Short answer: an earth terminal that reads open to the drive's heat sink is usually the drive's design, not a defect. Land the terminal the manual names on the cabinet PE bar with one short dedicated conductor, bond the heat sink to the cabinet as its own joint, and test the two jobs separately. Size that conductor from the overcurrent device ahead of the drive — a 20 A breaker takes 12 AWG copper — and hold the finished joint to the machine-panel figure of 0.1 Ω at 10 A. Molded earth symbols next to case screws are casting details, not wiring information.
Why does the drive earth terminal read open to the heat sink?
Because on many small drives the earth terminal returns only the internal suppression parts — filters and varistors — while the case bonds separately: a 3.0 kW drive measured with terminal 9 open to its heat sink, and a 2.2 kW sibling with no continuity on any of three earth-marked screws.
Inside such a drive, the terminal's job is the return path for suppression components on the input side. Where a drive carries few of those parts, the designer can leave the terminal off the case entirely and still satisfy the drive safety standard. The case is a separate piece of metal with its own duty: an exposed conductive part that needs a fault path once you mount it.
Four causes cover this reading, most likely first:
- Design isolation. The terminal feeds filter capacitors and varistors only; the case is bonded elsewhere or left to the mounting. On the 2.2 kW example, the manual named only E as the ground, and none of the three marked screws showed metal behind it.
- Coatings under the mounting hardware. Paint or anodizing under the mounting bolts gives the case a fragile touch bond that shares nothing with the terminal.
- Meter behavior. A buzzer trips somewhere between a few ohms and a few tens of ohms, meter by meter, so a real but resistive joint beeps on one meter and stays silent on another.
- A genuine defect. A loose internal strap or a cracked terminal post. Rare, and it only matters where the manual ties the terminal to the case.
Read the result as information about the drive's construction, and take the wiring decision from the manual instead of the housing.
Which earth point does the drive manual actually name?
The terminal the hardware manual names — E, printed as terminal 9 on the 3.0 kW example — is the only earth connection you can rely on, and every molded earth symbol beside a case screw carries no weight until a test or that manual gives the screw a job.
Molded symbols are cast into the housing and stay the same across variants whose internals change. A screw beside an earth symbol may clamp two housing halves, bond a circuit board, or sit over plastic; on the 2.2 kW example, all three marked screws read dead to everything. The manual is the only document that names a termination, so wire to the name it prints and leave the rest of the screws alone.
One practical limit: the terminal post on a small drive is short and light. It takes one conductor, at the size and torque the manual prints, and everything heavier belongs on a bar.
The conductor from that terminal is the fault path the electrical code cares about. NEC 250.4(A)(5) calls it the effective ground-fault current path and rules the earth itself out of that path, so the bar, the jumpers and the conductors do the work. The grounding and bonding guide walks that path in depth.
What do the continuity readings point to?
Each reading pattern points at a different part of the earth system, and five of them cover nearly every case you will meet on a small drive.
- Beeps between the two lower screws, silent from the manual's terminal. The screws bond the case halves and the terminal is a suppression return. The drive is healthy; wire the terminal to the bar anyway.
- Beeps that appear only once the drive is bolted to the plate. The cabinet hardware is the whole case bond. Test that joint on its own and add a strap across the coating.
- Open everywhere, including the manual's E, with external leads lifted. Read the manual again; where it says E bonds the case, the drive goes back to the vendor.
- A reading that falls from megaohms to milliohms when you tighten a bolt. A coating-dependent contact. NEC 250.12 wants paint and enamel stripped from threads and contact surfaces at grounding and bonding connections, unless the hardware is designed to make its contact through the coating, so bare that face or fit bond washers that do it for you.
- Numbers that wander under finger pressure. Loose hardware or a corroded contact. Torque it, or replace the joint with a conductor.
Write each number down as you take it; the pair of readings before and after mounting is what tells the two jobs apart.
How do you measure the earth path without fooling yourself?
De-energize both supplies, wait the discharge time the drive label states (five minutes is a common figure on small frames), zero the meter leads against each other, and lift every parallel path before you read — otherwise the cabinet, not the drive, is making the beep.
- Open every supply that feeds the drive and the motor, apply your site lockout, wait the stated discharge time, and measure the DC bus at its test points before touching a terminal.
- Short the probes together and note the lead reading; a two-wire meter reads its leads plus your joint, and that matters at these resistances.
- Lift the drive off the plate or take out its mounting bolts, and disconnect the external PE leads, so only the drive's own parts sit in the circuit.
- Measure the manual's terminal to the heat sink, each earth-marked screw to the heat sink, and each screw to the terminal. Record the numbers.
- Remount, then measure heat sink to the cabinet PE bar across bare metal.
- Finish with the machine-panel bond test: IEC 60204-1 calls for at least 10 A held for at least 10 s, with 0.1 Ω or less between the drive's PE terminal and the PE bar. A low-resistance tester does that; the buzzer only screens.
The readings before and after remounting are the interesting pair. If the heat sink only bonds once it is bolted, the bond is the cabinet's work, and the strap you add should make it independent of one bolt's coating.
How big should the earth conductor be, and how short?
Size it from the overcurrent device ahead of the drive: NEC Table 250.122 sets the equipment grounding conductor by that device's rating, so a 20 A breaker calls for 12 AWG copper, and the drive manual's own figure wins where it asks for more.
