Yes, the jumper stays. On the compact build of this drive family the braking resistor lands between PB and PO, the factory jumper between PO and PA/+ remains in place, and it comes out only when you fit an external DC link choke between those two terminals. Wiring alone leaves the brake dead. The deceleration ramp adaptation parameter brA ships at Yes, and with it there the drive stretches the ramp instead of braking, so you set brA to NO at COnF - FULL - FUn - rPt - brA. You prove the brake runs at the DC bus readout, which should climb to the chopper threshold and flatten there for the whole ramp. The worked numbers here, a 14.2 kJ stop and 237 W of average heat, are illustrative assumptions; put your load's figures in their place before you order parts.
What PB, PO and PA/+ actually are
A six-pulse diode bridge charges the DC bus. On a 480 V supply that bus idles near 650 V DC, which is 1.35 times the line-to-line voltage. PO is the rectifier side of the link and PA/+ is the bus side. The factory jumper carries the whole DC current between them when no choke is fitted.
A DC link choke sits exactly where that jumper sits, between the diodes and the bus capacitors. It tames line harmonics within a few percent of what a reactor in the AC line achieves, which is why drive application notes treat the two as near-equivalents. The brake chopper is a transistor inside the drive, brought out at PB. Your resistor from PO to PB completes the dump circuit. When bus voltage crosses the chopper threshold, the transistor switches the resistor across the bus, and the regenerated energy burns at P = V²/R.
| Marking | The node it reaches | Your conductor lands here? |
|---|---|---|
| PA/+ | Bus side of the DC link | Only with an external DC link choke, in place of the jumper |
| PO | Rectifier side, bridged to PA/+ by the jumper | Compact build: one resistor conductor |
| PB | Brake-chopper transistor output | One resistor conductor on every build with an internal chopper |
| PBe | Brake resistor return, book-style build | Book build: one resistor conductor |
Which terminal pair your build uses
Read the last letter of the part number before you cut any wire. B is the book-style build, C the compact one, and the resistor pair differs between them.
| Build | Resistor lands between | PO to PA/+ jumper |
|---|---|---|
| Compact, suffix C | PB and PO | Stays in |
| Book-style, suffix B | PB and PBe | Follows the installation manual for that build |
| Most other drives with a built-in chopper | PA/+ and PB | Stays in unless a DC link choke occupies it |
The generic PA-to-PB rule from other drive families is the trap on the compact build: landed there, your resistor sits on the wrong node and the chopper never reaches it. Drive lines differ in one more way. Some frames carry no internal chopper and take an external brake transistor module instead, and process-oriented ranges offer no braking resistor connection at all. A fan with a specified stop time needs a drive family with an external braking transistor, chosen at selection, because no retrofit exists.
Why the jumper stays, and what to do with the notch
The jumper carries the DC link from the rectifier to the bus, so it comes out for one reason only: an external DC link choke wired between PO and PA/+. With the jumper out and no choke fitted, the bus never charges and the drive will not run. You see that fault the moment you power up after the wiring day.
The breakable notch beside PO is undocumented in the installation material available to us, so leave it intact. Electrically you need two things at that terminal: the jumper's continuity to PA/+, and clean contact for your resistor conductor. A crimp ferrule on the conductor, both under the screw when the terminal accepts two conductors, meets both. Where the manual for your exact reference shows a different landing, the manual wins.
The parameter that switches the resistor
The resistor changes nothing until brA moves. At its factory value of Yes the drive protects the bus by stretching the deceleration ramp: your commanded 3 s becomes whatever the bus tolerates, the stop runs long, and the chopper stays off. Set brA to NO at COnF - FULL - FUn - rPt - brA, and make that change after the resistor is landed and measured. At NO with no dump circuit the next hard stop rides the bus into an overvoltage fault.
The drive maker's own guidance states the pass mark: with a correctly sized resistor the load stops in the configured deceleration time regardless of the load. If your process has no fixed stop time, coast or a longer ramp may serve you better, and the coast, ramp or brake resistor decision covers that choice before you spend money on hardware.
Where the heat puts the resistor
Run the numbers before the resistor goes inside your enclosure, because the sealed box is the constraint. Example assumptions: a flywheel of J = 0.8 kg·m² at 1800 rpm, a commanded 3 s ramp, one stop per minute, a 750 V DC chopper threshold, and a 47 Ω resistor at or above the manual's minimum for the frame.
- Speed: ω = 2π × 1800 / 60 = 188.5 rad/s
- Energy per stop: E = 0.5 × 0.8 kg·m² × 188.5² = 14.2 kJ
- Average power during the stop: 14.2 kJ / 3 s = 4.7 kW
- Peak dump capability: P = 750² / 47 Ω = 12.0 kW, so the chopper runs at 40 % duty through the stop, above the 4.7 kW the load demands
- Average heat at one stop per minute: 14.2 kJ / 60 s = 237 W
Stretch the ramp from 3 s to 6 s and the stop's average power halves to 2.4 kW, but the 14.2 kJ and the 237 W per-minute figure stay put. Now the box. Take a 20 × 16 × 8 in [508 × 406 × 203 mm] stainless wall-mount enclosure as the example, with about 0.58 m² of effective surface, the total minus the mounting face. At the stainless reference transfer of 3.7 W/m²K, 237 W lifts the interior by 237 / (3.7 × 0.58) ≈ 110 K. That is about 145 °C inside at 35 °C ambient, against the 40 °C the drive is rated for. Your margin at 35 °C ambient is 5 K, worth about 11 W in that box, and even a 25 °C room buys you only about 32 W.
