Yes — the label stays, and the number on it belongs to the line side of the switch. Lockout/tagout decides who may open the box and when; it never de-energizes the incoming lugs. Your electrician opens the handle, hangs the lock, swings the door and tests for absence of voltage, and every step up to the zero reading happens in front of a live 480 V source. That exposure is what the label states, and NFPA 70E spells out exactly what goes on it. In the worked example below, a disconnect fed from a 500 kVA transformer lands at 5.5 cal/cm² at 18 in [455 mm] with a 38 in [0.97 m] boundary, on stated assumptions you replace with your own study.
Why the handle changes nothing on the line side
Opening a disconnect separates its contacts and drops the load downstream. The incoming lugs, the line-side stabs and the cable joints ahead of them stay at full voltage until something upstream opens. Your exposure at that switch is set by the upstream supply and by how fast its breaker or fuse clears a fault. The handle position never enters the calculation, which is also why moving the disconnect into its own box changes nothing — why the line side stays live works through that geometry.
Three arguments come up whenever this question does: the switch is only a local disconnect, it will never be opened under load, and the site runs lockout/tagout. All three describe the switching task. The label prices the fault — how many cal/cm² the upstream supply pushes into an arc at your working distance — and switching is only one of the tasks that puts hands near the lugs. Locking out, testing for zero, torque-checking and thermal scanning all happen with the door open, and all of them are live work until the meter says otherwise.
A lockout program and an arc-flash label answer two different questions, so keep both. The program sets the sequence that proves the box dead. The label states the energy inside it until that proof is finished, and it ties the box to the study behind the number: transformer size, fault current, clearing time, date.
What NFPA 70E and the NEC ask for on the label
NFPA 70E calls for marking wherever equipment may be examined, adjusted, serviced or maintained while energized. The label carries the nominal system voltage, the arc-flash boundary and the incident energy at the working distance, or the PPE category when you use its tables. The NEC adds a field- or factory-applied arc-flash warning on switchboards, panelboards, industrial control panels, meter sockets and motor control centers outside dwellings, and on service equipment. Neither rule asks whether you intend to operate the switch loaded; both look at what stays energized when the door comes off.
The boundary has a meaning you can check: 1.2 cal/cm² [5.0 J/cm²] at the skin is where a second-degree burn begins. The arc-flash boundary is the distance at which the arc in question delivers exactly that. Inside it your planned work takes arc rated PPE, and the incident energy at the working distance sets the arc rating that PPE needs.
| Item on the label | Where it comes from | Worked example |
|---|---|---|
| Nominal system voltage | Your one-line diagram | 480 V, 3-phase |
| Incident energy at the working distance | IEEE 1584 study with your fault current and clearing time | 5.5 cal/cm² at 18 in [455 mm] |
| Arc-flash boundary | Distance where the energy falls to 1.2 cal/cm² | 38 in [0.97 m] |
| PPE | Arc rating at least equal to the incident energy | 8 cal/cm² kit, PPE category 2 |
The minutes the label actually covers
Walk your lockout sequence and watch where the person stands. Handle open, lock on, door open, meter on the line-side lugs. Until the meter reads zero on every phase, those lugs are a live arc source at arm's length and the test itself is energized work. That is why the PPE question comes up before the box is ever proven dead — PPE in an enclosure with live circuits ahead of the main covers choosing it from the label.
Your lockout program is the wider frame, and the OSHA lockout/tagout rules for industrial equipment govern its steps. The label governs the suit worn while those steps run. Keep the two documents saying the same thing: the procedure should point to the label's numbers for the test-for-zero step.
One safety note: the tester is a qualified person, the meter is rated CAT III 600 V or better for this panel, and it is proven on a known live source or a proving unit before and after the reading.
Worked example: a 480 V local disconnect
Treat these as assumptions and replace them with your own data: a 500 kVA transformer with a 480 V secondary and 5% impedance; an upstream breaker that clears the arcing fault in 0.3 s; an IEEE 1584 study reporting 5.5 cal/cm² at the 18 in [455 mm] working distance used for panel work at this voltage.
- Full-load current: 500,000 VA ÷ (1.732 × 480 V) = 601 A
- Bolted fault current, infinite bus: 601 A ÷ 0.05 = 12 kA, trimmed a little by cable impedance
- Boundary check: energy spreading from an arc falls with the square of distance, so 18 in × √(5.5 ÷ 1.2) ≈ 38 in [0.97 m], matching the study's boundary
- Label text: 480 V / 5.5 cal/cm² at 18 in / boundary 38 in / arc-rated PPE 8 cal/cm²
The kVA and the impedance come off the nameplate and the one-line. The 0.3 s comes from the coordination study or the breaker's time-current curve. Change one input and the label follows it.
