Short answer: the strike came in on the field pairs, and the clamp at the card had no low-impedance ground behind it. Rebuild every loop in this order: cable entry, then a loop surge protector with its ground lead under 300 mm [12 in] to the cabinet ground bar, then the isolator, then the analog input card. Keep the pair shield bonded at the cabinet end and prove it open at the well. An isolator mounted first takes the hit in place of the card: its isolation figure, typically a 500 V RMS dielectric test on 4-20 mA modules, is a steady-state spec that diverts no current. A storm that kills a few channels on each of three AI cards is the classic signature of this fault, and here is the trace, the fix and what keeps it fixed.
What the damage pattern tells you
Map each dead channel to its well and its cable route before you change anything. The pattern names the entry path:
- A few channels dead on each card, the rest reading normally. The surge entered on those specific field pairs and outran the clamp at the card terminals.
- Every channel on one card dead, with a damaged power supply. The surge rode in on the panel feed. That fix lives at the supply side, and it looks like surge protection for a 240 V machine panel.
- Dead channels share one cable route or one well. That route's cable or that well's ground is the entry point.
- Dead channels share no route at all. The weak link is bonding inside the cabinet, not the field.
- Transmitters dead at some wells too. The field-side suppressor clamped to a well ground that rose with the strike.
Check the five entry paths in this order
These causes run from most to least likely, and each check takes minutes with the panel de-energized.
- A clamp with no ground behind it. A suppressor element pushed onto a plain two-wire terminal block clamps to whatever ground that block offers — often none, so the surge walks through to the card. Measure continuity from the suppressor's ground terminal to the cabinet ground bar; you want near zero ohms.
- A ground lead that is too long. Measure every lead. Anything past about 300 mm [12 in] adds inductance, and the arithmetic below shows what that costs you.
- Both ends of the shield grounded. A ground-potential difference between well and plant drives strike current along the shield and into your cabinet bond. Lift the well-end shield and measure drain to well ground; any reading other than open is a second bond.
- A field suppressor riding a rising well ground. At wells that lost transmitters, confirm the suppressor ground, the transmitter case and the well casing join at one point through a short conductor.
- Split references in the cabinet. Clamp grounds on one bar, shield drains on another, the door bond loose — the surge gets a free path between them. Land everything on one ground bar before you call it grounded.
Why the isolator goes after the surge protector
The instinct to hang a 2-channel 4-20 mA isolator at the cabinet entry is half right: it belongs on that rail, one position later. Galvanic isolation on loop modules is typically specified as a 500 V RMS dielectric test, 2.5 kV on some units, and that is a steady-state insulation figure. Even reinforced insulation grades in component standards are proven with a 10 kV impulse, while a strike a kilometre from the route can still induce kilovolt-level common-mode on a long pair. The isolator has no path that diverts amps, so it converts the strike into a failed channel instead of a non-event.
The surge protector is built to take that current. IEC 61643-21 grades SPDs for signalling circuits by impulse discharge current and protection level, so you can compare them on paper. Pick one whose protection level sits below the card channel's rated input maximum; datasheet figures for 24 V loops typically land between 30 and 60 V. For scale, the common industrial test levels of IEC 61000-4-5 on signal ports are 1 kV line-to-line and 2 kV line-to-earth. Everything above that margin is yours to clamp.
| Position | Device | What it does with a strike |
|---|---|---|
| 1 | Cable entry and shield bond | The pair enters; the shield lands here, one end only |
| 2 | Loop SPD | Diverts the amps, clamps to its protection level |
| 3 | Isolator | Breaks ground loops, passes 4-20 mA |
| 4 | Analog input card | Reads the signal, never the strike |
The ground lead sets the clamp voltage
A suppressor clamps its conductors to its ground terminal, and that terminal rides on the lead you gave it. A straight round conductor carries about 1 µH of inductance per metre — a standard handbook figure. The 8/20 µs current wave used in SPD testing reaches crest in 8 µs, so a 10 kA event climbs at 10,000 A / 8 µs = 1.25 kA per microsecond. The lead's share of the clamp voltage is V = L × di/dt:
- 300 mm [12 in] lead: 0.3 µH × 1.25 kA/µs ≈ 375 V
- 1,000 mm [39 in] lead: 1.0 µH × 1.25 kA/µs ≈ 1,250 V
That voltage adds to the clamp level and lands straight across your analog input. Keep the lead under 300 mm [12 in], straight, one piece, on the same ground bar as the card reference and the shield drains. The same physics sets lightning arrester ground lead length on power cabinets.
The bar has to conduct, too. NEC 250.12 requires paint, lacquer and enamel removed from threads and contact surfaces at grounding and bonding connections. NEC 250.96(A) requires metal parts serving as grounding conductors — raceways, equipment, enclosures — bonded so they carry the fault current imposed on them. The wiring side of this is the enclosure grounding and bonding guide.
