Email us

Este artículo está en inglés. Ver el sitio en español

Cet article est en anglais. Voir le site en français

Dieser Artikel ist auf Englisch. Website auf Deutsch ansehen

Este artigo está em inglês. Ver o site em português

本文为英文。 查看中文网站

Grounding two supplies in one cabinet: bond to a single ground bar

Land both incoming equipment grounding conductors, the enclosure bond and the DC negative on one copper ground bar. The metal cabinet is a compliant bonding path under NEC 250.96(A), so a second bar changes nothing. In the worked 40 A / 30 A, 120/208 V cabinet, the common bond lifts fault current from about 1000 A to about 1430 A and drops the wall's lift during the fault from about 60 V to about 33 V.

NEMA4 Enclosure engineering team · Published November 24, 2026 · 9 min read

Run both feeds into one ground bar and land everything on it: the larger cord's green conductor, the smaller cord's green conductor, the bond to the enclosure wall and the DC negative. The metal cabinet itself is a compliant bonding path, so a second bar buys nothing. One bar keeps every fault path short and every connection in one place you can inspect. The worked cabinet here is a 120/208 V three-phase panel on a 40 A motor feed and a 30 A feed for heaters and a 24 V DC supply running 10 A. Every number below comes from that layout, and each section shows what moves when your cord lengths or feed sizes differ.

Do two supplies in one cabinet need one ground bar or two?

One bar serves both supplies: land the motor feed's equipment grounding conductor, the heater feed's equipment grounding conductor, the bond to the enclosure and the DC negative on the same bar. The metal cabinet is a compliant bonding path that joins everything you land on it.

Wired either way the result is the same, because the steel wall ties the grounding points together. That is why the choice between one bar and two is about workmanship, not about correctness. One bar still wins on three counts: both fault paths get the shortest return, you have a single point to inspect and re-torque, and the DC reference gets one defined home.

Each cord keeps its own green conductor, sized from its own breaker, and the bar joins the two without merging the feeds. The grounding and bonding guide covers the fault-path rules behind this in depth.

What does the NEC require when two feeds land in one cabinet?

The code cares that every metal part can carry the fault current any feed can impose. NEC 250.96(A) requires raceways, cables, equipment and enclosures to be bonded together so they can safely conduct that current. The larger feed imposes more than the smaller one.

Rule What it asks of your cabinet
NEC 250.96(A) Bond the metal parts — raceways, cables, equipment, enclosures — so they can carry the fault current the feeds can impose; the wall and the bar carry the larger feed's level
NEC Table 250.122 Size each equipment grounding conductor from the overcurrent device ahead of it: each breaker governs its own cord's green conductor
NEC 250.12 Remove paint, lacquer and enamel from contact surfaces at grounding connections; brushed stainless walls are bare metal already
NEC 250.4(A)(5) The earth is not part of the effective ground-fault current path, so fault current returns on copper, and a ground rod adds nothing to clearing
NEC 250.6 Keep neutral current off metal parts: the two neutrals land on an insulated neutral terminal, the grounds on the bar
NEC 250.119 Insulated equipment grounding conductors 6 AWG and smaller are green or green with yellow stripes

A cabinet with motor circuits, heaters and a 24 V DC supply meets the definition NEC 409.2 sets for an industrial control panel: two or more power circuit components, control circuit components, or both. UL 508A is the standard for listing one; the UL 50E listing guide explains when an inspector asks for that listing.

What do you need to bond two feeds to one bar?

You need four parts: a copper ground bar with at least five terminals, one bonding jumper from bar to wall sized for the larger feed, the two cord EGCs already sized by NEC Table 250.122, and a torque screwdriver so every lug lands at its marked value.

  • Ground bar, copper, at least five terminals: two cord EGCs, the wall jumper, the DC negative and one spare for the next circuit.
  • Bonding jumper, green/yellow copper sized for the larger feed's breaker, per NEC Table 250.122; the conductor named in the fault example below covers it with margin.
  • External-tooth star washers for every metal-to-metal joint, bar and lugs.
  • Torque screwdriver: stud hardware on panel bars typically marks 20-45 lb-in [2.3-5.1 Nm], so go by the marking on yours.
  • Two gland cutouts, ordered with the box so the glands land clear of the bar; the enclosure builder takes cutout positions with the size.
  • A brushed 304 or 316L stainless wall skips the paint-removal work, since it arrives as bare metal; the stainless enclosure line runs from 6 x 4 x 4 in to 60 x 36 x 16 in (H x W x D).

