Short answer: give every terminal a job — a field-wiring landing at the cabinet wall, a supply split to several loads, or a voltage-test point — and draw every installed terminal on the schematic, routing-only ones included. Keep the physical path on the panel layout, and let wire length decide nothing: a 120 VAC run routed across a 24 x 20 in [610 x 510 mm] plate loses about 80 mV at 2 A on 12 AWG copper, and no terminal block shortens a wire. The steps below take a build from point-to-point list to an energized, documented panel, with the drop math and the bending-space numbers that set the layout.
When does a panel actually need a terminal block?
Fit a terminal block when the terminal has a job to do: landing a field conductor at the cabinet boundary, splitting one 120 VAC supply to several loads, or giving you a test point where device terminals are cramped; everything else is optional. The three jobs cover nearly every terminal you will draw. A field connection gives external wiring a defined landing at the cabinet wall. A distribution terminal branches one supply — a breaker feed, a 24 VDC bus, an interposing contact — out to several loads. A measurement terminal exposes a test point when the device terminals sit behind a shroud. Direct wiring between two devices with accessible terminals stays direct. A servo power and feedback cable lands on the drive itself, because an intermediate block would add a joint and no function.
| Terminal job | Why it earns the space | What the drawing shows |
|---|---|---|
| Field connection | A defined landing for external conductors at the cabinet wall | The terminal, the field-side address and the device-side destination |
| Supply distribution | Branches one supply to several loads | Every branch, with the arrangement rated for the conductors and circuit |
| Measurement access | A test point where device terminals are hard to reach | The real electrical path through the terminal |
| Routing only | Organizes a bundle; no electrical function of its own | The terminal and its connections, labelled, so the path stays traceable |
Routing-only blocks are accepted practice in a tight cabinet, and every one you install still takes an identifier and a line on the schematic. Each terminal also carries only the current of its own branch, whatever sits beside it. They add up fast when you plan a build: sizing the rail from the connection count — how many terminal blocks you need counts points, not blocks — beats counting row positions.
What goes on the schematic and what stays on the layout?
Every terminal you install goes on the schematic with its own identifier, functional or not; the schematic shows the point-to-point electrical path through each terminal, and a separate panel layout carries the physical placement, duct routes and wire lengths. A schematic documents connectivity, not distance. It draws the actual interconnection: the black 120 VAC conductor from the breaker, through each terminal it lands on, out to its load. The neutral comes back the same way, so a technician never infers a hidden junction. The panel layout drawing, or the CAD cabinet view, carries the physical side: block positions, duct routes, device placement and wire lengths. Where routing affects length, separation or service access, plan it there. Keep the circuit logic true to the circuit rather than bending it to match the path; industry drawing practice makes the same split in I/O schematic standards that separate the functional from the physical.
Both documents must agree on three things: the start point, the end point and every intermediate landing. Before construction, check that every drawn terminal exists in the layout and every installed terminal has a documented purpose and connection. In a training cabinet the schematic doubles as the teaching document; what a PLC cabinet training schematic should include lists the drawing set.
How do you plan terminal blocks before you wire a panel?
Work from a point-to-point connection list before you touch the rail: list every connection, mark which conductors cross the cabinet wall, then assign each terminal a unique identifier that appears on the schematic, the terminal schedule and the physical block. You need four documents before the first wire is cut: the point-to-point list, a terminal schedule, a panel layout drawing and the manufacturer datasheets for the blocks you intend to buy. Then work the list in order:
- List every connection: breaker to loads, neutral returns, interposing contacts, field devices. Mark the conductors that cross the cabinet wall; they become field terminals.
- Give each proposed terminal one of the three jobs from the table, and leave device-to-device wiring direct where a block adds nothing.
- Assign a unique identifier to every terminal and record the destination on both sides in the terminal schedule. Multi-level blocks take one identifier per level.
- Place the rows on the layout: the field row beside the gland entry, distribution beside the breaker, test points within reach of the open door.
