Short answer: carry the regen pairs in one cable that includes its own ground conductor, and bolt a dedicated 6 AWG copper jumper between the resistor enclosure and the drive cabinet. Count the mounting bolts as clamping, not grounding. A servo drive's braking channel clamps the DC bus near 650 VDC and a hard stop can push it to 1000 VDC. The bond has to survive salt air, hoisting and heat, not just the first install. Work it through on a build like an eight-axis machine hoisted onto a ship's deck, with the resistor box on top of a 7 ft [2.1 m] cabinet. You end with three numbers: a jumper size, a cable voltage rating and a bond resistance you measure before power-up.
What the code asks of the bond
NEC 250.4(A)(5) describes the path fault current must take: metal parts carry it back to the source over a low-impedance conductor route, and the earth is not part of it. A regen element sealed in a metal tube sits as much as 1000 VDC from ground. One insulation failure puts the tube, and the box around it, into the fault path. The bond gives that current a conductor route back to the drive, where its protection clears it. It also holds box and cabinet at the same potential while anyone works on either. The deck, the hull and the mounting feet carry none of that duty.
NEC Table 250.122 sizes a grounding conductor from the overcurrent device ahead of the circuit: 10 AWG copper at a 60 A device, 8 AWG at 100 A. The NEC's sizing rules also permit one grounding conductor for several circuits that share a cable or raceway. You take it from the largest device among them. NEC 250.96(A) covers the boxes themselves: metal parts intended to carry fault current are bonded so they can conduct it. The arrangement writes itself — the ground conductor rides inside the cable with the pairs it protects, and the two enclosures get a jumper of their own. The grounding and bonding guide carries the fundamentals.
The regen + and − leads can stay ungrounded; the bond is for the metal. On an ungrounded DC circuit a first fault trips nothing, so bring the drive's ground-leakage alarm into the panel and treat it as a stop-and-investigate signal.
What you need
- Multi-conductor cable rated 1000 V with an included ground conductor; two to four resistor pairs per cable keeps an eight-axis machine to two or four runs.
- A 6 AWG copper jumper, bare or green-insulated, with two compression lugs, stainless bolt hardware and conical washers.
- Marine-grade circular connectors with spare contacts: one for the cable's ground conductor and one pair for the enable loop.
- High-temperature lead wire rated 150 to 200 °C for the span from terminal block to resistor element.
- A low-ohms meter that reads to 0.01 Ω, a torque wrench and a thermocouple or IR thermometer.
- Gland cutouts in both boxes; the 3D enclosure builder puts them on the drawing before you order.
The steps, jumper first
Lock out the 480 VAC feed and prove it dead before the first lug goes on.
- Size the jumper from the largest grounding conductor in the panel. Take the example cabinet: a 480 VAC, 60 A branch feeding eight servo axes on 6 AWG copper conductors. At 75 °C, the NEC ampacity table gives 6 AWG copper 65 A. NEC Table 250.122 sets 10 AWG copper as the smallest grounding conductor at 60 A. The regen cables you chose carry 6 AWG included grounds, so the largest circuit grounding conductor is 6 AWG, and the box-to-box jumper is 6 AWG copper too. It beats the 10 AWG minimum and its 65 A ampacity covers the 60 A device.
- Pick the cable on voltage before anything else. Read the braking clamp and the bus ceiling from the drive manual; in this example they are 650 VDC and 1000 VDC. Order cable marked 1000 V. A 1000 V cable keeps the insulation thickness of a 600 V type, but its maker proves the construction with a dielectric test at the 2000 V level, and that test is the margin at the ceiling. A 600 V pair runs out of rating the first time the clamp passes 600 V.
- Keep the cable out of the hot zone. Land it on terminal blocks in the connection pocket the resistor vendor provides. Bridge block to element with lead wire rated 150 to 200 °C. The jacket on standard marine and building cable is rated 90 °C dry, and air inside a working resistor box passes that on a long regen. Resistor sizing and duty are their own arithmetic; the braking resistor sizing article works them.
- Bolt the jumper to bare metal at both ends. NEC 250.12 asks for paint, lacquer and enamel to come off threads and contact surfaces unless the fitting is built to bite through. Use stainless bolts and conical washers under head and nut. Torque to the value marked on the lug. Run the strap where a walk-around sees it; a deck that flexes hides a loosened joint.
- Land every included ground at both ends. Each cable's ground conductor terminates on the resistor box frame at one end and the cabinet's ground bus at the other, through the connector's ground contact. Insulated grounding conductors of 6 AWG and smaller wear green, or green with a yellow stripe, per NEC 250.119. The grounding conductor entry and bonding article shows the landing order that keeps the run short and direct.
- Wire the loop that proves the ground before power. Two spare contacts carry a 24 V DC control pair in series with the drives' enable circuit, so the drives refuse to enable until the cable is mated. If the jumper comes off at every move, land a loop plate under its stud too, so enable needs both cable and strap. A signal pin carries amps, not fault duty; the strap carries the fault and the loop only proves it exists.
