Yes, you can put the new conduit entry on the right, and the box keeps its outdoor rating if the entry is sealed with wet-location hardware. For a 1/2 in trade-size fitting, drill a 7/8 in [22 mm] hole, center it at least 1 in [25 mm] from every edge, seam and screw boss, and fit a connector rated for wet locations. The water seal lives in the fitting, not in the plastic, so hole size and sealing hardware decide the outcome. A step bit run slow cuts the cleanest hole; a hole saw of the same size also works. The conical bit that cuts threads as it drills is a combination drill-tap, and it is a metal-panel tool: plastic boxes clamp through-fittings with a locknut, and thin plastic walls hold no machine thread.
Where the new hole goes
Three placement rules keep the box sound and the rating intact. First, stay on the flat wall between the corner ribs and the screw bosses, where the plastic drills cleanly and the locknut seats. Second, hold the hole center the same clearance from every edge, seam and boss. Third, space a second hole the same distance from the first one's edge, so two locknuts sit flat instead of fighting each other. If you are laying out several entries, how many gland penetrations an enclosure wall can take works through the spacing.
That clearance buys room for the hardware. A 1/2 in fitting's locknut spans about 1 1/8 in [29 mm], so its edge reaches 9/16 in [14 mm] from the hole center. At the spacing from a seam, the hole's near edge lands 9/16 in [14 mm] from the seam, and the locknut's edge lands 7/16 in [11 mm] from it. That strip is the flat the nut and its gasket clamp onto.
Worked example: a floodlight circuit is being tapped through a 6 x 6 x 4 in [150 x 150 x 100 mm] outdoor plastic box with entries on the left, bottom and top. The right flat gives about 4 in [100 mm] of clear wall. Center the new hole 1 1/4 in [32 mm] from the right seam and 2 in [50 mm] below the top corner: the hole edge sits 13/16 in [21 mm] from the seam, the locknut edge 11/16 in [17 mm], and a fifth entry later still fits. The circuit side of that tap — which conductor, which breaker — is its own question: tapping power for an outdoor floodlight.
Pick the face with water in mind:
| Face | When to use it | What the entry needs |
|---|---|---|
| Vertical side | Your default for a new run | Wet-location fitting, locknut inside |
| Bottom | Cable or flex drops away cleanly | Fitting plus a drip loop one conduit width below |
| Top | Last choice, since water rides the conduit down | Rain-tight hub and a drip loop: conduit hub or sealing locknut for top entries |
Before you drill, read the molded label for the box's type; outdoor plastic boxes are commonly marked Type 3R or Type 4X. The marking and the fitting together decide what the box survives afterwards, and whether a field-cut hole affects the rating covers the principle.
What you drill with
A step bit makes the cleanest hole in plastic; twist drills and hole saws grab thin walls and tear the exit side. Pre-drill a 1/4 in [6 mm] pilot hole first, because it gives the step a track to follow and saves the bit's small stages for real work. For the largest trade sizes, switch to a hole saw centered on the pilot hole; electricians' hole saws often carry a stop that limits the plunge. Support the wall while you drill: take the box off the wall when the fasteners allow, or brace a wood block against the inside face, because a flexing wall cracks at the hole.
Hole sizes, with their basis in UL 50's knockout table (Table 71-1A), which standardizes the diameters the fittings are built for:
| Fitting trade size | Hole to drill | Pilot hole | Typical use |
|---|---|---|---|
| 1/2 in | 7/8 in [22 mm] | 1/4 in [6 mm] | Lighting tap, floodlight feed |
| 3/4 in | 1 1/8 in [29 mm] | 1/4 in [6 mm] | Larger feed, spare capacity |
| 1 in | 1 3/8 in [35 mm] | 3/8 in [10 mm] | Main feed with spares |
Metric glands use their own diameters; M20 gland hole sizes for plastic and aluminum lists them, and the cutouts and glands guide holds the background.
Cut the hole in six steps
- Open the door, confirm the circuit is dead at the box with a tester, and loosen the box from the wall if you can. If it stays up, brace the wall from inside with a wood block behind the drill point.
- Mark the center on the flat you chose, the full clearance from every seam, edge and screw boss, on a vertical face where you have the choice.
- Drill the pilot hole square to the wall, slow and steady.
- Open it with the step bit one stage at a time, stopping at the stage the table lists for your fitting. Test-fit as you near the size, because plastic gives you one chance at a tight fit.
- Deburr both faces with a half-round file or a sharp knife so the fitting's gasket lands on flat plastic.