- Draw the schematic path through every terminal, then compare the terminal list against the point-to-point connections: every drawn terminal must exist in the layout.
- Size each block from its datasheet — wire range, current rating, short-circuit rating and clamp torque — for the conductor and circuit it serves.
How much voltage does a long 120 VAC run lose inside a cabinet?
A 120 VAC run across a 24 x 20 in [610 x 510 mm] plate loses about 80 mV at 2 A on 12 AWG copper, 0.07% of the supply, so wire length never justifies a terminal; length decides routing, not topology. Take the trainer cabinet as the worked example: a 24 x 20 x 8 in [610 x 510 x 200 mm] wall-mount stainless box, a breaker feeding a relay bank that draws 2 A, and the conductors routed 10 ft [3 m] through the duct. The NEC conductor-property table lists uncoated 12 AWG copper at about 2 ohms per 1000 ft [6.5 ohms per 1000 m] at 75 C, and supply plus return both count, so:
VD = 2 x 2 A x 10 ft x 2 ohms / 1000 ft = 0.08 V
That 80 mV is 0.07% of a 120 V supply. Length starts to matter only when distance and current rise together: the same 2 A pushed 100 ft [30 m] out to a remote machine loses 0.8 V, 0.7%. The run that forces a decision is that same 100 ft at 10 A, which drops 4 V, or 3.3% of the supply. The fix there is copper, not joints: 10 AWG at about 1.2 ohms per 1000 ft brings the same run to 2.4 V. A terminal block changes none of these numbers. Fitting the supply and its relays into a small box, with their heat, is its own layout problem — a 120 VAC power supply and relay inside a small enclosure covers it.
What clearance do terminal landings need on the mounting plate?
Give terminals room to land their wires: NEC 312.6 sets the wire-bending space at terminals in cabinets, 2.5 in [63 mm] for 2 AWG with one wire per terminal, and control wiring still needs strip, bend and tool clearance at every block. NEC 312.6 splits the rule across two tables: Table 312.6(A) applies where the conductor does not enter or leave the wall opposite its terminal, and Table 312.6(B) where it does. The 2.5 in figure for 2 AWG comes from Table 312.6(A). Control wire at 14 AWG needs a fraction of that, but every landing still needs room to strip, bend and clamp.
Every terminal row lives beside wire duct. Fill the duct to at most 50% of its interior cross-section; that is the fill the wiring-duct makers set in their fill tables, citing NFPA 79-2012 section 13.5.2. Leave a shop-rule 2 in [50 mm] between a block row and the duct wall, enough for a screwdriver tip and the wire riser. Row-to-row spacing and finger-duct clearance carry their own numbers — see terminal block row spacing and finger duct clearance. The whole backplate, from duct runs to DIN rail to grouping by voltage class, is laid out in the backplate and DIN rail layout guide.
How do you make field wiring and test points easy to service?
Build the field row where the conductors enter and the test row where you can reach it with a meter: field landings sit on a dedicated terminal row next to the gland entry, and test points sit within reach of the open door. Group the field terminals in one labelled row at the entry wall: sensors and actuators from the plant side all land in one place, which is what makes fault-finding fast. Multi-level blocks stack two or three circuits in one position; keep every level on one independent circuit and give each level its own identifier, so a field wire cannot land on the wrong potential. Scaled up, the same discipline keeps a distributed I/O cabinet maintainable — remote I/O panel design for maintainable field wiring shows it panel by panel.
Test points belong where a meter probe reaches without pulling a device forward. One safety note before the first probe: with 120 VAC present, verify absence of voltage and dress to the arc-flash boundary the panel label calls for; the PPE for working a live 120 VAC junction box is its own checklist.
When field wiring comes through the wall of a washdown box, the entry hardware decides the rating. Our 304 and 316L stainless junction boxes are rated NEMA 4X / IP66 by the manufacturer; they are not UL listed, and the rating holds only when every conductor enters through a gland matched to the cable and seated in a sealed cutout. Plan the gland row into the cutout drawing when you order — custom stainless enclosures are built to your drawing in 10 business days. Where a splice box ends and a terminal enclosure begins is its own line to draw — junction box vs terminal enclosure sets it.
