Budget 30 to 60 W for the line reactor on a 10 hp (7.5 kW) drive. Across the size range the loss runs 0.3 to 1.1 % of drive power: near the top at 5 hp, near the bottom at 100 hp. Those watts belong in the enclosure heat balance once, beside the drive's own loss. Find the maker's published figure first. When the datasheet gives only impedance, estimate the winding loss as 3 × I² × R with copper resistance corrected to running temperature, add a quarter for the core, and let the total drive the cooling choice. The worked example below lands on one number and shows what that figure does inside a sealed stainless box.
How many watts does a line reactor lose at full load?
At rated current, a three-phase line reactor for a 10 hp (7.5 kW) drive dissipates roughly 30 to 60 W; as a share of the power passing through, that is 0.4 to 0.8 %, falling toward 0.3 % by 100 hp.
Two mechanisms make the heat. Winding loss is current squared times winding resistance, and core loss comes from the alternating flux, which stays close to constant at fixed supply voltage. Reactor makers rate their parts by percent impedance, voltage and current, and the DC resistance sits low by design, so watts rarely appear on a nameplate. Impedance moves the total: at the same amps, a 5 % reactor carries more turns of copper than a 3 % one and dissipates more.
| Drive size | Reactor current at 460 V | Loss at rated current | Share of drive power |
|---|---|---|---|
| 5 hp (3.7 kW) | 8 A | 25-40 W | 0.7-1.1 % |
| 10 hp (7.5 kW) | 14 A | 30-60 W | 0.4-0.8 % |
| 25 hp (18.5 kW) | 34 A | 70-110 W | 0.4-0.6 % |
| 50 hp (37 kW) | 65 A | 120-180 W | 0.3-0.5 % |
| 100 hp (75 kW) | 124 A | 200-300 W | 0.3-0.4 % |
The bands are typical of the watts-loss tables reactor makers publish for 460 V units at 3 to 5 % impedance. Your reactor's own row always wins over these, and a 575 V or 230 V reactor of the same horsepower runs a different current and a different row.
Where do you find the published watts loss?
Get the number from the drive manual's power-loss chapter or the reactor maker's loss table, and read the row that matches your reactor's rated current and impedance — drive makers often print one system figure that already includes the recommended reactor.
That last point decides whether you add anything at all. Some drive manuals list drive, filter and reactor losses as one system total for a recommended line-up. When yours is that style, the reactor already sits inside the number and you add zero. When the accessories are listed separately, carry the reactor's watts as its own line.
Selection software and sizing spreadsheets hold defined product lists. A missing entry is a gap in that list, not a zero-watt rating, so where the tool accepts a user-defined heat source, enter your estimated watts there and keep the line visible on the printout. For the wider hunt through datasheets and efficiency tables, the guide to finding watts-loss data when the datasheet has none lists the places that number hides. Be sure which reactor you are feeding, too: line reactor or load reactor are different parts, and a load reactor on the motor cable carries motor current.
How do you estimate the loss when nothing is published?
Estimate copper loss as 3 × I² × R at running temperature, then add a quarter for core and stray loss: a 14 A reactor with 0.06 Ω per phase at 25 °C lands at 50 W, and that figure carries through the rest of this article.
- Read the rated current I off the reactor nameplate. This example uses 14 A, the typical 460 V input current of a 10 hp drive.
- Get the DC winding resistance per phase at 25 °C from the datasheet or the maker's support group. This example assumes 0.06 Ω.
- Correct it for temperature: copper resistance climbs 0.39 % per kelvin, so R at 60 °C windings is 0.06 × (1 + 0.0039 × 35) = 0.068 Ω.
- Compute the copper loss: 3 × I² × R = 3 × 14² × 0.068 = 40 W.
- Add the 25 % core and stray allowance: 40 × 1.25 = 50 W.
The 60 °C winding and the 25 % allowance are this example's assumptions; swap in the maker's figures when you have them. The temperature step is worth taking, because Class H insulation lets a reactor run far hotter than 60 °C, and every kelvin adds 0.39 % to the resistance. Run the same reactor at 120 °C copper and the winding gives 3 × 196 × 0.082 = 48 W, a 60 W budget. Compare your result with the table above; a number far outside the band for your size usually means a misread current or resistance.
How does partial load change the reactor's heat?
Winding loss falls with the square of current, so at 7 A instead of 14 A the copper part drops from 40 W to 10 W while the core keeps its 10 W, leaving about 20 W in the budget.
The square law applies to the copper alone, because core loss follows supply voltage and your 460 V is present all day. Splitting the estimate matters most on oversized drives. A reactor sized for 34 A that lives at 10 A dissipates under a ninth of its table copper loss, while its core loss stands. For swinging loads, use the RMS current: equal time at 14 A and 7 A gives sqrt((14² + 7²) / 2) = 11.1 A, so copper is 3 × 11.1² × 0.068 = 25 W and the budget is 25 + 10 = 35 W. Put a clamp meter on the reactor leads at your real duty and feed that reading into the same formula.