Worked example, with the numbers to copy: a 2.2 kW drive rated about 10 A at 230 V sits behind a 20 A branch breaker. NEC Table 250.122 gives 12 AWG copper for a 20 A device. Half a metre of that jumper adds about 2.6 mΩ, because 12 AWG copper runs near 5.2 mΩ per metre at 20 °C, so the fault path stays dominated by the bar and the rest of the circuit rather than the jumper. UL 508A sizes a listed panel's grounding conductor from the overcurrent device ahead of it on the same basis, and a drive manual can ask for a larger PE conductor for EMC; use the larger of the two sizes. Keep the jumper at 0.5 m or less, run it flat against the backplate, and land the motor's PE conductor on the bar at its own table size, set by the motor branch's device.
Does the heat sink need its own bond to the cabinet?
Yes — fit a short, flat bond across the mounted joint and test it as its own item, because the heat sink carries PWM common-mode current where inductance, not DC resistance, decides the impedance.
A straight round wire shows about 1 µH of inductance per metre in free air. At 1 MHz, a frequency a PWM switching edge reaches as it rings, that metre is about 6 Ω of impedance; the same metre of 12 AWG is about 5 mΩ at 60 Hz, where the fault clearing actually happens. The common-mode current sees the inductive number and takes any parallel metal it can find, which is why the drive, the heat sink and the motor cable shield all need short, wide, direct metal rather than one long thin lead.
So strap the heat sink to the backplate or the PE bar across bare metal, baring the coating at the contact faces as the coating rule above sets out. Terminate the motor cable shield in a 360-degree clamp at the gland plate instead of a pigtail, and size that link the way the gland-plate earth continuity article works out. Keep the drive's own PE run short and direct, as the VFD ground wiring article describes for the whole cabinet. The same physics gives welding returns their own low-resistance bond: an incidental bolted touch contact carries sensing current happily and falls over when real current flows.
Where should all the earths land: one bar or two points?
One bar: the drive's jumper, the motor PE conductor, the cabinet bond and the enclosure itself all land on a single PE bar, and two attachment points tied to that bar are one earth system, not two competing ones.
The worry behind the question is two earth points breaking a star rule. The star discipline decides where signal commons meet; the protective network is a mesh by nature, and any part with a rated fault path back to the bar passes. Even with two supplies in one cabinet, every protective conductor bonds to a single ground bar, which the two-supply grounding article works through in full. When the panel collects ten earth cables, give each conductor its own terminal on a bar rather than stacking them on one stud; the earth bar versus earth stud article makes that selection with the panel size that goes with it.
When is the drive actually faulty?
Almost never on this reading alone: the drive is faulty only where the manual ties the terminal to the case and the joint still reads open with every external path lifted, or where the terminal hardware is loose, corroded or too small for its conductor.
Work the checks in order and the drive usually clears itself: wire the terminal to the bar, add the heat-sink strap, and the installation is right even though the buzzer never agreed. Re-test after any drive swap, because a replacement of the same rating can bond internally where the old one did not, and the reverse. Where the manual does tie the terminal to the case, the open reading survives every parallel path lifted, and the hardware is sound, send your measurements to the drive vendor and keep the drive out of service until they answer. A continuity number from one unit tells you nothing about another; production runs and variants differ, which is why the manual plus your own measurement decide.
What should the next enclosure give the earth system?
A plain stainless mounting panel, space for a PE bar beside the drive, and cutouts for the terminal cover and the shield clamps — which is what our wall-mount boxes do: you set material, size and every cutout, and the panel comes bare.
A stainless backplate has no paint on it, so every bond point starts bare and the coating rule never comes into play. Our stainless wall-mount junction boxes carry a hinged gasketed door and a removable mounting panel, and each box is rated NEMA 4X / IP66 by the manufacturer; not UL listed. They are delivered in 10 business days, anywhere in the world, counted from your order; for custom work, from your approval of the drawing. Order the panel with room beside the drive for the bar, and put the bond retest on your commissioning sheet next to the torque checks.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 30 × 24 × 10 in | 304 stainless | 30 x 24 x 10 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can several earth conductors share the drive's earth terminal?
One jumper at the terminal, everything else on the PE bar. The post on a small drive takes a single conductor at the torque the manual prints; stacked lugs split the clamp pressure and work loose with vibration. The motor PE, the cabinet bond and the enclosure bonding point each get their own terminal on the bar, where a loose connection shows up as a number instead of a mystery.
Does the earth terminal still do a job when the drive has no input filter?
Yes. The terminal stays the drive's documented PE point whether the board behind it carries filters and varistors or almost nothing, and a later filter or board revision may use it. Wire it to the bar anyway, at the size the overcurrent device ahead of the drive sets, and leave the case or heat-sink duty to its own tested strap. An unwired PE terminal is a finding on any inspection, whatever the drive does internally.
How often should the earth bonds be retested?
At commissioning and after any drive swap or service that opened a bond joint. Record three numbers each time: drive terminal to PE bar, heat sink to PE bar, and the 10 A bond-test reading in ohms. Anything drifting above the 0.1 Ω machine-panel figure points at a loosened or corroded joint, and the fix is a cleaned contact face or a new strap rather than a firmer screwdriver.
What earth conductor size suits a 3.7 kW drive on a 30 A breaker?
10 AWG copper. NEC Table 250.122 sizes the equipment grounding conductor from the overcurrent device ahead of the load, and a 30 A device takes 10 AWG — one size heavier than the jumper behind the 20 A example. Where the drive manual asks for a larger PE conductor for EMC reasons, the manual's size wins, and the PE bar should have a terminal that accepts it.





