Two cables through one cable gland: when it works

One cable gland seals one round cable. Two cables through a single gland only work with a multi-hole seal sized to each cable, and flat or mixed cables usually defeat it. If the cables differ in shape or you need anchoring strain relief, cut a second entry and fit a second gland instead.

NEMA4 Enclosure engineering team · Published October 29, 2026 · 6 min read

A cable gland is built around one cable. Squeeze two into a standard gland and the seal cannot close the gap between them, so water and dust have a path straight in. Two cables can share a single wall entry, but only with a multi-hole seal that grips each cable separately. When the cables are different shapes, one round and one flat for example, that rarely works, and the reliable answer is a second entry with a second gland.

What a standard gland actually seals

A normal gland has a rubber seal with one hole. When you tighten the body, the seal compresses onto the cable's outer sheath. The seal works because the rubber fills the annular gap between the hole in the gland and one round cable of the right diameter.

That tells you the two conditions that must hold:

  • The seal must contact the cable's outer sheath, all the way around.
  • The cable diameter must fall in the gland's clamping range.

Two cables in one hole break the first condition. The rubber cannot wrap fully around either cable, so the joint between them stays open. The gland may look tight, but a hose test or a rainstorm will find the gap. Sizing rules for single cables are covered in how to size a cable gland for an RJ45 connector, and the same clamping-range logic applies to every gland you fit.

There is a second job people forget: the gland also anchors the cable. Pull on the cable and the gland should take the load, not the terminals inside. Two loose cables in one entry give you no anchoring at all. The article on installing a cable gland without losing the rating covers how much this matters in practice.

When two cables through one entry works

Sharing an entry is legitimate when the gland is designed for it:

  • Multi-hole seals. Some glands accept an insert with several holes. Each cable sits in its own hole, and the compression plate squeezes the whole stack. Every hole must match its cable; an empty hole needs a blanking plug.
  • Matched sizes. This works best with two round cables of similar diameter, for example two 6 mm (0.24 in) signal cables through one M25 (PG21) entry.
  • Follow the manufacturer's instructions. The combination of gland, seal and cable count is what the rating rests on. Anything improvised does not.

If you go this route, check the fill. A hole for a cable at the small end of the range grips better than one at the large end, because there is more rubber to compress. And keep the entry below the enclosure, never facing up, so water running down the cables does not pool on the fitting. The reasons are set out in why cable glands should not face up on an outdoor box.

Where two-cables-one-gland fails

The common failure cases are the ones worth spelling out before you order:

  • Flat or rectangular cable. Ribbon and flat power cables cannot be gripped by a round hole. The rubber contacts two edges and seals two lines, not a circle. Specialised sealing frames exist for flat cable, but a standard gland will not do it, and purpose-made hardware for very flat cable is often costly relative to the job.
  • One round and one flat together. This is the worst combination: the seal cannot suit both shapes, and the flat cable can slide in the entry with no anchoring.
  • Very different diameters. A 3 mm (0.12 in) thermocouple lead and a 12 mm (0.47 in) supply cable through one multi-hole seal means the small cable is barely gripped. Vibration works it loose within a season.
  • Cables that get serviced. When one cable will be swapped or removed, a shared seal means opening the entry and breaking the seal on the cable that stays.

In each of these cases, the honest answer is a separate entry per cable, or a different sealing method entirely.

The reliable alternatives

When a shared gland will not grip, choose among three options.

Second gland, second cutout. The straightforward fix. Each cable gets its own correctly sized gland, its own grip and its own future serviceability. On a stainless box, that means a second hole in the wall or, better, in a gland plate. A gland plate lets you add, move or resize entries without touching the enclosure body, which is why we cover when to specify one in stainless steel enclosures with a gland plate.

A custom cutout from the start. If you know the cable mix at design time, put the entries on the drawing. Our custom enclosures take any cutout pattern you specify, so two M20 (3/4 in NPT equivalent) entries sit where the wiring wants them instead of where the blank box happened to allow. The cutouts, glands and HMI windows guide explains what a cutout drawing needs to carry. You can also lay out the entries yourself in the enclosure builder, which takes quick cutouts for cable glands before you send the drawing for approval. Once the enclosure is in service, adding openings means new holes in stainless, and cutting changes the finish and can cost the rating, so design the entries in before the box is made.

Terminations instead of through-cables. For mixed or awkward cables, terminate before the wall. Land the flat cable on terminals or a short round jumper inside a small adjacent box, and bring one round, gland-friendly cable into the main enclosure. This costs space and parts, but it gives you a real seal and real strain relief on both sides.

What it changes in a real panel

The decision shows up in three places.

The rating you can claim. Our enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed. That rating is only meaningful with the entries sealed the way the gland and seal makers document. Two cables wedged into a single-hole gland means the box no longer performs to that rating, whatever the label says. NEMA itself does not test or certify enclosures; the type number describes what the manufacturer rates the design to withstand.

Strain relief and safety. An unanchored flat cable eventually works on its terminals. On a supply cable, a loose sample or sense conductor can put line voltage where you do not expect it. Separate glands with correct clamping keep each cable fixed under its own pull.

Condensation and long-term sealing. A partially sealed entry is the classic path for moisture that condenses inside on cold nights. If you are chasing water or corrosion inside a box, check the cable entries first; the article on moisture in an outdoor enclosure and corroded connectors walks through that diagnosis.

What to specify

Before you order the enclosure or the glands, write down:

For a background read on gland selection for conduit-style entries, the article on selecting cable glands for plastic conduit end seals covers the same clamping principle from the conduit side.

The short version: two round cables of similar size can share one gland if the seal is made for it. A round cable and a flat cable cannot. Give the flat cable its own entry, its own gland or a proper sealing frame, and put the entries on the drawing before the box is cut.

Questions

Can I run two cables through one cable gland?

Only with a multi-hole seal or a gland fitted with a divider insert, where each hole grips one cable at its outer sheath. A standard single-hole gland around two loose cables leaves a leak path between them and keeps no rating. If the seal cannot grip both cables, cut a second entry and fit a second gland.

How do you seal a flat cable through an enclosure wall?

A standard round-cable gland cannot compress a flat cable into a reliable seal, and the cable can slide in the entry. Use a sealing frame or grommet strip made for flat cable, or terminate the flat run to round, individually sealed conductors before they enter. Mount the entry so water cannot run along the cable into the wall.

Does putting two cables in one gland keep the IP rating?

Only if the gland and seal are rated for that use and every hole is filled or blanked to match the manufacturer's instructions. Any improvised combination, such as two cables squeezed into a single-hole gland, voids the rating the manufacturer gives the box. Ours are rated NEMA 4X / IP66 by the manufacturer; not UL listed, and that rating assumes the entries are sealed as documented.

Is one big gland better than two small glands?

One large gland with a multi-hole seal means one hole in the wall and one part to order. Two small glands give each cable its own grip, anchor it against pulling, and make future changes easier. For two round cables of similar size, a multi-hole seal works well; for mixed round and flat cables, two separate entries are usually cheaper and more reliable.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Configure it in the builderRequest a custom quote

Keep reading

More on layout and installation

All articles

Buying guides

The guides behind this answer

All guides