Short answer: yes, with one condition attached. The simplified low-voltage breaker equations in IEEE 1584 give you a screening incident energy when the trip curve never arrives, and they lean high against a healthy breaker whose instantaneous element clears the arcing current in 2 to 3 cycles (0.033 to 0.05 s at 60 Hz). They break exactly where the danger lives. Whenever clearing rides a time-delay band, energy scales linearly with duration, so 0.3 s of clearing carries six times the energy of 0.05 s. Run the screen, then check the arcing current against the pickup before the number goes near a label.
What the simplified equations give you
IEEE 1584 walks a study through nine steps: collect the system data, settle the modes of operation, determine the bolted fault currents, and carry on out to incident energy and the arc-flash boundary. At the device step you normally feed in a time-current curve for the breaker that clears the fault. The simplified equations for low-voltage breakers, carried in the guide since the 2002 edition, cover the case where that curve never turns up. Bolted fault current goes in; incident energy comes out for a typical breaker of that class, with an assumed arcing current and an assumed clearing time folded in. Contractors and service groups use them to flag dangerous panels fast. A preliminary number while the real data is chased is what the guide means them for.
The fit behind those equations has bounds worth knowing. The 2018 edition spans 208 V to 15 kV. Its low-voltage band, 208 to 600 V, is fitted for bolted fault currents from 500 A to 106 kA. Equipment below 240 V needs no arc study at all unless a 125 kVA or larger low-voltage transformer feeds it. The equations carry conditions in their notes, so read those notes and keep your voltage and your breaker class inside them.
Which way the error runs
Two facts of the model set the direction. Incident energy scales linearly with clearing time — the empirical fit is normalized to a 0.2 s arc, so doubling the duration doubles the energy. And the breaker answers to arcing current, which sits below the bolted value, roughly half to two-thirds of it through the low-voltage range.
When the arcing current lands well above the instantaneous pickup, the magnetic element clears in 0.025 to 0.05 s (1.5 to 3 cycles). The assumed time sits at the slow end of real behavior, so the screen leans high — the safe side. When the arcing current lands near or below the pickup, clearing jumps onto the delay bands. Figure 0.1 to 0.4 s on a set short-time delay, and seconds in long-time. The screen assumed cycles and the panel delivers tenths of a second, so the number runs low by the ratio of those two times.
The 2018 edition built its own warning into the arithmetic. It repeats every calculation at 85 percent of the arcing current and keeps the higher energy, because less current can clear slower and hurt more. Copy that habit into your screen: compare the pickup against 0.85 times the arcing current, and the margin tells you which world the panel lives in.
| Your case | Realistic clearing | Screened value | What you do |
|---|---|---|---|
| 0.85 × arcing current well above the pickup | 0.025–0.05 s (1.5–3 cycles) | leans high | label with it |
| arcing current within 20 percent of the pickup | one setting either side of instantaneous | swings either way | get the curve, recalculate |
| instantaneous off, 0.3 s short-time delay | about 0.33 s | 6.6× low | recalculate first |
| breaker of unknown service history | longer than assumed | runs low | test data or a replacement first |
| below 240 V, all transformers under 125 kVA | out of the study | none calculated | leave it out of the study |
One 480 V panel, two answers
Work this through with example numbers and swap every input for your own before anything is labeled. The panel runs at 480 V, fed from a 750 kVA transformer at 5 percent impedance. Full-load current is 750,000 / (√3 × 480) = 902 A, so the infinite-bus fault at the secondary is 902 / 0.05 = 18 kA. A 100 ft [30 m] feeder and the source behind it leave 14 kA at the panel bus. The study's arcing current is 8.9 kA, 64 percent of bolted, and the simplified screen prints 3.2 cal/cm² at the guide's default working distance for a panel, 18 in [455 mm], on an assumed 0.05 s clearing.
The feeder: trust the screen
The feeder breaker is a 225 A thermal-magnetic unit with its pickup at 10 × 225 A = 2,250 A. The arcing current is 8.9 / 2.25 = 4 times that pickup, so the magnetic element clears in about 2 cycles and the screen's 0.05 s is the slow end of what this breaker does. Run the 85 percent check: 0.85 × 8.9 = 7.6 kA, still 3.4 times the pickup, still instantaneous. The screen runs high or close here, so 3.2 cal/cm² can go on the label, and arc-rated clothing rated above it covers the exposure.