Checks before you energize
- Bond, box to cabinet ground bus, with the low-ohms meter, and treat 0.1 Ω as the ceiling. The copper is not the problem: 6 AWG runs about 0.395 Ω per 1000 ft at 20 °C, so an 8 ft [2.4 m] strap over the top of the 7 ft cabinet is 0.395 × 8 / 1000 = 0.003 Ω. Everything else on the meter is joint resistance, so a reading of 0.2 Ω means remake the joints, not upsize the copper.
- Work the interlock both ways. Pull the connector and the drives must refuse to enable; mate it and they enable. Repeat for the jumper's loop plate.
- Run 10 minutes of hard regen and measure the air at the terminal pocket. You want at least 20 °C of margin under the cable's 90 °C rating, so 70 °C or less on the thermometer.
- Test each regen pair to the box frame before the first power-up. A pinched pair is cheap to fix while the crane is still on site.
Mistakes that cost the bond
- Counting on the mounting hardware. Four bolts through paint hold a box and lose the fault path: salt air walks the clamp force down and heat cycles finish it. A hinge that touches a door is not a grounding path either — the door bonding jumper article makes the same argument for panel doors.
- Trusting the structure instead of a conductor. Anchor bolts and mounting feet carry weight; fault current needs a strapped conductor it can trust for years, which is the same reasoning that puts a dedicated bond on large tanks instead of their anchor bolts.
- Pulling 90 °C cable past the elements because it was already on the reel. Move the blocks into the cool pocket and spend the 150 to 200 °C lead wire on the hot span.
- Ordering 600 V cable because the insulation looks the same thickness. The rating lives in the 2000 V test, not in the thickness.
- Leaving paint under the lug, or burying the strap behind the cable tray. Scrape to bare metal, torque, and keep the strap first on and last off at every move.
- Skipping the re-check of terminations that weather outdoors, the way aluminum grounding conductor terminations at outdoor enclosures need a scheduled look.
The bond, by installation
| Installation | Grounding conductor | Box-to-box jumper | Proves the ground |
|---|---|---|---|
| All regen pairs in one cable | One included ground serves every pair in the cable, sized from the largest device (10 AWG copper minimum at 60 A) | 6 AWG copper, bolted to bare metal | Enable loop through the connector |
| Pairs split across two to four cables | Each cable carries its own included ground | Same 6 AWG jumper | Loop per cable, or a loop plate at the jumper stud |
| Permanently bolted dry indoor stack | Cable grounds as above | Jumper stays; mounting hardware only supplements | Measure the bond at commissioning and at each inspection |
| Hoisted or salt-air installs | Cable grounds as above | Jumper mandatory, first on and last off at every move | Enable loop plus a 0.1 Ω bond check at every setup |
Order the resistor box as a ventilated custom build, because a sealed box cooks the elements. Specify louvers sized to the airflow the resistor datasheet calls for, a drip shield over the openings, and the gland cutouts drawn before anything is cut. The custom enclosure page takes it from one piece, delivered in 10 business days from your approval of the drawing. Whether the bank rides the cabinet or sits beside it changes the heat picture, not the bond; the box-on-top article compares the two placements. Our sealed wall-mount and HMI boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed — right for the drive cabinet, wrong for hot resistors inside.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Does every cable between the two enclosures need its own grounding conductor?
Every cable that carries regen circuits carries a grounding conductor with them. Put all the pairs in one cable and that single included ground serves every circuit inside it, sized from the largest overcurrent device — 10 AWG copper minimum for a 60 A device per NEC Table 250.122. Split the pairs across four cables and each cable brings its own. The 6 AWG jumper between the boxes stays in either case.
Can the mounting bolts between the boxes act as the ground?
Treat them as clamping only. A bolted joint loses clamp force to salt air and heat cycling, and paint or anodizing under the washer sits exactly where fault current has to pass. Bolt the 6 AWG copper jumper to bare metal at both ends, then measure the bond with a low-ohms meter and keep it at or under 0.1 ohm; the bolts hold the box and the strap carries the fault.
What voltage rating does the regen cable need on a 1000 V DC bus?
1000 V. Cable marked 1000 V keeps the insulation thickness of a 600 V type but is proven by a dielectric test at the 2000 V level, which is the margin you want at the bus ceiling. A 600 V pair has nothing left once the braking clamp passes 600 V, and the example drive clamps at 650 VDC.
How hot is too hot for the cable inside the resistor enclosure?
Keep the hottest air the cable sits in below its insulation rating. Standard marine and building cable is rated 90 °C dry, and air near a braking resistor can pass that during a long regen, so land the cable on blocks in the cool pocket and bridge to the elements with lead wire rated 150 to 200 °C. Measure after a hard stop and keep at least 20 °C of margin.





