Sealed enclosure for six AC servo drives: sizing the heat load

Budget 2-3% of each AC servo drive's rating as continuous heat: six drives totalling 7.1 kW add 142-213 W, plus about 55 W for the 24 V supply and panel PC. A sealed 24 x 36 x 8 in stainless box sheds 6.4 W per K, so the inside rides 42 K above the shop; fit a manufacturer-rated NEMA 4X / IP66 heat exchanger sized to hold the drives under 40 °C.

NEMA4 Enclosure engineering team · Published November 10, 2026 · 7 min read

Short answer: budget 2-3% of each AC servo drive's continuous rating as heat, add the 24 V DC supply and the panel PC, and size a closed-loop cooler on the total. Six axes totalling 7.1 kW put about 270 W into a sealed 24 x 36 x 8 in [610 x 915 x 200 mm] stainless cabinet, and the walls of that box shed only about 6.4 W per kelvin. The inside therefore settles 42 K above the shop, near 67 °C in a typical shop, some 27 K past the 40 °C ambient most drives carry. The fix is a manufacturer-rated NEMA 4X / IP66 air-to-air heat exchanger, or a small enclosure air conditioner. Sealed stays the right call around coolant mist and metal dust; it just has to be sealed with a real cooler instead of vents.

How much heat do six servo drives put into a cabinet?

Budget 20-30 W of heat for every kilowatt of continuous servo drive rating, the band manufacturer watt-loss tables print for AC servo drives near rated load: six axes totalling 7.1 kW therefore add 142-213 W before you count the supply or the PC.

Work the list axis by axis: two 0.75 kW axes, two 1.8 kW axes and two 1.0 kW axes come to 7.1 kW, and 7.1 kW x 3% = 213 W at the hot end, 142 W at 2%. Add the rest of the panel: a 24 V DC supply delivering 82 W loses about 15 W at an assumed 85% efficiency, and assume a small industrial PC adds 40 W until you swap in its real rating. The estimate lands at 268 W, so 300 W is the design number for the cooler.

Duty moves the drive figure by about 1% of rating either way. An axis that creeps between light cuts sits near the 2% end; hard stops that push regenerative energy back through the brake resistor run toward 3% and a little past. The same watts-in budget sizes any sealed box: sizing a sealed enclosure for a PoE switch heat load runs it for network gear.

What does a sealed 24 x 36 x 8 in box do with 270 W inside?

A sealed stainless box of that size transfers about 6.4 W per kelvin through its walls, so 270 W lifts the inside air 42 K above shop ambient, well past the 40 °C ambient most drives carry.

The arithmetic sits in three lines:

  • Wall area: 2 x (0.61 x 0.91 m) + 2 x (0.61 x 0.20 m) + 2 x (0.91 x 0.20 m) = 1.72 m² of stainless surface.
  • Wall conductance: 3.7 W/m²K x 1.72 m² = 6.4 W/K, the still-air value for a stainless wall that the sizing guides here use.
  • Rise: 270 W / 6.4 W/K = 42 K, so the cabinet rides 42 K over the shop.

Every 10 W removed buys back about 1.6 K. Conduction alone holds this cabinet inside limits only up to 96 W for a 15 K margin (6.4 W/K x 15 K), about a third of the load. The stepper-drive heat check runs the same wall-loss sum for smaller cabinets and meets the same wall a few hundred watts up.

Which rating and material does a machine-shop cabinet need?

Specify a manufacturer-rated NEMA 4X / IP66 cabinet in 304 stainless for a coolant-mist shop, stepping up to 316L where washdown uses chloride cleaners or the air is salty; both grades enter the chloride stress-corrosion band above about 60 °C [140 °F].

NEMA 250 defines Type 4X as a corrosion-resistant enclosure that stays watertight under hose-down, with a 200-hour salt-spray test stacked on the Type 4 sequence. IEC 60529 defines IP66 as dust-tight (first digit 6) and sealed against powerful jets from a 12.5 mm nozzle at 100 L/min (second digit 6). Our wall-mount cabinets carry both marks, rated NEMA 4X / IP66 by the manufacturer; they are not UL listed. In US installations NEC 110.28 treats IP codes and enclosure type ratings as separate marks, so a drawing that calls out Type 4X carries the NEMA type too. The NEMA 4X vs IP66 rating guide lays out the test differences, and drive enclosure choice: rating, size and cooling makes the same call for a single drive.

On the metal: 304 holds in most machine shops, while chloride deposits that dry onto it can pit the surface even at room temperature, so rinse the cabinet or step to 316L, whose molybdenum lifts pitting and crevice resistance. The 60 °C [140 °F] stress-corrosion threshold sits at the same place for both grades; only the pitting margin differs.

Why seal the cabinet instead of fitting a fan-filter?

Seal it: a fan-filter trades 270 W of heat for a steady intake of coolant mist and conductive metal dust, and any breather, drain or filter that is not itself rated Type 4X / IP66 pulls the whole cabinet down to that part's rating.

A sealed box keeps the shop outside; the only paths left are the walls and the exchanger's closed loop. The catch is the seams. A stainless cabinet with an unrated plastic vent is a vent with a stainless border, because the assembly rating drops to the lowest-rated part. Whether a breather vent keeps a NEMA 4X rating walks that check vent by vent, and the door gasket earns the same glance after every washdown.

