Count clamping points, not blocks. One conductor per point is the working rule, and a neutral strip serving 20 outgoing conductors plus one incoming neutral needs 21 points: 11 two-point blocks when the wires reach both sides, or 7 three-point blocks. Keep two conductors off one screw unless the datasheet prints that exact pair. For control wiring of 14 AWG [2.5 mm²] and smaller, 5 mm and 6 mm wide housings are the accepted pick, and density comes from center-jumpered blocks, not doubled clamps.
Count points, not housings
A clamping point is one termination: the screw or spring cage that grips a single conductor. A feed-through block carries two of them, one each side of a shared internal bar, so it lands two conductors on one node without doubling a clamp. Single-circuit housings go further and give you three or four points on the same node. That is why 'one wire per block' is the wrong unit: the housing is plastic, the point is the connection.
A center jumper ties adjacent housings into one electrical node — one long terminal, in effect. It adds zero clamping points. What it buys you is density, because every point on every bridged housing stays usable.
| Arrangement | Points you get | Where it fits |
|---|---|---|
| Feed-through block, wires reach both sides | 2 | field side to component side |
| Feed-through block, wires reach one side only | 1 | strips tight against a duct wall |
| Single-circuit block, 3 points | 3 | one node feeding three directions |
| Single-circuit block, 4 points | 4 | distribution runs with branching |
| Two-level housings bridged by jumpers (one maker's example) | 8 per housing, 16 per pair | large common and neutral runs |
| Two conductors under one clamp | 0 extra | only with a listing for that pair |
What you need before you count
Five inputs set the count before you order anything:
- The schematic with every node marked: each group of conductors sharing one potential is one count.
- The wire list with sizes: the largest conductor in the panel picks the block family.
- The family datasheet: clamp range, the conductor combinations each clamp is listed for, and the jumper's current rating.
- A routing sketch showing which side of the strip each wire arrives from, field or component.
- Your plant or customer spec, when it sets a one-conductor-per-terminal rule that outranks the savings.
The count in five steps
- List every conductor on the node. Twenty outgoing conductors plus one incoming neutral is 21 conductors, so 21 points.
- Set the points per housing from the routing: 2 for a feed-through block reached from both sides, 3 or 4 for single-circuit housings, and 1 when every wire arrives on one side.
- Divide the points needed by the points per housing and round up.
- Add spares: at least one whole spare housing per run, with spare points on occupied housings labelled separately from spare housings held for new circuits.
- Read the current path: the jumper nearest the feed carries the largest share of the load, so feed a long strip near its middle. The worst segment then sees about half the strip current instead of all of it.
5 mm or 6 mm: picking the family
For panels with nothing larger than 14 AWG [a 2.5 mm² clamp], miniature families 5 mm and 6 mm wide are the standard choice, and both land one 14 AWG conductor per point. Wider housings buy rail length, not connections. When one conductor in the panel is larger — a 2 AWG incoming neutral, say — pick that clamp from its datasheet range and let the width follow. Insulation-displacement blocks are the other route: no stripping, and the design enforces one conductor per point on its own.
Do the rail arithmetic early. Twenty-one housings at 6 mm occupy 126 mm [5 in] of rail one-per-conductor; the same 21 conductors jumpered from both sides fit in about half that.
Two conductors under one screw
Most screw clamps are listed for one conductor. Terminal blocks are evaluated to UL 1059 (CSA C22.2 No. 158 in Canada), and the listing covers specific printed combinations, not the space you can see under the screw. Some screw-clamp lines do carry a listing for two conductors per connection. One maker's spec sheet rates its #2-14 AWG openings for two stranded copper conductors: two #8, two #10, two #12 or two #14. The pair is always the same size twice, never mixed.
So one conductor per clamping point stays the default, and density comes from jumpers and multi-point housings. A plant spec that allows two per terminal still stops at what the block's own listing prints. Before you double anything, read two wires on one terminal for the ferrule, torque and inspection side of a shared clamp.
A neutral strip: 20 outgoing conductors, 1 incoming
This is the classic counting case: a jumpered neutral run in a control panel. The inputs, each from its own document:
- 20 outgoing neutral conductors, 14 AWG, arriving at the field side (wire list)
- 1 incoming circuit neutral, 14 AWG, landing from the component side (one-line drawing)
- 6 mm two-point feed-through housings with center jumpers (family chosen for 14 AWG wiring)
- Both sides of the strip reachable: field duct below, component duct above (routing sketch)
The rule in words: points needed equals the conductors on the node; housings equal points needed divided by points per housing, rounded up; spares are what is left over.
The arithmetic:
- Points: 20 outgoing + 1 incoming = 21 points.
- Two-point housings: 21 ÷ 2 = 10.5, round up to 11 housings = 22 points, 1 spare.
- Three-point housings: 21 ÷ 3 = 7 housings = 21 points, 0 spares.
