Short answer: take the resistance from the drive's installation manual, and the wattage from the lift's worst loaded stop — a 55 kW hoist motor fixes neither number. The half-motor shortcut behind the familiar 25 kW suggestion for a 55 kW drive is a starting point at best: it says nothing about ohms, and it can land under the pulse power of a single stop. This article runs the full calculation on a worked case, a 3,000 kg service-lift car brought from 1.6 m/s to rest in 3 s by a 55 kW hoist drive. The mass, speed, ramp, inertia and duty in the case are assumed inputs; replace each with your lift's figures before you order anything.
What you need before you pick a value
You need seven inputs, and each decides a different line of the order.
| Input | Where you get it | What it decides |
|---|---|---|
| Drive reference | The drive nameplate | Which manual, and which resistance band |
| Min-max braking resistance | The installation manual for that exact frame | The ohms floor and ceiling |
| Rated load, car plus payload | The lift's load data | Gravitational energy per stop |
| Descent speed and ramp time | The motion profile or the drive's ramp settings | Stopping distance and pulse power |
| Equivalent inertia at the motor shaft | Motor and gearbox data sheets, through the gear ratio | Kinetic energy per stop |
| Full-load stops per hour | The duty record | Continuous average heat |
| Resistor data sheet | The resistor maker | Pulse curve, continuous watts, ohms |
The nameplate gives you the reference; the manual gives you the ohms; the lift gives you the watts. Two 55 kW hoists, one with a 1,000 kg car and one with a 4,000 kg car, return four times the energy per stop at the same speed, and the motor rating cannot tell you which one you commission.
Why motor kW sets neither ohms nor watts
Braking resistance is a limit of the drive's braking transistor, not a property of the motor. Push the ohms below the manual's floor and the current through the braking stage rises until the transistor overheats; drive makers print minimum values that vary with the drive's power and voltage rating for exactly that reason.
Wattage belongs to the lift instead: gravitational energy scales with mass, kinetic energy with inertia, and both with speed. And a resistor's wattage figure is itself conditional — it is a pulse rating at the duty the maker's data sheet states — so the ohms-and-watts pair on the nameplate only means something read together, as decoded in braking resistor ohms and watts. The page-length argument for sizing by energy rather than motor current is in sizing a braking resistor by energy, not motor current.
Read the resistance band from the drive manual
Open the installation manual for your exact drive reference and find the braking section. It prints a minimum and a maximum resistance, and both are hard limits. Below the floor, the braking chopper pulls more current than its transistor is built to switch, and the stage fails or the drive protects itself. Above the ceiling, the resistor cannot pull the DC bus down fast enough and the drive trips on overvoltage before braking completes.
The numbers move frame by frame. One current 22 kW, 400 V drive lists a 15 Ω minimum in its installation manual, and the catalog braking resistor sold for the previous generation of that power class is 14 Ω at 22.4 kW, rated IP20. Bigger frames usually carry lower floors, because their braking transistors switch more current; your 55 kW frame carries its own pair, in the same place. The check on a small drive is walked through in minimum braking resistance for a small VFD.
Size the resistor in six steps
- Copy the min-max resistance pair from the installation manual for your exact drive reference.
- Write the worst stop in numbers: full-rated load descending, entry speed v in m/s, ramp time t in s.
- Convert: stopping distance h = v × t ÷ 2, because speed falls linearly to zero, and motor speed to ω = 2π × n ÷ 60 rad/s.
- Add the energy terms: gravitational E = m × g × h with g = 9.81 m/s², plus kinetic E = ½ × J × ω², with J the equivalent inertia at the motor shaft.
- Divide by time: pulse power is E ÷ t, and the heat shed between stops is E × stops-per-hour ÷ 3,600 s. The duty side gets the longer treatment in how to size a VFD braking resistor for duty.
- Buy against all three numbers — ohms inside the manual's band, a pulse curve covering your energy at your ramp time, continuous watts above your average — then wire it to the drive's braking terminals with the factory jumper where the manual keeps it, and mount it outside the sealed enclosure. The jumper case is in braking resistor terminals and the factory jumper.
Size to 100 percent of the calculated energy. Gearbox friction, motor losses and the drive's own losses return less than the arithmetic says, so the difference is margin you keep.
