VFD cabinet sizing for an 11 kW and a 22 kW drive

Yes: both drives, the two TRM133 controllers and the PLC fit one cabinet, and the heat budget, not the panel area, sets its size. At full load the lineup loses about 1.75 kW, while a sealed 2000 × 800 × 600 mm stainless cabinet sheds about 120 W in a 35 C room. Bolt the 10 kg drive to the mounting plate, then cool with about 975 m³/h of filtered air or a 2 kW air conditioner for washdown.

NEMA4 Enclosure engineering team · Published November 24, 2026 · 7 min read

Short answer: yes, one cabinet takes the 11 kW drive, the 22 kW drive, both TRM133 controllers, the PLC63 or PLC73 and the protection, and the heat budget sets its size, not the panel area. At full load the two drives alone turn about 1.65 kW into heat inside the box. A sealed stainless cabinet of practical size sheds only a small fraction of that at drive temperature limits. So you pick the cooling first and lay the plate out around it. Bolt the 10 kg drive to the mounting plate, keep the controllers out of its exhaust, and treat every loss figure below as a screening value: the drive manuals' loss tables replace them before you order the cooler.

The heat the lineup dumps into the box

Start with watts, not millimetres. A drive of about 95% efficiency loses 5% of rated power at full load, published VFD loss figures run from 3% to 7%, and a higher carrier frequency pushes them up. Screen at 5%, then replace it with the loss table from each drive manual at the switching frequency you will actually run. The motors' own losses heat the motor room, not your cabinet; if you need that split, calculating 3-phase motor losses covers the no-load-to-full-load method.

Part Screening loss Where the number comes from
11 kW drive 550 W 5% of rated power at full load
22 kW drive 1100 W the same screen
Two TRM133 controllers 20 W under 10 W each, example assumption
PLC63 or PLC73 10 W example assumption
24 V supply for the controllers 15 W supply losses, example assumption
Breakers and contactors 50 W per-pole losses at load current, example assumption
Total 1745 W the drives carry about 95% of it

Design at full load even when the process rarely asks for it. The loss that follows the square of current is a quarter at half load, but the fixed switching losses stay. The cabinet has to survive the day both motors demand everything.

The soft starters need one decision before layout: each motor gets either a drive or a soft starter, because a starter upstream of a VFD adds thyristor loss and disturbs the drive's input stage for no benefit. If the starters serve other motors, count their heat. With a bypass contactor they dissipate only during the ramp; without one they conduct for the whole run.

Sizing the cooling for an 11 kW and a 22 kW drive at 35 C ambient

The inputs, and where each comes from:

  • Heat load: 1745 W, from the table above.
  • Cabinet: a custom 2000 × 800 × 600 mm [79 × 31.5 × 23.6 in] stainless box, free-standing.
  • Wall coefficient: k = 3.7 W/m²K for stainless, this site's reference value.
  • Allowed air inside: 40 C (104 F), the usual ambient limit for drives and most electronics.
  • Room: 35 C (95 F) at design.

The rule in words: a sealed cabinet sheds heat equal to the wall coefficient × effective area × (allowed inside temperature − room temperature). The surface area by mounting type gives the area factors, and the sealed stainless dissipation method runs the same arithmetic.

The arithmetic:

  1. Outside area: 2 × (2.0 × 0.8 + 2.0 × 0.6 + 0.8 × 0.6) = 6.56 m²; call it 6.5 m² effective, free-standing.
  2. Rise available: 40 − 35 = 5 K.
  3. Sealed capacity: 3.7 × 6.5 × 5 = 120 W.
  4. Cooling deficit: 1745 − 120 = 1625 W.
  5. Filtered air, clean room: V ≈ 3.0 × 1625 ÷ 5 = 975 m³/h [574 cfm]. The 3.0 is 3600 s/h ÷ (1.2 kg/m³ × 1005 J/kgK), rounded.

Result: the sealed route closed at 120 W, and this lineup sits more than thirteen times past it, so the cabinet gets forced cooling. In clean indoor air, two 500 m³/h [294 cfm] fan-filter units low on the door with two exhaust filters high carry the 975 m³/h; two intakes side by side add their flows, while a fan behind a fan does not. In washdown or dirty air, keep the box closed and order an air conditioner above the deficit: 2.0 kW, the next common size over 1.65 kW.

What moves the answer: a 30 C room doubles the allowed rise to 10 K, sealed capacity becomes 3.7 × 6.5 × 10 = 240 W, the deficit falls to 1505 W, and about 450 m³/h, one 500 m³/h unit, covers it. Cabinet area helps only in proportion: even 10 m² of stainless sheds 185 W at a 5 K rise. Size fans from the curve with the filter mat fitted, because free-air ratings overstate what the mat lets through. The enclosure heat calculation guide walks the same arithmetic for a single heat source.

Filter fan or air conditioner: the room decides

Room Cooling to order Box
Clean indoor air, below 40 C fan-filter units and exhaust filters, 975 m³/h in the example washdown rating not needed
Washdown, food areas, hose water sealed-loop cabinet air conditioner, 2.0 kW in the example sealed, hose-proof
Oily or gritty air air conditioner; a fan would pull the grit through sealed
Room at or above 40 C air conditioner, because outside air is no colder than the limit sealed

A filter fan is a filtered opening: from the moment it is cut in, the box is no longer a sealed washdown enclosure, so that route belongs to clean indoor rooms. Wherever hose water can reach the cabinet, specify it rated NEMA 4X / IP66 by the manufacturer; not UL listed. Material follows the room too: 304 stainless for indoor washdown and food plants, 316L where chlorides, brine or salt air reach the box.