The decision falls out of the arithmetic: this resistor lives outside the sealed enclosure. Give it its own housing outdoors, sized for rain and heat, or a box on top of the machine cabinet, with the clearances and mounting detail in sizing and mounting a braking resistor in a VFD enclosure. Size the drive box itself from its own losses with VFD enclosure sizing from heat and clearance.
The conductors cross the wall through one gland rated for hose washdown, which keeps the box at its NEMA 4X / IP66 rating, rated by the manufacturer and not UL listed. The assembly holds only the rating of its weakest fitted part, so the gland carries the same duty as the door gasket. Place the hole on the drawing first: the cutout designer lays it out on any face, and a custom stainless enclosure arrives with it cut, delivered in 10 business days counted from your approval of the drawing. Bond the resistor housing to the drive enclosure so the fault path stays metal all the way through. NEC 250.96(A) requires metal parts serving as equipment grounding conductors to be bonded so they safely carry any fault current likely to be imposed on them, and enclosure grounding and bonding shows the landing points.
What you need
- A resistor at or above the manual's minimum ohms for your frame, with wattage at or above your duty cycle
- A true-RMS meter with an ohms range for the cold-resistance check
- Crimp ferrules sized to your conductor, and a torque screwdriver
- High-temperature wire, 180 °C class or better, for the run near the resistor body
- A gland rated for the enclosure's environment when the resistor sits outside
Wire it in eight steps
- Read the part-number suffix and the table above: PB to PO on the compact build, PB to PBe on the book build.
- Check the resistor against the manual's braking table, then measure its cold resistance; the braking resistor minimum-resistance article explains why the ohms floor matters. An open or wrong-value unit shows up here, at zero cost.
- Isolate the drive, wait the discharge time your manual states, 15 minutes being the usual figure, then confirm 0 V DC between PA/+ and PO with a meter before you touch a braking terminal.
- Land one resistor conductor on PB and the other on PO, ferrules crimped and the jumper untouched. Torque to the value printed at the terminal block; M3 power terminals run near 0.8 N·m [7 lb·in] and M4 near 1.5 N·m [13 lb·in] on compact drives.
- Route the pair away from analog and communication wiring and keep it short. The chopper's switching edges couple into anything running parallel, so the spacing that protects a VFD's analog speed signal protects the brake leads too.
- Mount the resistor in free air, or in its own housing, glanded through the enclosure wall as above.
- Set brA to NO at COnF - FULL - FUn - rPt - brA.
- Run the stop that used to stretch or fault, then repeat it at the worst-case load and cycle rate.
Checks that prove the brake runs
- Stop time first: with a correctly sized resistor the load stops in the commanded ramp regardless of the load. A 3.0 s command that delivers 4.5 s says the ramp is still being stretched.
- Bus readout second: during the ramp the DC bus rises to the chopper threshold, flattens there for the whole stop, then falls once the drive reaches zero speed. A climb into an overvoltage fault says the dump circuit is open, too high in ohms, or short on watts.
- Temperatures third: after ten consecutive worst-case stops the resistor surface should stabilize and the enclosure temperature should stop climbing. A reading that keeps rising is an overload, and the hot-panel overload article carries the arithmetic.
When the resistor stays cold
A cold resistor is a wiring or parameter fault; a hot one with repeating overvoltage trips is a sizing fault. Separate the two before you change hardware, because the fixes share no parts, and either one costs you a shift if it surfaces in production.
| What you see | Most likely cause | The fix |
|---|---|---|
| Resistor cold, stop runs long | brA still at Yes, the factory default | Set brA to NO |
| Resistor cold, brA at NO | Resistor on the wrong pair, typically PA/+ to PB on the compact build | Move it to PB and PO |
| Drive dead after wiring work | PO to PA/+ jumper out with no DC link choke fitted | Refit the jumper |
| Overvoltage fault on decel, brA at NO | Resistor open, above the frame's ohms floor, or undersized in watts | Measure cold resistance and re-check it against the manual's braking table |
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 6 × 6 × 4 in | 304 stainless | 6 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 8 × 6 × 4 in | 304 stainless | 8 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 10 × 8 × 4 in | 304 stainless | 10 x 8 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Should I remove the jumper between PO and PA/+ when I add a braking resistor?
It stays. The jumper completes the DC link from the rectifier to the bus, and only an external DC link choke takes its place. With it out and no choke fitted the bus never charges and the drive will not run. Your resistor conductor lands on PB and PO on the compact build with the jumper untouched.
Can I meet a 3 s stop with ramp adaptation left at Yes?
No. At Yes the drive lengthens the ramp automatically whenever the bus climbs, so your 3 s command becomes whatever the bus tolerates and the resistor stays cold. Set brA to NO once the resistor is landed, then watch the bus readout through a stop: it should rise to the chopper threshold, about 750 V DC in this article's 480 V example, and hold there for the whole ramp.
How much heat does a braking resistor add inside the enclosure?
Divide the stop energy by the cycle time: 14.2 kJ once a minute is 237 W average. In a 20 × 16 × 8 in stainless box at 3.7 W/m²K that is about a 110 K rise, against the 40 °C the drive is rated for. Anything past a few tens of watts average belongs in its own vented housing outside the sealed enclosure.
Is the DC bus still dangerous after the drive is switched off?
Yes. On a 480 V drive the bus capacitors hold about 650 V DC after the isolator opens. Wait the discharge time stated in your manual, 15 minutes being the usual figure, then measure 0 V DC between PA/+ and PO before you touch PB or any braking conductor.