Worked example: a 3,000 kg service lift stopping from 1.6 m/s in 3 s
The inputs, each with its source:
- 55 kW hoist drive, 400 V class — the frame in this case; its manual supplies the ohms
- m = 3,000 kg — assumed car plus full rated payload
- v = 1.6 m/s — assumed descent speed when the stop starts
- t = 3 s — assumed ramp to rest
- J = 0.5 kg·m² — assumed equivalent inertia at the motor shaft, rotor plus reflected load
- n = 1,480 rpm — assumed 4-pole motor at 50 Hz, near full speed in the descent
- 20 full-load stops per hour — assumed duty for a busy service lift
The rule: a load lowering through h hands back m × g × h of energy, and the rotating parts hand back ½ × J × ω². The resistor absorbs the sum once per stop, then sheds the repeats as steady heat.
- h = 1.6 m/s × 3 s ÷ 2 = 2.4 m
- ω = 2π × 1,480 ÷ 60 ≈ 155 rad/s
- Gravitational energy = 3,000 kg × 9.81 m/s² × 2.4 m = 70,632 J ≈ 70.6 kJ
- Kinetic energy = 0.5 × 0.5 kg·m² × (155 rad/s)² = 6,006 J ≈ 6.0 kJ
- Energy per stop = 70,632 + 6,006 = 76,638 J ≈ 76.6 kJ
- Pulse power = 76,638 J ÷ 3 s ≈ 25.5 kW, for 3 s at every stop
- Continuous average = 76,638 J × 20 ÷ 3,600 s ≈ 426 W
Read the result as three numbers. The resistor takes 76.6 kJ in 3 s — call it about 26 kW of pulse power, rounded up for the order — sheds 426 W between stops, and its ohms sit inside the band the 55 kW manual prints. The kinetic share is 6.0 of 76.6 kJ, under 8 percent, so an inertia you cannot pin down costs little: tripling J to 1.5 kg·m² lifts the pulse to 29.5 kW. The 25 kW half-motor figure fails this stop outright, and the exact half, 27.5 kW, clears it by coincidence — 4,000 kg at the same speed returns 94.2 kJ of gravitational energy alone and breaks it. On these inputs, anything under about 26 kW of pulse power or 430 W continuous is undersized; and no wattage figure replaces the manual's ohms.
The descent can outweigh the stop
Between stops, a hoist can out-brake its own stopping profile. Hold full load at constant descent speed and the drive brakes the motor the whole way, returning power at m × g × v before losses: 3,000 kg × 9.81 m/s² × 1.6 m/s ≈ 47 kW, every second the car is going down. Lower it through a 12 m travel and the descent alone returns about 353 kJ at that average — four and a half times the stop's energy, at about twice its pulse power, sustained the whole way down.
So the duty decides the hardware. Descents that are short, lightly loaded or occasional fit the resistor sized above; routine full-load lowering over most of the travel calls for a regenerative drive or unit that returns the energy to the supply. Undersized resistors announce themselves slowly, shift by shift, and the pattern is in braking resistor overload from a hot panel.
Where the resistor lives and where its heat goes
Catalog drive resistors are rated IP20 — protected against finger contact, nothing more — so they live behind a guard or inside a housing, out of dust and spray. Their heat is the second reason to keep them out of the drive box. The worked lift sheds 426 W of continuous heat, and a duty with powered lowering sheds kilowatts. Sealed inside a stainless box with about 3.4 m² of outer surface — near enough 1 m × 0.8 m × 0.5 m — that 426 W moves through walls at 3.7 W/m²K for a rise of 426 ÷ (3.7 × 3.4) ≈ 34 K. A 30 °C plant room then sits the box interior near 64 °C, 24 K over the 40 °C that drives and most electronics take unless a datasheet allows more. The wall-loss method behind that figure is in estimating enclosure thermal resistance from heat load, and you can run your own box through the enclosure heat calculator.