How do you land both feeds, the enclosure and DC negative on the bar?

Land them in this order: mount the bar on bare metal, bond the bar to the wall, land the motor feed's EGC, land the heater feed's EGC, then tie the 24 V DC negative to the bar as the last conductor.

  1. Lock out and tag both feeds and pull both plugs, then confirm zero volts at the cabinet end of each cord before the first lug moves.
  2. Mount the bar low on the back wall, below the terminal zone; the backplate and DIN rail layout guide covers bar placement alongside the rail layout.
  3. On painted steel, bare the metal under the bar and under every lug; on brushed stainless the wall is bare already.
  4. Fit an external-tooth star washer under the bar and under each lug.
  5. Run the green/yellow jumper from bar to wall and torque it first, since the larger feed governs its size.
  6. Land the motor feed's EGC on its own terminal, then the heater feed's EGC on the next terminal.
  7. Land each device's green/yellow lead along the bar — heater elements, drive PE terminals, the 24 V supply's PE.
  8. Tie the DC negative to the bar at exactly one point; control panels tie DC negative to the AC ground bus so every 24 V return ends at one reference.
  9. Land the two neutrals on the insulated neutral terminal beside the bar, one per terminal; the grounded conductor joins the grounding system only at the service, and a cord plug is not the service.
  10. Torque every lug to its marking and tug each conductor once.

A compact 120/24 V panel follows the same order with fewer conductors. The grounding and bonding guide shows the fault-path checks behind every step.

Does one common ground bar create a ground loop?

No loop worth chasing exists in a correctly bonded cabinet. Equipment grounding conductors carry zero current in normal operation; in the example cabinet the only current on the bar is fault current, present for the few milliseconds a breaker needs to clear.

Bonding means deliberately joining grounding parts, so parallel paths between grounded metal are the design, not a defect. Between faults the bar sits at the grounded supply's potential, within millivolts of earth. Both plugs on a machine like this usually hang from one service, whose grounded conductor and EGCs are bonded at the source, so the two feeds share one reference from the start.

Loop trouble starts with signal wiring, not power grounds. A 4-20 mA loop whose shield is grounded at both ends picks up whatever small difference exists between two grounding points. Tie shields at one end and keep analog returns off the power bar.

What does the fault path look like by the numbers?

In the worked example, a phase-to-wall fault on the heater circuit drives about 1000 A through the lone cord EGC but about 1430 A with the bar bonded. The wall's voltage during the fault falls from about 60 V to about 33 V.

The example cabinet uses 50 ft [15 m] cords: 10 AWG copper on the 30 A heater circuit and 8 AWG on the 40 A motor circuit. Those sizes carry 35 A and 50 A respectively at 75 °C. Conductor resistance at 20 °C is about 1.0 Ω per 1000 ft [3.3 Ω/km] for 10 AWG and about 0.63 Ω per 1000 ft [2.1 Ω/km] for 8 AWG. Copper resistance rises about 0.39 % per K, so at 75 °C every resistance here rises about 21 %.

Cord EGC alone. The loop is two 50 ft runs of 10 AWG: 2 × 0.050 Ω = 0.100 Ω at 20 °C, or 0.121 Ω at 75 °C. A phase-to-wall fault on a 120 V-to-ground system drives 120 V ÷ 0.121 Ω ≈ 990 A. The wall rides above remote earth by the EGC's share: 990 A × 0.0605 Ω ≈ 60 V until the breaker clears.

Bar bonded to the wall. The fault returns through two parallel paths. One is the cord's own EGC, 0.0605 Ω warm. The other runs through the wall, the wall jumper and the motor cord's EGC: 50 ft of the larger conductor is 0.0315 Ω at 20 °C, or 0.0381 Ω warm. Parallel: 0.0605 × 0.0381 ÷ 0.0986 ≈ 0.0234 Ω. The loop drops to 0.0839 Ω, the fault rises to 120 V ÷ 0.0839 Ω ≈ 1430 A, and the wall's lift falls to 1430 A × 0.0234 Ω ≈ 33 V.