How do you size the heat exchanger or air conditioner?

Size a closed-loop air-to-air heat exchanger as load divided by the temperature difference you can afford: holding 40 °C inside against a 25 °C shop gives 300 W across 15 K, so a unit rated at least 20 W per K keeps the drives inside their limit.

Manufacturers quote exchanger capacity at a stated temperature difference, so convert before comparing: at that rating the 268 W load rides about 13 K above the shop, near 38 °C inside, under the 40 °C line with margin. Shop temperature is the swing factor. At 35 °C the affordable difference collapses to 5 K, and the 300 W design load then needs 60 W/K, which is where the air conditioner takes over: pick an enclosure AC with published cooling capacity above 300 W, and a 500 W class unit leaves margin for a fouled condenser. Either way the cooler itself must carry the Type 4X / IP66 rating, or the cabinet drops to whatever the cooler holds.

The fan vs air conditioner vs heat exchanger comparison sorts the three by dust load, and the heat pipe air-to-air heat exchanger design calculations page works this W/K arithmetic in more detail.

How do you lay out the cabinet so the cooling still works?

Mount the drives with their heatsinks flat on the backplate, leave 2 in [50 mm] of clearance above each one, and keep 20-25% of the mounting panel spare so a seventh axis or a larger PC still has somewhere to go.

Heat stratifies in a sealed box, so put the 24 V supply low, the drives mid-panel, and the PC clear of the exchanger's return air. A small EC circulation fan evens the gradient so the walls and exchanger see average air; mixing moves no heat out by itself. Cut the cable entries on the drawing, sized for the glands you will fit, and latch the door evenly so the gasket seals all round. One safety line: lock out and verify absence of voltage before the first terminal.

For service with the panel energized, NEC 110.26(A) asks for clear working space in front, at least 3 ft [900 mm] deep for 0-150 V to ground in Condition 1, with room for the door to open 90°, and NEC 240.24(A) holds the highest breaker handle at or below 2.0 m [6 ft 7 in].

What do you put on the order?

Order a 36 x 24 x 8 in [915 x 610 x 200 mm] 304 stainless wall-mount cabinet with hinged gasketed door, removable mounting panel, and cutouts drawn for the glands and the heat exchanger, delivered in 10 business days from your approval of the drawing.

Two numbers carry the most weight on the quote request: the 300 W design heat load and the 15 K difference it assumes against shop ambient.

Line Spec for this six-axis cabinet
Cabinet 36 x 24 x 8 in [915 x 610 x 200 mm] wall-mount, 304 stainless, hinged gasketed door, removable mounting panel
Rating Manufacturer-rated NEMA 4X / IP66; not UL listed
Heat load 268 W estimated (213 W drives + 15 W supply + 40 W PC), 300 W design
Cooling Closed-loop air-to-air heat exchanger sized for a 15 K rise, itself rated Type 4X / IP66
AC alternative 500 W class enclosure air conditioner where the shop tops 35 °C
Cutouts Gland entries and exchanger aperture drawn before build
Spares 20-25% spare panel area
Delivery Delivered in 10 business days, counted from drawing approval

The enclosure selector turns environment, inside size and cooler type into a shortlist, and the stainless size finder filters 304 and 316L wall-mount boxes from 6 x 4 x 4 in up to 60 x 36 x 16 in [152 x 102 x 102 to 1,524 x 914 x 406 mm].

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
36 × 24 × 8 in304 stainless36 x 24 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
16 × 12 × 8 in304 stainless16 x 12 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
24 × 20 × 8 in304 stainless24 x 20 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
30 × 24 × 10 in304 stainless30 x 24 x 10 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

How many watts of heat does a servo drive add per kW of rating?

About 20-30 W per kW, the 2-3% band manufacturer watt-loss tables print for continuous operation. A light-duty axis sits near 20 W per kW; hard cycles that push regenerative energy through the brake resistor run toward 30 W per kW and a little past, so read the table for your drive and sum the axes.

Can a sealed stainless enclosure cool itself through the walls alone?

Only below roughly 96 W in a 24 x 36 x 8 in [610 x 915 x 200 mm] stainless box: the walls transfer about 6.4 W per kelvin, so a 15 K rise carries 6.4 x 15 = 96 W. A six-drive cabinet at 268 W needs a closed-loop cooler on top of the walls.

Does a heat exchanger keep the NEMA 4X / IP66 rating?

Yes, when the exchanger is itself manufacturer-rated Type 4X / IP66 and lands on its gasket as its instructions show; our cabinets are manufacturer-rated, not UL listed. A vent, drain or filter rated lower pulls the whole assembly down to that part's own figure.

Air-to-air heat exchanger or air conditioner for a 300 W cabinet?

Heat exchanger while the inside can ride about 15 K above the shop: 300 W over 15 K sets the capacity. Switch to an air conditioner when the shop reaches 35 °C, because the usable difference drops to 5 K and an exchanger would then need three times the capacity for the same load.

What inside temperature should a servo drive cabinet hold?

Hold 40 °C or less at the drives, the ambient rating most drives and industrial electronics carry unless their datasheet allows more. A correctly sized exchanger on a 268 W load rides about 13 K above the shop, so about 38 °C inside with margin.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Build it from 36 × 24 × 8 inRequest a custom quote

Check the heat load in the calculator · Outdoor enclosures: sizes for this job