Short answer: the study is right, and your grounding is doing its job. IEEE 1584 calculates incident energy from a three-phase arcing fault, and the impedance you added sits in the neutral-to-ground path, which stays idle during a three-phase fault. In the worked example below, a 1000 kVA, 480 V transformer still delivers 20.9 kA of bolted three-phase fault current with the resistor installed, so the printed energy stays where it was. What the resistor did is cut line-to-ground faults from about 21 kA to 5 A, which stops most arcs from starting at all. Keep both facts in the report: the unchanged three-phase number, and the grounding control written beside it.
Why did the incident energy stay the same after I added impedance grounding?
Because the calculation never sees the resistor: the study feeds IEEE 1584 the three-phase bolted fault current, and on the example transformer that input reads 20.9 kA with the grounding impedance in place exactly as it did without it.
The software did what the standard tells it to do. Incident energy, arcing current and the arc flash boundary all come from one modeled three-phase event, and the equations ask for the inputs that describe that event. An unchanged value is the correct result, so treat it as confirmation. Two checks make it airtight: the transformer grounding arrangement in the model matches what you installed, and the printed value comes from the three-phase case. Both true, you can stop hunting for a hidden setting, because the 2018 equations contain none for grounding.
What fault does the IEEE 1584 calculation actually model?
A three-phase arcing fault in an enclosure: the guide's equations take the three-phase bolted fault current, the voltage, the electrode gap and the box dimensions, and they are valid from 208 V to 15 kV line-to-line.
The outputs are arcing current, incident energy and the arc flash boundary, the distance at which the energy falls to 1.2 cal/cm², the onset of a second-degree burn. The required input is the three-phase bolted current, full stop. A ground-fault current is a different quantity in a different path; feed the study a single-digit ground-fault figure and it prints a meaningless number. Below 208 V, a 120 V control panel for instance, the guide points to theoretical models instead, and the 120 V control panel fed from an MCC has its own answer.
Where does the grounding impedance sit in the fault path?
Between the transformer wye point and earth, in the zero-sequence path: a balanced three-phase fault drives no current through it, and a line-to-ground fault drives all of its current through it.
Run the arithmetic on an illustrative example, a 1000 kVA delta-wye transformer with a 480 V secondary and 5.75 % impedance, solidly grounded today with a neutral resistor proposed. Put your own nameplate values in place of these before you quote anything.
- Secondary full-load current: 1,000,000 VA ÷ (1.732 × 480 V) = 1203 A
- Bolted three-phase fault at the terminals: 1203 A ÷ 0.0575 = about 20,900 A, call it 20.9 kA
- Bolted line-to-ground fault, solidly grounded: about the same figure, because the delta primary makes the transformer its own zero-sequence source
- Neutral resistor for a 5 A ground fault: 277 V ÷ 5 A = 55 Ω
- Bolted three-phase fault with the resistor in circuit: unchanged
| Quantity | Solidly grounded | With the 5 A resistor |
|---|---|---|
| Three-phase fault at the panel | 20.9 kA | 20.9 kA |
| Line-to-ground fault at the panel | about 20.9 kA | 5 A |
| Ground-fault current reduction | — | about 4,200 to 1 |
| Study output at 18 in, 0.1 s clearing | 8.4 cal/cm² | 8.4 cal/cm² |
The 8.4 cal/cm² is this example's assumed study output at an 18 in working distance with a 0.1 s clearing time. The software prints it once without the resistor and once with it, identically, and 8.4 sits just above the 8 cal/cm² arc rating that covers NFPA 70E's second PPE category. That identical pair of lines is the whole answer to the question.
Does impedance grounding reduce arc flash risk at all?
Yes, at the point where arcs begin: IEEE 142 grounding practice is built on the observation that most faults start line-to-ground, and holding those faults to single-digit amperes keeps them from escalating into the three-phase event the label describes.
On a solidly grounded system, a line-to-ground fault pours kiloamperes through the arc, ionizes the path and involves the other phases within cycles. Held to a trickle, the same fault barely warms its point of contact; it stays a maintenance item you locate from the ground-fault alarm and repair on schedule. That is fewer arc-flash events over the plant's life, real risk reduction the three-phase equation never prices in. The trade is that the system stays energized during a ground fault, so the resistor needs monitoring and an alarm people answer. A low-resistance scheme holds the same fault to a few hundred amperes when you need selective tripping, and the three-phase number ignores that too.