- Push the fitting through, hand-start the locknut, and snug it with pliers; hand-tight plus a half turn is plenty in plastic. Full contact all the way round means the seal will be too.
Vacuum the shavings before you close the door. Loose swarf under the door gasket is a leak path you created for nothing.
Seal the entry to the box's rating
The cut wall seals nothing by itself: the box now performs at whatever level the fitting in the new hole provides. A rain-tight metallic hub with its gasket keeps a Type 3R plastic box where it was. A plain indoor snap-in connector pulls the whole assembly down to that connector's level, usually dripping-water performance, so buy the fitting before you buy the drill bit. Field-drilled conduit entries that keep a NEMA 4X rating shows the same logic on stainless.
For flex out to the floodlight, a liquid-tight connector with its sealing ring is the standard choice, and the wet-location flex connector for an outdoor box compares the types. Under the flange of a non-gasketed connector on a 3R box, lay a thin bead of neutral-cure silicone. Use neutral cure on polycarbonate, since acetic sealants craze it; on a 4X plastic box, rely on the fitting's own O-ring so the rating stays traceable to hardware.
While the drill is out, a 3R box that takes wall-run spray also wants a drain. NEC 314.15 permits field-drilled drainage openings of 3-6 mm [1/8-1/4 in] in boxes listed for damp or wet locations, and one at the lowest point is enough. A sealed 4X box earns its marking by having no drain at all. Drip loops, drain placement and the rest of the weatherproofing set live in sealing an outdoor junction box.
Checks when the entry is finished
- Locknut seat: full contact all the way round, the fitting shoulder meeting its gasket, and the conduit taking a firm pull without shifting.
- Hose test: run water over the entry from about 2 ft [0.6 m] for two minutes, then open the door. A dry interior passes; a damp ring under the locknut means re-seat the gasket and snug the nut again.
- Door seal: wipe the gasket land clean and confirm the door closes on it evenly.
- First rain: one look inside after real weather tells you more than the hose did.
The mistakes that cost the rating
- One step too far and the gasket has nothing to sit on. The repair is a gasketed blanking plug in the oversize hole and a fresh hole the full clearance away from it.
- A hole started at a rib or screw boss cracks the box when the locknut tightens, and the crack grows with sun and temperature cycling. Stay on the flat between them.
- Bring the run in from the side, or fit a rain-tight hub on top with a drip loop; water follows an unsealed conduit straight into the box you just sealed.
When to order the holes instead of cutting them
One field entry suits a plastic box; five does not. When the layout has glands, a display opening and pushbuttons, draw the openings and let them arrive cut. The cutout designer lays holes, glands and display openings on any face, checks their spacing, and sends the drawing with your quote request. A custom stainless box is delivered in 10 business days anywhere in the world, counted from your approval of the drawing, and stainless gives you flat walls with no molded bosses to dodge. Our enclosures are rated NEMA 4X / IP66 by the manufacturer and not UL listed. For small splice and pull jobs, the stainless junction box sizes page lists the wall-mount boxes with their panels and depths.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 6 × 6 × 4 in | 304 stainless | 6 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 14 × 8 in | 304 stainless | 16 x 14 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can I drill a new conduit hole anywhere on an outdoor plastic box?
Yes, on any flat wall between the corner ribs and screw bosses, with the hole center at least 1 in [25 mm] from every edge and seam. That spacing leaves the 1 1/8 in [29 mm] locknut of a 1/2 in fitting about 7/16 in [11 mm] of flat to clamp against. Curved lids and ribbed corners are the faces to leave alone.
What size hole does a 1/2 in conduit fitting need?
Drill 7/8 in [22 mm], the knockout diameter UL 50's Table 71-1A standardizes for 1/2 in trade fittings. A 3/4 in fitting takes 1 1/8 in [29 mm] and a 1 in fitting takes 1 3/8 in [35 mm]. Pilot-drill first, then open the hole with a step bit one stage at a time.
Can I tap threads in a plastic box so the fitting screws straight in?
Use through-fittings instead. Combination drill-taps cut machine threads that need metal to hold; in a plastic wall they strip and the fitting pulls out. A connector body passes through the hole and a locknut clamps it, or a self-tapping plastic hub winds into a plain hole cut to its size. Both grip by pinching the wall, so the thread question never arises.
Will a field-drilled hole lower the box's weather rating?
Only through the fitting you mount in it, because the plastic wall seals nothing on its own. A rain-tight hub with its gasket keeps a Type 3R plastic box performing at 3R, while a plain snap-in connector pulls the assembly down to dripping-water level. A 3-6 mm [1/8-1/4 in] drain at the low point gives any water that gets in a way out.