So give the resistor its own space: guarded, with free air, in a clean corner of the plant — most floors have one within cable reach of the drive. Where the spray reaches everywhere, seal it into a gasketed stainless housing sized from the heat: 426 W wants about 7.7 m² of wall for a 15 K rise inside, so plan on a large box or split the grids into two housings. Slots or a fan in that housing give up the rating — a ventilated enclosure is not rated NEMA 4X / IP66. Any housing we build for the job is manufacturer-rated NEMA 4X / IP66 — not UL listed — sized from your heat load. Placement, clearances and fixing are walked through in sizing and mounting a braking resistor in a VFD enclosure; bond the housing frame and door as you would any panel, the pattern in grounding a resistor enclosure on a drive cabinet. For washdown plants, start from the NEMA 4X stainless wall-mount enclosures and carry the 426 W into the size.
Checks on the bench and on the first shifts
- Lock out and verify absence of voltage before you fit or measure anything, and confirm the drive's fault mode sets the mechanical brake before the first powered test.
- Measure the resistor cold, drive disconnected: the reading sits near nameplate — a 14 Ω unit reads about 14 Ω — and inside the manual's band. An open grid reads infinite ohms and trips the drive on overvoltage at the first descent.
- Enable braking-by-resistor in the drive's brake settings; with the mode unset the chopper stays off and every stop ends in an overvoltage trip.
- Run the heaviest descent in the duty and watch the DC-bus display: it should rise through the ramp, settle, and stay below the overvoltage threshold with no fault.
- Shoot the grid with an infrared thermometer every few stops: the surface should plateau by roughly the tenth cycle. Still climbing means the average heat has outrun the duty rating — re-specify.
- Log loads and stops for a week and compare with the 20 per hour the sizing assumed.
The decision by duty
- Short descents, discrete stops: the resistor sized from the worst stop — ohms inside the drive manual's band, a pulse curve over your stop energy at your ramp time, continuous watts at or above your average, mounted in its own ventilated space.
- Long or frequent powered descents: regeneration. Full-load lowering returns about 47 kW for every second of travel in the worked case; a regenerative drive hands that energy back to the supply instead of heating a grid bank, and the resistor selection drops out of the problem.
- Holding at rest: the mechanical brake, always. It holds the car and catches it on fault; the resistor only decelerates, and it plays no part at zero speed.
On the order: the drive reference and its installation manual for the resistance band; the worst-stop numbers — mass, speed, ramp, stops per hour — for the pulse and continuous ratings; and, where the spray reaches, a gasketed stainless housing sized from the heat load, delivered in 10 business days from your approved drawing.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
What happens if the braking resistor is below the drive's minimum resistance?
The braking chopper sees roughly double the current at half the ohms, and the pulse power in the resistor doubles with it, because both follow the bus voltage divided by the resistance. The braking transistor is built for the manual's minimum and nothing below it; under the floor, the stage fails or the drive protects itself. Stay inside the min-max band the installation manual prints for that exact frame — one 22 kW, 400 V manual lists 15 Ω.
At what point does a hoist need regeneration instead of a braking resistor?
When the average regenerated power outruns any resistor you can mount. Sixty full-load stops per hour turn the worked 76.6 kJ per stop into 76,638 J × 60 ÷ 3,600 s ≈ 1.28 kW of continuous heat, three times the 20-stop figure, and powered lowering adds far more on top. A regenerative unit returns that energy to the mains, and the resistance band stops applying because no chopper fires.
Does a longer stopping ramp reduce the load on the braking resistor?
It lowers the pulse power but raises the heat per stop. Stretch the worked stop from 3 s to 6 s: the car coasts 4.8 m instead of 2.4 m, gravitational energy doubles to 141 kJ, the stop total climbs from 76.6 to about 147 kJ, and pulse power falls only from 25.5 to 24.5 kW. The ramp buys peak current headroom, not total heat: the between-stop average rises from 426 W to about 818 W at the same 20 stops per hour.
How much does an unknown inertia change the resistor size?
Less than the load does, so bound it instead of stalling. The rotating share in the worked example is 6.0 kJ of 76.6 kJ, under 8 percent of the stop; tripling the assumed inertia from 0.5 to 1.5 kg·m² lifts pulse power from 25.5 to 29.5 kW, about 16 percent. Take motor and gearbox inertias from their data sheets, reflect them through the gear ratio, add them, and carry the result as your kinetic term.





