Short answer: order one braking resistor per drive and land it on the braking terminals — the pair the drive manual wires across the DC link through the braking chopper. Leave U, V and W to the motor cable. When the load overhauls the motor during a stop, the machine pushes energy back through the inverter to the DC link, the link voltage climbs toward the overvoltage trip, and the chopper switches the resistor across the bus to burn the surplus as heat. While that switch is on, the resistor sees link voltage squared over its resistance — 12.8 kW at worked-example values of 800 V DC and 50 Ω — duty-cycled to whatever average your stop rate sets. The terminal labels differ between drive families; the circuit and the arithmetic never do.
The DC link is where the energy lands
A drive rectifies its supply into a capacitor bank, and that bank is the DC link. Everything the inverter does, it does by chopping that voltage. On a 480 V drive the rectifier charges the link to the peak of the line, √2 × 480 V ≈ 679 V, settling near 650 V under load.
Motoring, the inverter turns that DC into the variable-frequency output your motor sees. Braking, the motor becomes a generator: its current is forced back through the inverter's power devices into the link, the capacitors charge, and the voltage climbs. Give that energy nowhere to go and the drive trips on overvoltage, and your load coasts to a stop you did not order.
Those same capacitors carry the drive's ripple current the whole time, and VFD input phase chopping raises DC-link thermal stress on an unbalanced supply, so the braking circuit deserves its own engineered connection rather than an improvised one around the link.
What the braking chopper does
A braking chopper is one switch — an IGBT — with one resistor, both across the link. Drive application notes on dynamic braking describe the same behaviour in every family: when link voltage reaches a set level, the switch closes, the resistor draws link voltage ÷ resistance, the bus pulls down, the switch opens, and the cycle repeats. The bus rides just under the trip point, and the braking energy leaves as heat in the resistor instead of as a fault.
Run the magnitudes with worked-example values — an 800 V DC set point and a 50 Ω bank, both replaced by your drive's printed threshold and permitted resistance. While the switch is on, the bank draws 800 V ÷ 50 Ω = 16 A and dissipates 800² ÷ 50 = 12,800 W. That instantaneous pulse sits far above anything the bank sheds on average, which is the whole point of the switching. With no switch in the circuit, a 50 Ω resistor straight across the 650 V link would dissipate 650² ÷ 50 = 8.45 kW with no rest at all.
Compact drives often build the switch and a small resistor in. Larger frames bring out terminals for an external bank when the duty outgrows the internal one.
Why the resistor never lands on U, V and W
U, V and W are the inverter's output: three terminals carrying the chopped link, pulse-width-modulated at the carrier — drive installation manuals commonly set that between 2 and 8 kHz — arranged into a wave the motor follows. The braking energy never sits there. It travels from the motor, through the same inverter devices, onto the DC link, and the chopper is waiting for it there.
A resistor across two output terminals fails in both directions. While the drive runs, the bank sees the PWM output and dissipates continuously as a parasitic load. While the load regenerates, the bank sits downstream of the inverter and the voltage that climbs is on the link, so the drive still trips and you gain nothing. Keep the wiring simple: the motor cable lands on U, V and W, the bank lands on the braking pair in the power-circuit diagram, and nothing else lands on either.
One bank per drive, sized to energy
Three motor phases funnel into one DC circuit, and the chopper is one switch, so one bank carries the entire duty. Resistance sets the power the bank can absorb, P = V²/R at the link voltage: halve the ohms and you double the absorbing power, until the current, V ÷ R, passes what the chopper is built to switch — the reason every manual prints a minimum resistance. Watts must cover the duty, meaning energy per stop and stops per hour, which is how to size a VFD braking resistor for duty. For the nameplate end of it, what a 50 Ω, 1200 W spec means unpacks the two numbers.
Finding the terminals on your drive
Labels differ by family, so work from the power-circuit diagram in the operating instructions — the page showing power terminals — and not from the control-terminal drawing. On many compact drives the braking pair is marked PB and PO, with a jumper between them that routes the internal resistor onto the chopper; the PB and PO jumper article covers when that jumper comes out. Larger frames bring the braking pair out beside the DC-link pair and print the permitted resistance range; the minimum resistance for a small VFD shows what dropping below it costs.
| Terminal or pair | What it is | What lands on it |
|---|---|---|
| U, V, W | Inverter output to the motor | The motor cable, and nothing else |
| DC-link pair (+ and −) | The rectified bus feeding the inverter | Common-bus ties the manual allows; a bare resistor never goes straight across it |
| Braking pair (PB and PO on many compact drives) | The chopper's output | One braking resistor bank, sized to the duty |
| Control terminals | Logic inputs and outputs | The bank's thermostat contact, as an external fault |
Wiring the bank into your panel
Treat the resistor pair as a power circuit: twisted where you can, routed with the drive's power wiring, kept away from analog, encoder and communication cables. The chopper's switching makes this pair a noise source even though the current reads DC on average. The thermal load on the copper is modest — at a 10 % duty, the 16 A peak works out to 16 × √0.10 ≈ 5.1 A RMS — so heat, not amps, is what kills resistor wiring. Run silicone- or glass-fibre-insulated wire rated 180-200 °C for the last 12 in [300 mm] to the bank, and keep other cables off its housing.
