A sealed enclosure sheds its heat through the walls at Q = k × A × ΔT, and the area term is where the estimate usually goes wrong: A is not the six-sided box area. IEC 60890, the technical report for estimating temperature rise in low-voltage assemblies by calculation, weights each face by what it can actually do — the bottom counts zero, the back against a wall counts zero, sides against neighbouring cabinets drop out. Get A right for the mounting you actually have and the watts follow. A 20 × 16 × 8 in stainless wall box sheds about 33 W at a 15 K rise; the same box mid-suite under a covered roof sheds 25 W. Mounting alone moves passive dissipation by about a third, so run this before you order a cooler.
The equation and the three numbers you control
The watts your box sheds equal a heat transfer coefficient k for the wall material, times the effective cooling area A, times the temperature difference ΔT between inside air and outside air. Flipped around, ΔT = Q / (k × A) predicts the rise your heat load will produce. Either direction, you need the same three numbers.
| Wall material | k, W/m²K |
|---|---|
| Stainless steel, mill finish | 3.7 |
| Painted steel | 5.5 |
| Plastic or polycarbonate | 3.5 |
These are total coefficients, convection plus radiation, for a wall in still air, led by stainless because that is what we build. Paint radiates better than bright mill-finish stainless, which is the whole reason the painted figure is higher; where the cubicle heat-rise factors 5.5 and 0.053 come from traces that value to its source.
ΔT is your permitted internal temperature minus the worst ambient at the location. Most drives and power supplies carry a 40 C ambient rating unless their datasheet says more, and 35 C inside is the long-standing panel design norm. Allow 40 C inside a 25 C room and ΔT = 15 K; the same box in a 35 C plant gets ΔT = 5 K and sheds a third of the watts. The equation is linear: halve the rise and you halve the dissipation.
For a sealed box — ours are rated NEMA 4X / IP66 by the manufacturer and not UL listed — the walls are the only heat path, so every watt the panel dissipates crosses A. Add up your component losses first, then come back here for the wall side. Once you fit a filter fan, the airflow carries the heat and the wall area matters far less.
Effective area by mounting type
IEC 60890 defines the effective cooling surface for seven installation arrangements, and the factors in each formula already discount the faces that cannot lose heat: the top carries 1.4, a covered top 0.7, the bottom counts zero, and faces buried against a wall or a neighbouring cabinet drop out of the sum. A suite means cabinets bolted side by side; a covered roof means a roof panel or drip shield fitted over the box. Work in outside dimensions, converted to metres.
| Installation case | Effective area A, m² |
|---|---|
| Single enclosure, free-standing on all sides | 1.8 × H × (W + D) + 1.4 × W × D |
| Single enclosure, wall-mounted | 1.4 × W × (H + D) + 1.8 × H × D |
| First or last in a suite, free-standing | 1.4 × D × (W + H) + 1.8 × W × H |
| First or last in a suite, wall-mounted | 1.4 × H × (W + D) + 1.4 × W × D |
| Within a suite, free-standing | 1.8 × W × H + 1.4 × W × D + H × D |
| Within a suite, wall-mounted | 1.4 × W × (H + D) + H × D |
| Within a suite, wall-mounted, covered roof | 1.4 × W × H + 0.7 × W × D + H × D |
Pick the row that matches the box as it will be built, not as drawn. A cabinet shown free-standing often ends up with a neighbour bolted on and a drip roof over it a year later; for the example box below that is 12 W of the 37 W gone.
Steps to the watts a box will shed
- Convert the outside height, width and depth of the enclosure to metres: H, W, D.
- Pick your installation row from the table above and compute A with its formula.
- Take k for the wall: 3.7 W/m²K for stainless, 5.5 for painted steel, 3.5 for plastic.
- Set ΔT = permitted internal temperature − worst-case ambient at the location, in K.
- Multiply: Q = k × A × ΔT is the heat the box sheds in still air, at steady state.
- Set that beside your panel's heat load. Under it, the sealed box holds its temperature; over it, take a bigger box — sizing a non-ventilated stainless enclosure by heat dissipation works that choice through — or move to exhaust cooling, from watts to fan airflow.
Worked example: a 20 × 16 × 8 in stainless wall box at a 15 K rise
The inputs, each with its source: outside H 20 in [508 mm], W 16 in [406 mm], D 8 in [203 mm], the H × W × D order the catalog uses; k = 3.7 W/m²K for mill-finish stainless; internal limit 40 C from the drive rating, ambient 25 C in the panel room, so ΔT = 40 − 25 = 15 K.
The rule, single enclosure wall-mounted: A = 1.4 × W × (H + D) + 1.8 × H × D.