The main: recalculated
The same fault cleared by the 400 A main tells a different story. Its electronic trip unit runs long-time and short-time only, with the instantaneous turned off for selectivity. The short-time delay sits at 0.3 s, and contact parting takes total clearing to about 0.33 s. Energy scales linearly with time: 3.2 × (0.33 / 0.05) = 21 cal/cm². One trip setting moved this panel past 8 cal/cm², the rating of a common arc-flash suit, and up toward the 40 cal/cm² line where many facilities stop energized work entirely. More current is available at the main than at the feeder as well, so 21 cal/cm² is the floor of the range.
That is the whole judgment. The screen is trustworthy in the first case and dangerous in the second, and the pickup test tells you which one you are standing in.
What the number changes in the enclosure
The label is the first thing it changes. NFPA 70E puts the incident energy, the arc-flash boundary and the working distance on the equipment, so a screened 3.2 and a recalculated 21 are two different doors, not two versions of the paperwork.
Since 2018 the enclosure itself is an input to the model. You pick an electrode configuration — vertical electrodes in a box, vertical with a barrier, or horizontal in a box — and you give the box dimensions. That is why how IEEE 1584 handles MCC buckets matters and why entering widths over 49 inches gets special handling. It is also why shallow enclosures calculate lower incident energy than deep ones at the same current, and why arc flash with several circuits in one junction box models the whole box rather than one circuit.
The line side is where a screen built on one breaker misleads you most. Lugs and taps ahead of the main clear on an upstream device, usually with a delay behind it and more current available. The worst energy in the enclosure is therefore normally at the incoming compartment, and why the line side stays live, PPE with live circuits ahead of the main and incoming line compartment design cover that half of the box.
Access has to live with the label. NEC 110.26(A) requires clear working space in front of equipment you service energized and room for the door to open at least 90 degrees, which the enclosure sizing guide works through with the depth rules. If an operator runs a touch panel on that same door, an operator at a touch panel without PPE has its own answer.
Close the gap before the label
Pull the nameplate — frame, sensor rating, trip-unit type — and get the manufacturer's time-current curve for that unit at your settings. Recalculate with the actual arcing current and the actual clearing time, then keep both results with their ratio in the study file. A 3.2-versus-21 comparison is the shortcut's bias demonstrated on your own gear, worth more than any rule of thumb. Remember that the curve moves with panel temperature: MCB trip curves and panel temperature shift in a hot enclosure, and so does your clearing time. Open the door dead — lock out and test for absence of voltage — and treat a screened number as wrong in the dangerous direction until the real curve lands.
Put this in the study file:
- the edition you calculated with;
- the missing breaker data, named;
- the pickup check at 0.85 times the arcing current;
- both results and their ratio;
- the value you put on the label.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can I put a screened incident energy on the arc-flash label?
Yes, when the arcing current at 85 percent still clears on the instantaneous element, roughly 2 to 3 cycles or 0.033 to 0.05 s at 60 Hz. The simplified result then runs high or close, and you can label with it. On any delayed clearing, recalculate with the real trip curve first: one 0.3 s setting turned a 3.2 cal/cm² screen into 21 cal/cm² in the worked example.
Do the simplified breaker equations always overestimate incident energy?
They lean high against a healthy breaker clearing on its instantaneous element, and lower still against a current-limiting breaker clearing in under half a cycle, about 17 ms. They run low against anything that clears on a delay. Energy scales linearly with duration in the IEEE 1584 fit, so 0.3 s instead of 0.05 s is six times the energy: the error follows the trip setting.
What fault currents does the IEEE 1584 model cover?
The 2018 fit spans 208 V to 15 kV. At the low end, hold your bolted fault current between 500 A and 106 kA to stay inside the fitted band. Equipment below 240 V needs no arc study unless a 125 kVA or larger low-voltage transformer supplies it, which is the guide's own cut-off.
Why does IEEE 1584-2018 also calculate at 85 percent of the arcing current?
Because a smaller arcing current can clear slower on an inverse-time element and leave more energy, the guide computes both values and keeps the higher result. Your screening check does the same: compare the pickup against 0.85 times the arcing current, and the margin above the pickup tells you which side of instantaneous you are on.
Where in the enclosure is the screened number weakest?
At the incoming compartment. The screen reflects only the breaker you modeled, while lugs and taps ahead of the main clear on an upstream device, commonly with a 0.1 to 0.4 s delay and more available current behind it. The highest energy in the box is usually on the line side, so screen that separately.