Short answer: land the incoming ground on a PE terminal block snapped onto the same DIN rail as the supply, then run a jumper of the same wire size from that block to the supply's PE terminal. On a 15 A branch, NEC Table 250.122 calls for a 14 AWG copper equipment grounding conductor, and the jumper matches it. If you ground the supply through its DIN clip alone, the whole fault path rides on a spring joint and on whatever finish sits under it. The block bonds the rail for every device on it; the wire carries the fault. The loop behind this is the one described in the enclosure grounding and bonding guide.
What the DIN clip actually carries
A DIN clip is a spring joint, not a terminal. Its grip comes from spring pressure, plating and the finish on the rail, and none of it appears as a rated current on the clip's datasheet. Standard TS-35 top-hat rail is 35 mm [1.38 in] tall, and steel rail is commonly 1 mm [0.04 in] thick, 2 mm [0.08 in] on heavy-duty runs. On bright galvanized rail a clean clip can read milliohms; under powder coat or anodizing the same joint can read ohms or open. Heat cycling, vibration and a loosening screw move that reading over time, so a bond you measured last year is not the bond you have today. If you are choosing clips for a ground-critical rail, DIN rail spring clip selection guide compares the spring types and how each one grips.
Three ways to wire it, and the one to use
What separates the arrangements is the supply's internal fault path: the route a chassis fault takes back to the source.
| Wiring | Supply's fault path | Relies on the clip? | Verdict |
|---|---|---|---|
| Incoming ground straight to the supply PE terminal | Wire, end to end | No | Works for the supply; the rail and its other devices stay unbonded |
| Incoming ground to a PE block, jumper from block to supply PE terminal | Wire, end to end | No | Use this one: a wired supply and a bonded rail |
| Incoming ground to a PE block, supply PE terminal left empty | Clip contact only | Entirely | Avoid it: finish under the clip can leave the chassis live |
The second arrangement costs one jumper and buys both things. The supply's fault path is copper from end to end, and the block's metal feet bond the rail so switches and controllers have a parent to connect to. The jumper does not fight the clip either: both paths meet at the same protective earth node, so they share fault current instead of competing.
Sizing the bond for a 10 A supply on a 15 A branch
Take the supply most panels carry: a DIN-mount unit giving 24 VDC at 10 A on a 120 VAC input.
Inputs, and where each one comes from:
- Output 24 VDC at 10 A, which is 240 W: read from the supply nameplate.
- Efficiency 0.90: an assumption for this example; use the figure on the supply's own datasheet.
- Input 120 VAC: the branch the panel hangs on.
- Upstream overcurrent device 15 A: the breaker ahead of the panel; the ground conductor follows it, not the load.
- PE block rating: 20 A continuous, the figure a typical DIN-rail grounding block's datasheet lists.
The rule in words: the jumper from the PE block to the supply's PE terminal is sized like the incoming equipment grounding conductor, and that conductor is sized from the rating of the overcurrent device ahead of it, per NEC Table 250.122.
The arithmetic: input power is 240 W ÷ 0.90 = 267 W. Steady-state input current is 267 W ÷ 120 V = 2.2 A. A 15 A device takes a 14 AWG copper equipment grounding conductor, so the jumper is 14 AWG copper. The block carries 2.2 A against its 20 A rating, a margin of 20 ÷ 2.2 ≈ 9.
The decision: land the incoming 14 AWG ground on the block and jumper 14 AWG to the supply PE screw. The same inputs set the ceiling: 20 A of block at 120 V is 2,400 VA of input, which at 0.90 efficiency is 2,160 W of output, or 90 A at 24 V; above that, move to a wider block. A fault current is far larger than a continuous rating, so the same datasheet's short-time figure is what carries the breaker's trip current, and the jumper size still follows the breaker, not the load.
The wire sizes behind a jumper in a metal box are worked from the other end in bonding jumper size inside a metal junction box.
What you need
- Grounding (PE) terminal blocks with metal feet that bite the rail; the 20 A class covers the supply in the example.
- Copper jumper wire in the incoming ground's size: 14 AWG on a 15 A branch.
- Crimped ferrules or ring terminals and a crimp tool, in the style the supply's manual shows for its PE screw.
- A torque screwdriver, set to the value printed on the block or the supply.
- A multimeter that reads from milliohms to ohms for the checks below.
- A lockout kit and a voltage tester for step 1.
- 35 mm [1.38 in] steel TS-35 rail screwed to a bare-metal backplate.
Wiring the rail, the block and the supply
- De-energize the 120 VAC feed, lock it out and prove absence of voltage at L and N with the meter.