What checks prove the finished panel matches the drawings?
Energize only when the as-built wiring, the terminal identifiers, the schematic and the layout agree: trace every conductor end to end, compare the installed blocks with the terminal schedule, and clear every missing or extra terminal before the first power-up. Run the checks de-energized and locked out:
- Compare every installed block against the terminal schedule, counting positions and levels. Clear every missing, extra or differently identified terminal.
- Trace each conductor end to end: breaker feed, neutral return, branches, external circuits. The built path must match the drawn path, intermediate terminals included.
- Torque every clamp to the value printed on the block and tug-test each conductor. The common failure is strip length, not clamp force — why wire works loose in a screw-clamp terminal covers the strip check.
- Check continuity of the intended path, and confirm nothing shares a neutral connection with another circuit.
- Confirm the room in front of the panel. NEC 110.26(A) calls for working space at equipment serviced while energized: at least 3 ft [900 mm] deep for 0-150 V to ground in Condition 1, 30 in [750 mm] wide or the equipment width, with the door opening 90 degrees.
If the panel is a listed assembly, two markings come out of the terminal plan. UL 508A requires the panel to be marked with its short-circuit current rating, the lowest SCCR of the installed components, terminal blocks included. A panel built into a Type 3, 3R, 3S, 4, 4X, 6 or 6P enclosure also carries an Outdoor or W marking on the inside of the panel, again under UL 508A. What sets a block's own contribution is covered in terminal block SCCR in a control panel.
The decision, case by case: a conductor crossing the cabinet wall gets a terminal, drawn and labelled. One supply feeding several loads gets a distribution terminal sized for its conductors. Cramped device terminals get a test-point terminal. Two devices with accessible terminals get a direct wire. A run that feels too long gets its drop computed with the math above, then bigger copper if the number matters — and whatever you install goes on the schematic with its identifier before the first wire lands.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 6 × 6 × 4 in | 304 stainless | 6 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 8 × 6 × 4 in | 304 stainless | 8 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 10 × 8 × 4 in | 304 stainless | 10 x 8 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Do routing-only terminal blocks go on the schematic?
Yes. Every installed terminal appears on the schematic with its own identifier, whether it carries a logical function or just organizes a bundle. The schematic draws the real electrical path through it, and the terminal schedule records the connections on both sides. Physical placement stays off the schematic: routing, duct paths and wire lengths belong on the panel layout. Remember a routing-only block still adds one clamp joint per conductor, so give it a purpose - organization or a test stop - rather than using it to fix a routing problem the layout should solve.
Can a terminal block shorten a long wire run or cut its voltage drop?
No. Drop depends on current, length and conductor resistance, and a terminal changes none of them: a 2 A load 10 ft [3 m] out on 12 AWG copper loses about 80 mV, and the same load at 100 ft [30 m] loses about 0.8 V, with or without a joint in the middle. If a drop matters, upsize the copper: 10 AWG has about 1.2 ohms per 1000 ft against 2 for 12 AWG, about a 40% cut in both resistance and drop.
How do multi-level terminal blocks help a bank of field signals?
A two- or three-level block stacks independent circuits in one block position, so 24 field signals fill 24 positions instead of 48 or 72 - a rail length you can read straight off the layout. Keep every level on one circuit and give each level its own identifier, because the field wire lands on whichever level the technician opens first. Levels that mix circuits are the classic hidden junction; the schedule and the block labels are what prevent it.
What keeps a field-wiring landing from wrecking the enclosure rating?
The entry hardware does. A stainless wall-mount box rated NEMA 4X / IP66 by the manufacturer - not UL listed - holds that rating only when every conductor enters through a gland matched to the cable OD and seated in a sealed cutout. One lower-rated gland sets the whole assembly to its rating. Plan the gland row into the cutout drawing together with the terminal layout, and keep field landing rows low in the box so washdown water cannot run toward the blocks.





