless wall, and the cable room each entry needs inside. It ends with the escapes when the wall runs short: two rows, a clocked gland, a gland plate.
How far apart should two cable glands sit on a wall?
Set the hole centers 1.5 times the larger gland's wrench-flat width apart, which puts two M40 glands about 70 mm [2.75 in] on center and two M20 glands 36–41 mm [1.4–1.6 in] apart. The wrench flat is the number that matters because it is both the widest part of the gland and the face your spanner engages. Read the across-flats wrench size off the gland datasheet, take the larger of body and locknut, and multiply by 1.5. For two different sizes, use 0.75 times the two flats added together, which returns an equal pair to the same 1.5-times rule.
One stainless M40 datasheet lists 46 mm on the locknut and 50 mm on the body; sizing to the body flat gives 1.5 × 50 = 75 mm [3.0 in] between centers, and the locknut flat alone gives 69 mm. That spread is why the rule multiplies the measured flat rather than the thread.
| Gland thread | Across flats, common designs* | Centers, two alike (1.5 × flat) | Bodies touch below (1.155 × flat) |
|---|---|---|---|
| M16 | 22–24 mm | 33–36 mm [1.3–1.4 in] | 25–28 mm [1.0–1.1 in] |
| M20 | 24–27 mm | 36–41 mm [1.4–1.6 in] | 28–31 mm [1.1–1.2 in] |
| M25 | 30–33 mm | 45–50 mm [1.8–2.0 in] | 35–38 mm [1.4–1.5 in] |
| M32 | 36–41 mm | 54–62 mm [2.1–2.4 in] | 42–47 mm [1.7–1.9 in] |
| M40 | 46–50 mm | 69–75 mm [2.7–3.0 in] | 53–58 mm [2.1–2.3 in] |
| M50 | 55–60 mm | 83–90 mm [3.3–3.5 in] | 64–69 mm [2.5–2.7 in] |
*Across-flats wrench sizes for common brass and stainless metric glands; your gland's datasheet wins, and a wide-body M40 sits at the top of its row.
One gland installation guide tabulates minimum hole spacings from 20 mm at the small sizes to 75 mm at M40 and above, and the 1.5-times rule lands every M40 design inside that band. Treat the band as a floor, not a target: wrench swing sets the real pitch. How many holes the wall itself can carry is a separate limit, set by sheet strength rather than wrench room, and how many gland penetrations a wall can take covers that decision.
How close is too close before the glands touch?
Two hex bodies overlap corner-to-corner below 1.155 times the across-flats width, so two M40 glands with 46 mm flats touch below 53 mm [2.1 in] between centers no matter how you clock them. The 1.155 factor is hexagon geometry: corners reach 15.5 percent past the flats. At the floor the corners kiss; the wide-body M40 design clears from 58 mm [2.3 in] upward. Between the floor and the 1.5-times pitch sits the zone that fills punch-lists: the glands fit, but a socket has no swing, so the second locknut takes a thin open-end, and only if you engage it before the neighbor's gland enters the wall. Plan the tightening order along with the distance: bodies in, washers on, locknuts torqued one at a time.
What do you need before you mark the wall?
You need four things: the gland datasheet's wrench sizes and recommended hole diameter — 46 mm and 50 mm across flats on the M40 example — plus a hole saw to match, a straightedge and scribe, and the thin spanner that reaches a narrow hood.
- The datasheet numbers: across-flats wrench sizes for body and locknut, and the recommended hole diameter for a metal wall. The method behind that hole size is the same one the M20 hole-size guide walks through, and a plastic wall cuts differently.
- A drawn layout at the spacing rule, dimensioned from one datum edge. The fundamentals of a hole specification — size, position, sealing face, gland type — sit in the cutouts guide, and the cutout designer turns the sketch into a checked drawing you send with the quote.
- Cutting gear for stainless: pilot drill, hole saw, cutting oil, deburring tool, and a magnet or vacuum for the swarf.
- The wrench that will actually reach: a thin open-end for tight rows, a socket and extension where there is room. Choose it before you drill, because the wrench, not the thread, decides the pitch.
How do you lay out and cut the holes?
Lay the pattern out at 1.5 times the measured flat, cut each hole to the datasheet diameter, and tighten every gland fully before its neighbor's hardware goes on, because a locknut needs its full swing.
- Pick the face and keep the holes on the flat. Bottom entries suit a hood; keep every hole edge two sheet thicknesses clear of a bend, which is 3 mm [0.12 in] on a 1.5 mm [0.059 in] wall, and keep the hole inside the sealing face, off the door-gasket footprint. Leave 10 mm [0.39 in] of flat sheet around each hole as a shop rule for washer bearing and deburring.
- Measure the larger of the body and locknut flats with calipers and multiply by 1.5 for the on-center pitch; for a mixed pair, add the two flats and multiply by 0.75. Scribe the centers from your datum edge, and give a staggered second row the same 1.5-times distance to its nearest neighbors on the diagonal.
- Center-punch, pilot drill, then cut with a hole saw at slow speed with cutting oil, and deburr both faces. Cut into an enclosure that already carries wiring only with the supply locked out and absence of voltage verified.
- Vacuum the swarf out of the gasket channel and off the sealing face; a stainless sliver under the door gasket weeps on the first washdown.