- H + D = 0.508 + 0.203 = 0.711 m
- 1.4 × W × (H + D) = 1.4 × 0.406 × 0.711 = 0.404 m²
- 1.8 × H × D = 1.8 × 0.508 × 0.203 = 0.186 m²
- A = 0.404 + 0.186 = 0.590 m²
- Q = 3.7 W/m²K × 0.590 m² × 15 K = 32.7 W
The ceiling for this box in this spot is about 33 W. A 10 W power supply and a drive shedding 20 W sit inside it; 35 W of losses is already over. When you are over, more wall is the cheapest fix: a 24 × 20 × 10 in stainless box on the same wall computes to A = 0.89 m² and Q = 3.7 × 0.89 × 15 = 50 W. Past that you are buying cooling, not steel.
The same box through all seven cases, same k and ΔT:
| Installation case | A, m² | W at ΔT = 15 K |
|---|---|---|
| Single, free-standing | 0.672 | 37 |
| Single, wall-mounted | 0.590 | 33 |
| First or last in suite, free-standing | 0.631 | 35 |
| First or last in suite, wall-mounted | 0.549 | 30 |
| Within a suite, free-standing | 0.590 | 33 |
| Within a suite, wall-mounted | 0.507 | 28 |
| Within a suite, wall-mounted, covered roof | 0.450 | 25 |
Rows two and five land on the same area here only because this box is exactly twice as wide as it is deep; on other proportions they part company. Best to worst is 37 W to 25 W, a third of the dissipation gone from mounting alone. If a second cabinet may be bolted on later, size to the suite row now.
Reading a published dissipation table
Enclosure makers publish dissipation tables in watts at ΔT = 20 K — 45 C inside, 25 C outside — one column per installation case, all computed from these same formulas. Check the arithmetic once and you will trust the scaling: a single free-standing painted-steel floor cabinet, 1800 × 400 × 400 mm, lists 310 W in such a table. Run the row yourself: A = 1.8 × 1.8 × (0.4 + 0.4) + 1.4 × 0.4 × 0.4 = 2.82 m², and Q = 5.5 × 2.82 × 20 = 310 W. The table is the formula.
To use a row at your own conditions, divide by 20 K and multiply by your ΔT: that 310 W row is 15.5 W per kelvin, so at ΔT = 10 K — 40 C inside a 30 C room — the cabinet sheds 155 W. For stainless walls multiply again by 3.7 / 5.5 = 0.67, which lands at 104 W. Read the watts from the column that matches your mounting.
Checks when done
- Compute for the mounting as built. A recessed corner or a new neighbour cabinet turns a free-standing row into a suite row; for the example box that slip over-promises 9 W of the 37 W.
- Use the hot-day ambient, and outdoors add the sun: solar heat load on an outdoor enclosure sizes that gain, and a sun shield cuts it before you pay for cooling.
- Hold 15 to 20% spare between your losses and the box's watts. The coefficients are for still air, and a box in a corner moves less air than one on an open wall.
- Cross-check the finished panel in the enclosure heat calculator; it runs the same equation and adds the cooling capacity once the walls fall short.
- When the watts point to a bigger box, the stainless size finder filters wall-mount and HMI enclosures by outside size and grade, and how to size an electrical enclosure covers working space and fill. Custom dimensions and cutouts are delivered in 10 business days, counted from your approval of the drawing.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 10 in | 304 stainless | 24 x 20 x 10 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
How much does mounting type change enclosure heat dissipation?
For a 20 × 16 × 8 in stainless box at a 15 K rise: 37 W standing alone, 33 W on a wall, 28 W mid-suite on the wall, 25 W mid-suite under a covered roof. Pulling it off the wall buys back only about 13% more area, while a covered roof plus neighbours on both sides costs about a third. Size to the row the box will live in, not the one on the drawing.
How do I scale a dissipation table rated at 20 K to my temperature rise?
Published watts are k × A × ΔT at ΔT = 20 K, so they scale straight with your rise: divide the row by 20 and multiply by your ΔT in kelvin. A 310 W row holds 15.5 W per kelvin, which is 155 W at a 10 K rise. If the table is painted steel and your box is stainless, multiply again by 3.7 over 5.5, about 0.67.
What heat transfer coefficient should I use for a stainless enclosure?
3.7 W/m²K for mill-finish stainless in still air, against 5.5 for painted steel and 3.5 for plastic; these totals bundle convection and radiation. Paint, not the steel beneath it, is what raises the figure, because radiation carries a large share of the heat at these wall temperatures. A sun-exposed outdoor box adds solar gain as a separate load on top.
Does a bigger enclosure always shed more heat?
Yes, and the watts track face area, not volume. Double every dimension of the 20 × 16 × 8 in example and the effective area quadruples, so the box sheds about 130 W instead of 33 W at the same 15 K rise — four times, not the eight times the volume suggests. Where floor or wall space exists, more steel beats adding a cooler.