The shield: one end, and prove it
Single-ended grounding — bonded in the cabinet, isolated at the well — is the right scheme. It keeps noise and strike current out of the shield, and it holds only while the field end stays truly isolated. Walk the wells and do three things:
- Lift the shield from the transmitter and from any terminal that bonds to the well ground.
- Measure drain to well ground with those leads off. Open means the scheme is intact; any resistance means a hidden second bond.
- Tape the end back so it cannot touch metal, then re-terminate.
Wells that take repeated strikes get one refinement: a floating shield end can still flash over mid-strike. Land it through a gas discharge tube to local ground, sized with a DC spark-over above the loop's working voltage — about 90 V for a 24 V loop. That turns an uncontrolled arc into a chosen one. The cabinet-side details are in cable shield termination at the enclosure entry, and the one-end logic in thermocouple and RTD shield grounding.
The fix, in order
- Lock out the feed and test for absence of voltage, then swap the dead cards. Record which channel maps to which well while the labels are open.
- Mount one loop SPD per field pair on the DIN rail at the cable entry. Ground lead under 300 mm [12 in], straight, to the ground bar.
- Mount the 2-channel 4-20 mA isolators after the SPD and ahead of the card terminals — where they clean up ground loops without ever meeting the strike.
- Land every shield drain on that same bar at the entry, tape back the well ends, and fit the gas discharge tubes at the repeat-strike wells.
- Prove the loop budget before power-up, on a 24 V loop with a 250 Ω input resistor. At 20 mA the burden drops 5.0 V, and every 50 Ω of SPD series resistance adds 1.0 V more. That leaves 24 − 5.0 − 1.0 = 18.0 V for the transmitter, comfortably above the 12 V minimum many two-wire transmitters specify. Read both numbers off your datasheets; when the leftover shrinks below the minimum, pick a lower-resistance SPD or raise the loop supply.
Prove it before the next storm
- Inject 4, 12 and 20 mA at the transmitter terminals with the field end disconnected, and compare the cabinet reading at each point, channel by channel. Agreement within about 1 % of span says the SPD adds no leakage and the isolator no offset.
- Re-measure shield to well ground at every well with the transmitter leads lifted; open is the pass.
- Log the ground bar bond with a ground tester as your baseline. Single rods commonly read 25 Ω or more to earth, while a plant instrumentation grid targets 5 Ω or less — that is the number worth defending.
When an installed SPD starts dying storm after storm instead, the device is reporting on its ground; that diagnosis is its own article in a 4-20 mA surge protector that keeps failing.
When to re-specify the enclosure
The ground you just rebuilt lives inside a box at every well, and a box that floods or corrodes eats that bond within a season. Give the field-side electronics stainless: 304 inland, 316L where brine, salt spray or washdown reach it. Our boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed, and NEMA does not test or endorse enclosures. The small stainless junction boxes hold the well-head terminals and field suppressors; the larger outdoor stainless enclosures hold the cabinet-side SPDs and isolators, with the sun as the heat load to design around. Sealed entries keep the water out — the method is in field-drilled conduit entries that keep a NEMA 4X rating and the layout in the cutouts and glands guide. Any of them is delivered in 10 business days from your order, and a custom size from your approval of the drawing.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Does a 4-20 mA isolator protect the analog card from lightning?
It protects the card only when a surge protector sits ahead of it. The isolator's galvanic isolation — typically a 500 V RMS dielectric test, 2.5 kV on some modules — is a steady-state figure, and it diverts no strike current. Order the loop cable, SPD, isolator, card, and the isolator sees only the clamped residue, a few tens of volts.
How long can the surge protector's ground lead be?
Keep it under 300 mm [12 in], straight, one piece, to the cabinet ground bar. A straight conductor carries about 1 µH per metre, so a 10 kA 8/20 µs strike adds roughly 375 V on a 300 mm lead and about 1,250 V on a full metre. Run it in a single sweep; a coil or a sharp loop multiplies the inductance and the voltage with it.
Should the cable shield also be grounded at the well?
Ground it at the cabinet end only and prove the well end reads open to well ground with the transmitter leads lifted. Where a well takes repeated strikes, land the field end through a gas discharge tube to local ground instead of leaving it floating: pick a DC spark-over above the loop's working voltage, about 90 V for a 24 V loop.
How do I prove the fix before the next storm?
Inject 4, 12 and 20 mA at the transmitter terminals with the field end disconnected, and compare the cabinet reading at each point for every channel; agreement within about 1 % of span says the SPD adds no leakage. Then log shield-to-ground continuity as open at each well and record the ground-bar bond resistance as the baseline for next season.