Return path Loop impedance at 75 °C Fault current Wall lift during fault
Cord EGC alone 0.121 Ω ≈ 990 A ≈ 60 V
Bar, wall and second EGC in parallel 0.0839 Ω ≈ 1430 A ≈ 33 V

Both cases sit far past a thermal-magnetic breaker's magnetic pickup, typically 5-10× the 30 A handle rating, or 150-300 A. The trip is instantaneous, inside a cycle or two — one 60 Hz cycle is 16.7 ms. The arithmetic ignores source and contact impedance, so real currents land lower; the comparison is what carries. Bonding the bar and the wall cuts the wall's fault lift by about 44 percent and raises the clearing current by about 44 percent. Longer cords move the numbers fast: at 100 ft [30 m] the loop impedance doubles and the fault current halves.

Which checks prove the bonding is good?

Three measurements close the job: bar-to-wall below about 0.1 Ω, each cord EGC reading near its copper value, and near-zero volts between the bar and the neutral terminal with both feeds energized.

  • Bar to wall on a low-ohm meter: the short jumper adds about 0.0003 Ω of copper, so the reading is almost entirely the two connections. Anything higher means paint, a missing star washer or a loose stud.
  • Each cord EGC, pin to bar with the cord dead: the heater cord reads about 0.05 Ω and the motor cord about 0.03 Ω over their 50 ft runs. A much higher reading means a damaged cord or a bad crimp.
  • Bar to neutral with both feeds energized and the 10 A controls load running: a few tenths of a volt to about 1 V is normal drop, and a reading near 120 V means a neutral landed on the bar — clear the feeds and move it to the insulated terminal.
  • Re-torque every lug once after the first week of service on a machine that vibrates.

When does a second ground bar make sense?

For safety bonding, a second bar gains nothing: one bar, one bond to the wall and parallel fault paths are the whole design. A second bus earns its place only as a signal-reference point you deliberately keep away from power returns.

  • Metal cabinet, two cord feeds like the example: one bar bolted to bare wall, the wall jumper, and every green conductor plus the DC negative landed on it.
  • Non-metallic cabinet: still one bar, but the wall is out of the circuit, so every bond travels by conductor and the bar becomes a true splice point; the grounding and bonding guide covers bonding non-metallic boxes with metal raceways.
  • Analog instrumentation sharing the cabinet: add an insulated signal-reference bus tied to the bar at one point, with power returns kept on the main bar.

What goes on the order: a five-terminal copper bar, a green/yellow wall jumper sized from NEC Table 250.122, star washers and two gland cutouts placed away from the bar. The custom stainless enclosures build to your cutout layout and deliver in 10 business days, counted for custom work from your approval of the drawing.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
60 × 36 × 16 in304 stainless60 x 36 x 16 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
48 × 36 × 16 in304 stainless48 x 36 x 16 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
60 × 36 × 12 in304 stainless60 x 36 x 12 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Can one green conductor serve both feeds instead of two?

Only when both circuits share one raceway: the NEC permits a single equipment grounding conductor for multiple circuits in the same raceway, sized for the largest overcurrent device. A copper conductor with a 50 A ampacity at 75 °C covers the larger breaker here with margin. With two separate cords and plugs, each cord keeps its own green conductor, sized from its own breaker.

Does a cabinet with two supplies need its own ground rod?

No. NEC 250.4(A)(5) keeps the earth out of the effective ground-fault current path, and a rod beside an enclosure is an auxiliary electrode under NEC 250.54: it may connect to the equipment grounding conductor, but it never replaces it. In the worked cabinet, the example fault returns about 1000 A on copper for a few milliseconds; a rod under the floor carries none of that clearing current.

Should the 24 V DC negative tie to the ground bar solidly or through a resistor?

Tie it solidly at one point on the bar. A solid DC-negative-to-ground bond is the standard layout in control panels with drives, heaters and 24 V DC controls, because every load return then ends at the same reference. A resistor appears only in instrumentation schemes that call for one by design; a heater-and-motor cabinet is not one of those.

Does the cabinet door need its own bond?

Yes. Bolt a flexible grounding strap across the hinge so the door reads like the wall: under about 0.1 Ω from door to bar on a low-ohm meter. The strap also holds the door at the wall's potential when you rest a meter case or a spare lug against it, and it keeps working after the hinge gets lubricated or the door is repainted.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Start from the plant-floor PLC cabinet buildRequest a custom quote

NEMA 4X enclosures: sizes for this job

Keep reading

More on layout and installation

All articles

Buying guides

The guides behind this answer

All guides