What moves the number
Clearing time moves it linearly. Ride the arc for 0.6 s instead of 0.3 s and the same fault delivers 5.5 × (0.6 ÷ 0.3) = 11 cal/cm², which takes you past the 8 cal/cm² of category 2 and into 25 cal/cm² suits. One coordination setting, twice the energy.
Fault current follows the transformer and its impedance. The example's 5% unit gives 12 kA at the lugs; the same 500 kVA at 3% gives 601 ÷ 0.03 = 20 kA, and the incident energy climbs steeply with the arcing current.
Distance works on the square in open air: read the example's arc from 24 in and you get 5.5 × (18 ÷ 24)² = 3.1 cal/cm². Inside an enclosure the walls push energy back toward you, so the study sets the number rather than pacing off it.
When 11 cal/cm² is the answer, cut the number instead of buying heavier suits. Set the upstream instantaneous to reach the fault, put current-limiting fuses on the feeder, use zone-selective interlocking where coordination allows, or move the switching into an enclosure built to contain an arc. Reducing equipment down to category 2 by design runs those options with numbers.
The decision, case by case
| Your situation | Label? | What goes on it |
|---|---|---|
| Local disconnect, upstream feeder closed while the door is open | Yes | Line-side values from your study |
| Disconnect is the main incoming, utility ahead | Yes, and often the plant's highest number | Service-side values; utility clearing times run slow |
| Site procedure opens the upstream breaker before the local door | Yes | Values set by that upstream device and its clearing time |
| Switch never operated under load, door opened only to lock out | Yes | Line-side values; the test for zero energy is the energized task |
Give the box a second label when it holds two assemblies with different line sides — when one enclosure needs several arc flash labels sorts that case. The decision is the same in every row: label it, and let the study set the number.
The label and the box it rides on
Outdoors or in washdown, the label has to outlast the environment and the box has to keep its rating. Engraved aluminium or UV-laminated polyester holds up in sun and hose-down; place it in the standing sightline so it reads before the door opens. Our stainless enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed — NEMA does not test or certify enclosures. The NEMA enclosure types guide maps types to locations; pick 316L for coastal and washdown sites, 304 for sheltered outdoor duty. We cut the door for your disconnect handle and deliver in 10 business days, counted from your approval of the drawing on custom work — start in 316L stainless enclosures or sort by environment and inside dimensions in the enclosure selector.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Is a generic arc flash warning sticker without numbers enough?
Only as a supplement. NFPA 70E puts three data on the label: the nominal system voltage, the arc-flash boundary and the incident energy at the stated working distance, or the PPE category if you use its tables. A label reading 480 V, 5.5 cal/cm² at 18 in, 38 in boundary tells the electrician which suit to wear; a bare warning gives nothing to act on.
Do we relabel after changing the upstream breaker settings?
Yes. Incident energy scales linearly with clearing time, so doubling the time from 0.3 s to 0.6 s took the example from 5.5 to 11 cal/cm², past the 8 cal/cm² of category 2 and into 25 cal/cm² suits. NFPA 70E also calls for reviewing the arc-flash risk assessment at least every five years, and whenever the supply, transformer or protection changes.
Does the load side of the disconnect need its own label?
When the handle is open and locked, the load side is dead and the line side is not, so one line-side label usually covers the whole enclosure. Add a second label when the load side is fed from another source, or when the box holds a second assembly with its own incoming lugs — each label carries the boundary and cal/cm² of its own side.
Where on the enclosure should the arc flash label go?
In the normal standing sightline, readable before the door opens, and durable for the location. Outdoors and in washdown, engraved aluminium or UV-laminated polyester holds up; paper under tape fades fast in direct sun. Keep it clear of the hinge swing and the lock hasp so hardware and hands leave the numbers visible.
Who is allowed to calculate the incident energy for the label?
A qualified person with the one-line data: transformer kVA and impedance, conductor sizes and lengths, and the settings or time-current curves of the upstream protective devices. The study follows IEEE 1584 with your clearing times; the label then carries the resulting cal/cm² at the stated working distance, with the date and study reference for audits.