Most banks carry a thermostat, a contact commonly rated around 250 V AC at a few amps, that closes on overtemperature. Land it on a drive input configured as an external fault so an overworked bank stops the drive instead of cooking quietly. House the bank in its own vented enclosure rather than the drive cabinet, and bond that box into the cabinet's grounding scheme as the enclosure grounding and bonding guide and grounding a regen resistor enclosure set out.
The link holds charge after the supply comes off. Wait the discharge time the manual states, then measure across the braking terminals and read zero volts DC before your hands go in.
The heat has to live somewhere
Worked example, with assumptions you replace from your own documents: a 480 V drive with an 800 V DC chopper set point, a 50 Ω bank, stops of 10 s, and six stops every 10 minutes.
- Pulse energy per stop, worst case with the chopper on throughout: 12.8 kW × 10 s = 128 kJ. The bank's pulse rating covers this.
- Duty: 6 × 10 s = 60 s of braking per 600 s, a 10 % duty cycle, so the average is 0.10 × 12,800 W ≈ 1,280 W. The bank's continuous rating covers that.
- Placement: 1,280 W sealed inside a 20 × 16 × 8 in stainless enclosure — 0.78 m² of surface at 3.7 W/m²K for stainless — gives 1,280 ÷ (3.7 × 0.78) ≈ 440 K of internal rise. Nothing survives that. At this size each 100 W sealed in adds about 35 K, so even a 130 W average is a 45 K rise.
The decision: the bank goes in its own vented housing beside the drive cabinet — sizing and mounting a braking resistor in a VFD enclosure sets out the clearances — and you run the enclosure heat calculator on whatever stays inside the sealed box. A bank pushed past its rating in a warm panel faults exactly when braking is hardest, the sequence braking resistor overload from a hot panel walks through. When the housing needs gland cutouts and a thermostat entry, a custom enclosure is built to that layout.
What to order, by case
- Compact drive, light duty. The internal resistor behind the PB–PO jumper covers occasional stops: wire nothing, order nothing.
- Duty past the internal resistor, or no internal one. One external bank per drive on the braking terminals, ohms inside the manual's printed range, watts from the pulse-and-average arithmetic above.
- Drive with no chopper. A resistor cannot be retrofitted around it. Choose a drive with a chopper or a regenerative unit, and plan the panel's heat for it.
- Heavy, repeated braking — hoists, centrifuges, downhill conveyors. An external bank in its own vented housing, thermostat wired back to the drive, sized from the energy of the duty the way braking resistor sizing for a hoist drive does it.
- Two drives. Two banks, each on its own chopper. Sharing one bank across two links is a common-bus design of its own, not a wiring change; multi-drive enclosure sizing covers how those lineups are planned.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Do I order one braking resistor or three, one for each motor phase?
One. The three motor phases funnel into a single DC link, and the chopper is a single switch across it, so one bank carries the whole duty. At an example threshold of 800 V DC, a 50 Ω bank draws 800 V ÷ 50 Ω = 16 A and dissipates 800² ÷ 50 = 12.8 kW while conducting. Size its watts from your stop frequency, not from the phase count.
Why can't the resistor go across two of the motor terminals?
Because U, V and W are the inverter's PWM output, chopping the bus at the drive's carrier, which installation manuals commonly set between 2 and 8 kHz. A resistor there dissipates whenever the drive runs and does nothing during regeneration: the generated current returns through the inverter to the DC link, and the bus still climbs until the drive trips on overvoltage. The braking terminals sit where the energy actually is.
What happens if I wire the resistor straight across the DC-link terminals?
It burns. With no chopper switching, the resistor sits on the full bus continuously: at the nominal 650 V of a 480 V drive, a 50 Ω bank dissipates 650² ÷ 50 = 8.45 kW with no duty cycle at all. That is a fire in a bank rated for a 10 % duty. The resistor goes on the chopper's braking pair, so the switching limits the average power.
Can the resistor bank share the sealed cabinet with the drive?
Only if the heat budget says so, and it rarely does. The 1,280 W average of the worked example, sealed in a 20 × 16 × 8 in stainless box with 0.78 m² of surface at 3.7 W/m²K, gives a 440 K internal rise. Put the bank in its own vented enclosure beside the drive cabinet and run the enclosure heat calculator on what stays inside.
Why is there a jumper between PB and PO on my drive?
On compact drives those two terminals are the braking pair, and the jumper routes the internal resistor onto the chopper. You lift it only when the manual has you wire an external bank across the same terminals; lifting it with nothing connected leaves the chopper nowhere to put braking energy, and the drive trips on overvoltage at the next hard stop.