- Four-point housings: 21 ÷ 4 = 5.25, round up to 6 housings = 24 points, 3 spares.
- One-side routing: 20 housings for the outgoing conductors, incoming neutral on the far side of the first = 40 points with 19 stranded empty.
- Rail length: 11 × 6 mm = 66 mm [2.6 in], against 126 mm [5 in] one-per-conductor.
| Layout | Housings | Points provided | Spare points |
|---|---|---|---|
| Two-point, both sides | 11 | 22 | 1 |
| Three-point | 7 | 21 | 0 |
| Four-point | 6 | 24 | 3 |
| One side only | 20 | 40 | 19 on the far side |
The decision: order 11 two-point housings as the minimum that works, or 12 to hold a spare housing and 3 free points. For three-point housings, 7 is the floor and 8 leaves 3 spares. The threshold is 21 points — 10 two-point housings give 20, and the incoming neutral then has no home short of doubling a clamp. This run carries neutrals only: equipment grounds land on the ground bus, because NEC 250.6 keeps neutral current off metal parts. For whether the panel needs that bar at all, read does a control panel need a neutral conductor.
Spares that are actually spare
A spare point on an occupied housing accepts one more wire on a node you already have. A spare housing accepts a new circuit, which may want a different block type or its own jumper group. Label them as two different things on the drawing, because in two years nobody remembers which the empty position was. One whole spare housing per run is the floor; beyond that, size spares from the growth the job actually forecasts.
Group the strip so growth lands in the right run — field I/O together, power together. The grouping method in junction box terminal layout works the same decision for I/O boxes.
Fitting the strip into the panel
Your count becomes rail length, duct and clearance. Hold wire duct to 50% fill: NFPA 79-2012 section 13.5.2 is where one duct maker sets all its fill tables, and 50% of the cross-section is all that round cables realistically allow. A large incoming conductor needs bending space at its terminal — NEC 312.6 gives 2.5 in [64 mm] for 2 AWG with one wire per terminal — so land the big neutral at the end of the strip where the wire has room.
When the strip pushes you into a taller box, check inside dimensions on the enclosure size chart. The backplate and DIN rail layout guide sets the duct and rail spacing around it, and junction box height with bottom conduits and terminal blocks covers bottom-entry boxes. A custom stainless enclosure with your cutouts is delivered in 10 business days, counted from your approval of the drawing.
Checks when the drawing is done
- Every conductor on the wire list maps to one numbered point, and on every node the points provided meet or beat the conductors listed.
- No clamp carries two conductors unless the datasheet prints that exact pair.
- Jumpers are rated for the feed current, and the feed sits near the middle of long runs.
- Spare points and spare housings carry different labels.
- Both sides of every housing are reachable without wires crossing a duct.
- Duct fill sits at or below 50%, and the largest incoming conductor has its bending space.
Mistakes that cost the count
Four errors cover most short strips. Rounding down: 21 points ÷ 2 is 10.5, and 10 housings hold only 20 conductors. Forgetting the incoming feed, which costs a point on every distribution run. Counting a jumper as a connection point, which leaves a conductor with no clamp. And filling the run to 100% — 7 three-point housings with zero spares — so the first panel addition lands under someone else's screw.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 6 × 6 × 4 in | 304 stainless | 6 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 8 × 6 × 4 in | 304 stainless | 8 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 10 × 8 × 4 in | 304 stainless | 10 x 8 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can two wires share one terminal block screw?
Only when that exact clamp carries a listing for the pair. One maker's specification sheet rates its #2-14 AWG openings for two conductors: two #8, two #10, two #12 or two #14 stranded copper, always the same size twice. Terminal blocks are evaluated to UL 1059, and the listing covers the printed combinations — a clamp that physically fits two wires is permission for nothing.
Should I use 5 mm or 6 mm blocks for 14 AWG wiring?
Either works: both families land one 14 AWG [2.5 mm²] conductor per point. Pick 5 mm when rail length is tight — 21 housings save about 21 mm [0.8 in] over the 6 mm family — and 6 mm when you want more room for ferrules and fingers. In every case match the family to the largest conductor in the panel, not to the average.
How many spare terminal blocks should a strip have?
At least one whole spare housing per run, plus whatever growth the job forecasts. In the 21-point example, 11 two-point housings leave only 1 spare point, so order 12; 7 three-point housings leave none, so order 8 and keep 3 spare points. Label spare points on occupied housings separately from spare housings held for new circuits.
Should neutrals and grounds share one terminal strip?
No. NEC 250.6 keeps neutral current off metal parts: circuit neutrals land on an isolated neutral bar and equipment grounds on the ground bus, as two separate strips. Insulated grounding conductors of 6 AWG and smaller are green or green with yellow stripes under NEC 250.119. Count each strip as its own node when you work the housing count.