- Screw the rail to the backplate through its mounting slots with toothed washers under the heads. In one of our stainless wall-mount junction boxes the removable stainless panel is bare metal, so the rail screws bond directly to it; the box is manufacturer-rated NEMA 4X / IP66 and not UL listed.
- Snap a PE block beside the supply and land the incoming ground wire on it. Where that wire enters through a gland, sealing a ground wire where it leaves the box covers the gland and drain detail.
- Land L and N on the supply's line terminals, and leave the bending space the conductors need at the terminals; NEC 312.6 sets it for cabinets and cutout boxes. When a box runs out of depth, custom enclosures built to the size you need give it to you in one piece, delivered in 10 business days from drawing approval.
- Crimp the 14 AWG jumper and run it from the PE block to the supply's PE screw.
- For each other device with a PE terminal — a switch, a compact PLC, a signal conditioner — run its own lead to a PE block, in the size its instructions show. The clip is not that lead.
- Torque every termination to the printed value and tug each wire once before the covers go on.
Checks before you energize
Four meter readings tell you the bond is real:
- PE block to the supply chassis: a fraction of an ohm, steady.
- PE block to the housing of every other device on the rail: the same reading. An ohm or two, or a number that drifts when you press the device, is a clip riding on finish.
- Incoming ground lug to the far end of the rail: continuity along the whole rail, not just at the block.
- Lift the jumper at the supply and repeat the first reading. The difference is what the clip was carrying; a near-open circuit with the jumper off means the clip never carried anything. Refit the jumper, torque it, and confirm the reading comes back.
Devices that share the rail
A switch or controller on the same rail is grounded when three things hold. Its maker must rate the clip or housing as a PE connection, or give the device a ground terminal. Its contact to the PE block must measure clean. And the rail's rated current, listed by material and cross-section in the rail datasheet, must cover the run between device and block. A device with a PE screw gets a wire even when the clip reads clean, because the screw is the path its maker tested. A device with no terminal and no PE-rated clip stays on the meter: press it, watch the reading, and if it moves, snap it beside a PE block and run the lead. Shields and functional-earth leads for sensors and comms are a separate decision; they follow the signal design, not this bond.
Mistakes that break the ground path
- Landing the neutral on the PE block. NEC 250.6 aims to keep neutral current off metal parts; neutrals land on the isolated neutral terminal and grounds on the ground bus. Separating neutral and ground in a subpanel on a 4-wire feeder walks the feeder case.
- A jumper smaller than the incoming ground. It sits in series with the whole fault path, so it sets the path's weakest link.
- Counting on rail length instead of a wire. The rail is a parallel convenience between block and supply, never the only path.
- A painted backplate with plain screws. The rail floats on powder coat; toothed washers or a scraped bare-metal spot fix it.
- A nonmetallic box. There is no metal path to bond to, so the equipment grounding conductor lands on its own terminal; the EGC in a plastic enclosure shows the landing.
- Skipping the lift test. Without it you never learn how much of the bond was spring pressure.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 6 × 6 × 4 in | 304 stainless | 6 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 8 × 6 × 4 in | 304 stainless | 8 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 10 × 8 × 4 in | 304 stainless | 10 x 8 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can the DIN rail itself serve as the grounding conductor?
It can serve as a bonding conductor along its length; a rail's current rating depends on material and cross-section, and the rail datasheet lists it. A standard 35 mm [1.38 in] steel rail is commonly 1 mm [0.04 in] thick. The weak element is the clip joint, not the rail: spring pressure over paint or oxidation reads high today and something different next month. Wire the supply's PE terminal to a PE block, and let the rail serve the smaller devices that have no ground terminal of their own.
What size wire jumps from the PE block to the supply's PE terminal?
The size of the incoming equipment grounding conductor: 14 AWG copper on a 15 A branch, per NEC Table 250.122, which sizes that conductor from the overcurrent device ahead of the panel. In the worked example above, a 2.2 A input rides a 14 AWG jumper, with the 20 A PE block sitting at about a ninth of its continuous rating.
Does the block-to-supply jumper create a ground loop?
No. The jumper and the clip contact join the chassis to the same protective earth node, so they are parallel fault paths at one potential and simply share current. Noise loops are a signal-reference problem: shields or functional-earth leads tied to earth at two points that sit at different potentials. Keep those leads a separate decision from this bond.
How do I ground a rail device that has no ground terminal?
Meter it: housing to the PE block should read a fraction of an ohm and stay there when you press on the device. A drifting or ohms-class reading means the clip sits on finish, so snap the device beside a PE block and run its own lead. If the datasheet neither rates the clip as a PE connection nor offers a terminal, treat the lead as mandatory.