One more lever: if the drive family offers a through-panel mounting kit, the heatsink sits outside the door and most of the drive's loss leaves with it. The drive manual gives the internal share, and you rerun the budget on that share alone. On a washdown door the kit's gasket and the cutout must hold the assembly's rating, so the kit comes from the drive maker and we cut the door to its drawing on a custom order.

Mounting the drives and laying out the plate

The 10 kg [22 lb] drive bolts to the mounting plate with the fastener pattern its manual prints; put the tapped holes or rivet nuts on the enclosure drawing. DIN rail carries the breakers, terminals and controllers, and it is the wrong home for a drive of that mass under vibration.

Mount both drives vertically, side by side, with the top and bottom clearances their manuals print; manuals for 11 to 22 kW frames commonly call for 50 to 100 mm [2 to 4 in] of free space above and below. A drive breathes in at the bottom and exhausts at the top, so a unit stacked above another eats preheated air. When the height forces stacking, offset the two horizontally or fit a sheet-metal baffle. The single-drive enclosure sizing article works the clearances for one unit, and the six servo drives in one box case sums losses the same way.

Keep the TRM133 pair and the PLC out of the exhaust plume: low on the plate, or on the door if they are panel-mount housings, with each door cutout taken from that controller's datasheet. Faces in the door also put setpoint changes where no live plate is exposed. Breakers go at the top near the supply entry, soft starters beside the drives, and the 24 V supply beside its controllers. Once the positions are fixed, the backplate and DIN rail layout guide sets the duct and rail spacing.

Keeping the controllers quiet

Drive output cables carry steep-edged PWM voltage, and the TRM133 sensor inputs with the PLC's analog inputs pick it up when they run parallel to it. Give power and signal separate ducts and cross them at right angles. Run shielded motor cable and bond the shield 360° at the enclosure gland plate or in the drive maker's EMC clamp. Bond each drive's PE to the plate with a short, wide conductor; the enclosure grounding and bonding guide shows the path. Feed the controllers from their own 24 V branch. A reading that jumps only while a drive runs is a wiring fault: fix routing and shielding before touching any controller tuning.

What to put on the order

Item Specify
Cabinet custom 2000 × 800 × 600 mm [79 × 31.5 × 23.6 in] floor-standing, or the size your drive widths plus wiring space add up to
Material 304 stainless for this room; 316L if the air turns salty or chemical
Cooling 2.0 kW sealed air conditioner, or two 500 m³/h [294 cfm] fan-filter units with two exhaust filters in clean air
Mounting plate drilled and tapped for both drives' bolt patterns
Door cutouts for the TRM133 and PLC faces from their datasheets, gaskets seated on flat stock
Gland plate bottom entry for power, motor and control cables, with EMC clamps for the shields

Prove the build under load before commissioning: loggers at each drive's intake, beside the PLC and both controllers, and under the roof, through the worst duty the motors will see. Isolate the drives and confirm absence of voltage before reaching past the door, and respect the DC bus discharge time the manual prints. Air at the roof that climbs without leveling off means undersized cooling; a controller reading that tracks drive speed means EMC, not heat. Run your own figures through the enclosure heat calculator, and a custom cabinet built to your dimensions on this drawing is delivered in 10 business days from your approval of the drawing.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
60 × 36 × 16 in304 stainless60 x 36 x 16 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
48 × 36 × 16 in304 stainless48 x 36 x 16 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
60 × 36 × 12 in304 stainless60 x 36 x 12 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
16 × 12 × 8 in304 stainless16 x 12 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Is 5% a fair screening figure for drive losses?

Yes, for screening: a drive of about 95% efficiency turns 5% of rated power into heat at full load, so a 100 hp drive loses 5 hp, 3729 W. Published VFD loss figures run from 3% to 7%, and a higher carrier frequency pushes them upward. Before you buy the cooler, replace the screen with the loss table from each drive manual at the switching frequency you will actually run.

What if the drives rarely run at full load?

Size at full load anyway. The loss that follows the square of current falls to a quarter at half load, but the fixed switching losses stay, and the cabinet must survive the day the process demands everything. Part-load figures from the manual can trim the cooler only when the duty is fixed. Confirm the result with temperature loggers under the worst real duty before you call the cooling done.

Can I hang the 10 kg drive on DIN rail?

No. DIN rail hardware is made for breakers, terminals and controllers, not for 10 kg [22 lb] of drive under vibration. The smaller drive goes on the plate the same way unless its manual shows a rail-mount frame for that exact model.

Do the soft starters add heat, and do they need their own contactors?

They add heat, and the bypass decides how much: with a bypass contactor a soft starter dissipates only during the ramp, and without one its thyristors lose power for the whole run, so take the watts from its datasheet. Feed each motor from either a drive or a soft starter; a starter upstream of a VFD adds loss and disturbs the drive's input stage. In the example, 50 W covered the breakers, contactors and starter hardware.

Will a filter fan keep the enclosure washdown-tight?

No. A filter fan is a filtered opening, so the assembly stops being sealed the moment it is cut in; that route suits clean indoor rooms. For washdown, outdoor or oily air, keep the box closed and fit a cabinet air conditioner sized from the same deficit, 1625 W in the example, making 2.0 kW the size to order. The cooler's cutouts go on the enclosure drawing like every other hole.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Start from the plant-floor PLC cabinet buildRequest a custom quote

Check the heat load in the calculator · NEMA 4X enclosures: sizes for this job