- Fit each gland with its washer or O-ring in the datasheet's orientation, and hand-start the locknut square to the hole.
- Torque each locknut fully before the neighbor's gland goes in. Where a socket cannot swing, engage a thin open-end on the flats at an angle, or grip the round shoulder with a strap wrench — the same way stuck transmitter covers open without damage.
What do you check before you close the door?
Confirm four things before the door closes: each hole matches its datasheet diameter, the washer sits flat and compressed, the locknut holds its torque, and every cable runs straight out of its gland to a clamp.
- Hole diameter against the datasheet, with the thread passing without force.
- Washer and O-ring flat and untwisted, seated on clean metal; the seal lives there, not in thread compound.
- Daylight between neighboring hexes — about 16 mm between corners at the 69 mm M40 pitch. Corners touching means a hole moved.
- Locknut torque re-checked after the first heat cycle, because glands loosen under vibration and thermal movement; the datasheet's retention feature does that work.
- Every cable running straight to a clamp set close to its gland.
How much room do the cables need inside the box?
Clamp every cable within 300 mm [12 in] of its gland and run it straight out of the body, because gland installation guides call for both to keep lateral tension off the seal. Two M40 entries mean two cables of up to 32 mm [1.26 in] OD, since one common M40 design clamps 24–32 mm and the gland's clamping range has to match the cable. A cable datasheet's minimum bend radius runs 6 to 8 times the OD, so a 32 mm jacket wants roughly 190–260 mm [7.5–10 in] of swing before it turns toward the duct. On stainless wall-mount junction boxes that check decides the depth and whether the duct row sits a course lower, and it is cheaper done before you order. Outside, give each entry a drip loop so water sheds off the jacket.
Can you fit glands closer by staggering or turning them?
Yes: clock one gland 30 degrees so a flat faces the neighbor's flat, or stagger the holes onto two rows, and the just-touch distance for a 46 mm hex drops from 53 mm [2.1 in] to 46 mm [1.8 in]. Clocking buys overlap margin and no wrench swing, so the 1.5-times pitch still governs any pair you plan to torque. A two-row stagger keeps 1.5 times the flat on the diagonal, which shortens the horizontal run of the pattern without crowding any pair. Past four entries on one face, or on a narrow hood rail, a bolted gland plate carries the crowd instead of the sealing wall and turns every hole into machined work. Fewer holes beat clever spacing too: two cables share one gland when the gland is documented for it, so it is worth checking before drilling two.
Which mistakes cost the wrench room or the rating?
The common failure is a layout drawn from thread size instead of the measured flat: two M40 holes at 45 mm [1.8 in] centers look right on the drawing and wedge the bodies together on the wall.
- Pitch from the thread number. M40 does not mean 40 mm centers; the measured across-flats width sets the pitch.
- A hole through the bend radius or the gasket line. The cut sits outside the seal, and washdown water finds it on the first shift.
- A mis-drilled hole closed with sealant alone; a wrongly drilled hole has graded fixes before that.
- Locknut tight but washer missing or twisted. The gland holds and the box still takes water.
- Assuming the rating rides on the hole pitch. Our walls are rated NEMA 4X / IP66 by the manufacturer; not UL listed, and the rating survives on approved glands, washers and torque.
- Certified rooms run by gland rules. On a certified hazardous-location enclosure, the certificate sets hole spacing, not the gland datasheet — and we do not build certified boxes.
- Crowding discovered on site. Order the pattern cut at the works through the cutout designer, and the box arrives machined, delivered in 10 business days from your approval of the drawing.
Decision: measure the flat, multiply by 1.5, and keep that pitch between every neighboring pair — about 70 mm for the M40 pair, 36–41 mm for M20s. Clock or stagger when the wall is short, move to a gland plate past four entries, and let the works cut the holes when the pattern is tight.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 14 × 8 in | 304 stainless | 16 x 14 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
What spacing applies when two glands are different sizes?
Use 0.75 times the sum of the two across-flats widths. A 50 mm-flat M40 body beside an M25 with a 30 mm flat gives 0.75 × 80 = 60 mm [2.4 in] between hole centers. Keep the plain 1.5-times rule between neighbors of the same size, so a row of M20s on 24 mm flats sits at 36 mm [1.4 in] centers.
Does hole spacing change the NEMA 4X or IP66 rating?
Spacing itself does not; the sealing hardware does. The rating holds when each gland is the enclosure maker's approved accessory for that rating, the hole matches the datasheet diameter, the washer or O-ring seats flat and the locknut is torqued. Our stainless boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed, and a field-drilled wall seals only as well as the glands you fit.
Can two cables share one M40 gland instead of two holes?
Only when the gland maker documents it. A common M40 design clamps a single cable of 24–32 mm [0.94–1.26 in]; two smaller cables fit some glands through documented reducing or multi-hole inserts, and each seal must match its own cable diameter. If the datasheet lists one cable, drill two holes at the spacing rule instead.
How close can a gland hole sit to a bend or the door gasket?
Keep the hole edge two sheet thicknesses clear of any bend — 3 mm [0.12 in] on a 1.5 mm [0.059 in] stainless wall — and keep the hole, washer and locknut entirely on the flat sealing face, off the gasket footprint. As a shop rule, leave 10 mm [0.39 in] of flat sheet around every gland hole for washer bearing and deburring.