How much hotter does the reactor make the enclosure?
In a 20 × 16 × 8 in [508 × 406 × 203 mm] stainless box, the reactor's share alone adds 22.5 °C of temperature rise; on top of a 210 W drive it moves the total rise from 95 °C to 117 °C, which is cooler territory.
Here is the arithmetic with every input stated. The box has 2 × (0.508 × 0.406 + 0.508 × 0.203 + 0.406 × 0.203) = 0.78 m² of surface, and hung on a wall it offers about 0.6 m² effective. A stainless wall moves 3.7 W per square metre per kelvin, so the rise is load / (3.7 × 0.6) = load / 2.22:
- Drive alone at full load, 210 W (2.8 % of 7.5 kW, read from the drive datasheet): 210 / 2.22 = 95 °C rise.
- Drive plus reactor, 260 W: 260 / 2.22 = 117 °C rise.
- The reactor's share of that, 22.5 °C.
Drives are built for 40 °C ambient unless their datasheet allows more. At 35 °C outside you have a 15 K allowance, and the bare box sheds 15 × 2.22 = 33 W. The remaining 260 W goes to a closed-loop cooler: an air conditioner or an air-to-air heat exchanger. A unit rated 300 W at 35 °C ambient covers the load with margin. Dropping the reactor to save its watts costs the drive the input protection it was bought for; what happens when you drop VFD input line reactors shows that bill. The enclosure heat calculation guide walks the method end to end, the enclosure heat calculator runs your box and your watts, and sizing a VFD enclosure from heat and clearance settles the dimensions around it.
Does it count when the reactor mounts outside the box?
Heat counts inside the sealed boundary: a reactor on the backplate of your sealed enclosure is in the budget, and one bolted to the outside wall or racked in a separate cabinet is out of it.
On washdown and outdoor sites, keep it inside a box rated NEMA 4X / IP66 by the manufacturer — not UL listed — with its watts in the balance. Every hole through that wall is another seal to maintain, and the assembly rating follows its weakest part. Indoors, on a vented Type 12 panel, an outside or separate-compartment mount genuinely removes that loss from the internal load; the heat still lands in the room, which matters only in a small equipment room. Leave about 4 in [100 mm] of clear air above and below the reactor, or the maker's printed clearance when that is larger. When the box has to grow around the reactor and its clearance, custom stainless enclosures are built to your material, dimensions and cutouts, delivered in 10 business days from your approval of the drawing.
What proves the number after the panel is built?
Run the panel at its real duty for an hour, then read the air temperature inside the box and the current on the reactor leads: 40 °C or less with the current you assumed means the budget holds.
- Interior air at drive height, at 35 °C ambient, at or below the drive's 40 °C limit.
- A clamp reading on the reactor leads within about 1 A of the I in your estimate.
- A heat-budget sheet that lists the reactor exactly once, beside any system figure that already carries it.
- An interior temperature that climbs over the months, which points to a blocked filter or a tired cooler fan rather than the reactor.
Anything beyond a clamp reading at the open door means lockout and a proved absence of voltage first. Four classic misses skew these numbers: motor nameplate amps used where reactor amps belong, 25 °C resistance used raw, total loss scaled by current squared when only copper follows the square, and a blank in a sizing tool read as 0 W. A hot casing tells you the reactor works and nothing about its watts; that number comes from the estimate or the maker's row.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 30 × 24 × 10 in | 304 stainless | 30 x 24 x 10 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can you read the watts loss straight off the % impedance?
No. Impedance fixes the voltage drop at rated current and says nothing about copper or core loss; at the same 14 A, a 5 % reactor dissipates more than a 3 % one. Estimate it instead: 3 × 14² × 0.068 Ω = 40 W of copper loss, plus a quarter for the core, which is the same 50 W budget this article works with.
How much less heat does the reactor make at half load?
The copper part falls with the square of current: 40 W at 14 A becomes 10 W at 7 A. Core loss tracks supply voltage, so its 10 W stays, and the budget lands near 20 W. Clamp the real line current at your duty and feed that number into the same formula.
Can a bigger enclosure absorb the reactor heat without a cooler?
Only a much bigger one. At a 15 K allowed rise, a stainless wall at 3.7 W/m²K sheds 55.5 W per square metre, so the 260 W example needs about 4.7 m² of wall, near a 55 × 40 × 20 in cabinet. For a 10 hp drive with its reactor, a closed-loop cooler rated for the 260 W is the smaller build.
Where should the reactor go in a washdown enclosure?
Inside the sealed box, on the backplate with about 4 in [100 mm] of clear air above and below it, and with its watts in the heat budget. Keep the door gasket and wall penetrations tight: our enclosures are rated NEMA 4X / IP66 by the manufacturer, not UL listed, and the assembly rating follows its weakest part.