Work on the panel by the label as printed. The three-phase hazard is fully intact, so de-energize, lock out and prove absence of voltage before your hands go in the box.
What changed between the 2002 and 2018 equations?
The grounding term went away: the 2002 edition shifted its three-phase incident energy slightly between grounded and ungrounded systems, and the 2018 rewrite dropped the distinction, so the model now ignores grounding entirely.
Two consequences follow. An old 2002-era study may show a small grounding-related difference that a 2018 re-run will not reproduce, and the gap is the equation set rather than your network. And in a 2018-based study, toggling the grounded or ungrounded flag changes nothing at all, so read which edition your software applied before you credit a change, or its absence, to the grounding. Run the 2018 equations and expect grounding to be invisible in the number.
What does change the number on the label?
Clearing time, working distance, electrode configuration and the enclosure you enter: the 2018 equations correct for box height, width and depth, so those inputs move the printed value far more than any grounding change will.
- Clearing time is the biggest lever. Incident energy scales with duration at a given arcing current, so halving the clearing time halves the energy; a maintenance setting on the trip unit or a current-limiting fuse does more than the resistor ever could.
- The box dimensions you enter matter. Shallow enclosures calculate lower incident energy, and enclosures wider than 49 in follow their own entry rule. Measure the box you actually build.
- Barriers work physically. Separating equipment into smaller compartments is one of the few changes that drops a whole category rather than a decimal.
- A junction box carrying several circuits carries the worst circuit's label, so splitting circuits between boxes gives each its own number.
When those changes point you at a different box, the enclosure selector checks the inside height and width you will be modeling.
How should the report show the grounding benefit?
On its own line beside the three-phase result: state the unchanged incident energy from the model, then the control itself, line-to-ground current held to 5 A by a 55 Ω neutral resistor on the transformer wye, with monitoring and alarm.
What your software can show today is the ground-fault case, run as a short-circuit result: about 21 kA before the resistor and the target figure after. Attach that table to the arc-flash study and the benefit is documented in numbers, roughly 4,200 to 1. Keep it beside the incident-energy figure rather than inside it, and put four things in the package:
- The equation edition, 2018, so nobody hunts for the 2002 grounding term
- The modeled case named as three-phase, with its working distance
- The grounding note with resistor ohms and target current
- The ground-fault detection and alarm scheme that makes the limited fault current survivable
The label on each disconnect keeps the three-phase value, including a disconnect that sits under lockout. And whatever lives at the wye point, the enclosure bond and equipment grounding conductor still carry the fault current that does flow; system grounding never weakens them.
The decision by case:
| Your case | What to do |
|---|---|
| Solidly grounded wye today | Label from the three-phase case; nothing about grounding to note |
| High-resistance grounding installed | Same label; add the ground-fault note, the short-circuit table and the alarm scheme |
| Old study shows a small grounding difference | It is the 2002 term; re-run the 2018 equations |
| Asked to prove the line-to-ground reduction | Report the before-and-after short-circuit run, about 4,200 to 1 |
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Will high-resistance grounding lower the number on my arc flash label?
It will not, and the unchanged value is the correct result. The label reports the modeled three-phase event, which keeps its 20.9 kA basis in the worked example and its 8.4 cal/cm² output. The reduction you bought lives elsewhere: line-to-ground faults fall from about 21 kA to 5 A before they can escalate into the three-phase arc the label describes.
Can the 5 A ground-fault current go in as the study input?
The calculation takes the three-phase bolted fault current as its input, so a ground-fault value of a few amperes returns a meaningless incident energy. Ground-fault current belongs to the zero-sequence path; the three-phase quantity belongs to the phase conductors. To price a single-phase arc on its own, use a model built for single-phase events and state its assumptions in that case.
Does an impedance-grounded system still need arc flash PPE for live panel work?
Yes, by the label as printed. The three-phase hazard is fully intact in the example, and 8.4 cal/cm² at 18 in still needs arc-rated clothing above everyday cotton. De-energize where you can, lock out and prove absence of voltage before opening the door. The grounding control prevents faults from starting; it changes nothing once one burns.
What should the study report say beside the arc flash value?
One line with numbers: line-to-ground fault current held to 5 A by a 55 Ω neutral grounding resistor on the transformer wye, with detection and alarm, plus the ground-fault short-circuit table showing about 21 kA falling to that limit. Name the 2018 equation edition, since the 2002 set still reacted slightly to grounding and 2018 ignores it.





