Run every arrester ground lead in bare copper of at least #4 AWG [21 mm²], keep the run short and straight, and land its lower end on a bar bonded to the transformer tank. At an assumed 10 kA discharge, each metre of #4 adds about 8 V on top of the arrester's discharge voltage. Swap in your own design current; the volts scale line for line. A lead that ends on its own unbonded rod adds an earth term you cannot read off the wire, and that is the voltage your tank insulation feels. The feeder usually stays in when an arrester conducts, because the surge lasts microseconds; a sustained trip means an arrester failed shorted or the line flashed over somewhere else. When a transformer dies with every isolator intact, look at the ground path before you blame the arresters.
What each sign after a storm points to
One of six signs meets you after a storm on an overhead-fed transformer. Read the list against what you actually see, because each sign names its own next step.
- Isolator blown, ground lead hanging from one phase — the arrester conducted energy above its capability and failed. Replace that assembly, inspect the other two phases, then run the ground-path checks in the sections below.
- Housing cracked, burned or tracked — a damaged arrester whatever the isolator shows. Replace it.
- Line tripped and stayed tripped — a sustained phase-to-ground current: an arrester failed shorted, or the strike flashed over elsewhere on the line. Patrol the line, then leakage-test all three arresters.
- Isolator intact, lead attached, no trip — no hit, a hit the arrester shrugged off, or the uncommon failure that never blows the isolator. A leakage test before the next season settles it.
- Transformer damaged and every isolator intact — the ground path is the suspect: lead drop, separate unbonded electrodes, a corroded joint. Start at the bar and the rod connection.
- Green or black on the bare lead, paint under a lug — a high-resistance joint that carries full discharge current. Clean to bare metal and re-torque.
Modern MOV arresters fail rarely, and they almost always blow their isolator when they fail, so the quiet failure is uncommon. That is why a dead transformer with intact isolators points at the grounding before it points at the arresters.
Why the feeder usually stays in
An arrester neither absorbs nor stops a surge. It diverts the current to ground and clamps the voltage for the equipment connected in parallel with it. Inside is a voltage-sensitive variable resistance: at normal line voltage the resistance is high and only leakage current flows. EPRI's monitoring guidance for line arresters puts a typical arrester's capacitive current at 1-5 mA at its maximum continuous operating voltage. Above the protective level the resistance collapses, the surge passes to ground, and when the voltage recovers the high resistance returns.
The relay therefore sees a pulse lasting microseconds, not a power-frequency fault. A phase-to-ground trip needs something that sustains the current: an arrester failed shorted, a flashover elsewhere on the line, or an instantaneous element that picked up on the surge itself. Pull the relay event record before anyone climbs, because it separates the three cases in minutes.
| Relay event record shows | What it means | Next step |
|---|---|---|
| Impulse pickup, no sustained current | The arrester did its job | Read the isolators and restore the feeder |
| Sustained ground current until the trip | Failed-short arrester or line flashover | Patrol the line, then leakage-test all three |
| Trip with no fault current behind it | Relay picked up on the surge alone | Inspect isolators, then review the pickup settings |
Sizing and routing the ground lead
Size the lead for the discharge it must carry. Field practice on overhead transformer installs runs bare copper of at least #4 AWG [21 mm²]. Moving up to #2 AWG cuts the lead resistance roughly a third below #4 and trims every voltage in the worked example by the same share. Skip the jacket: a discharge measured in microseconds gains nothing from insulation, and bare metal shows you corrosion and burned clamps between storms.
Route each lead short and straight from the arrester base to the bar. Every extra metre costs about 8 V at a 10 kA discharge, and a coil in the run adds inductance to a path that wants none. For a three-phase bank, tie the three leads to one common bar and run a single conductor down to the electrode, the arrangement long used on pole installs.
Bond that bar to the transformer tank and to the cabinet that carries it. NEC 250.96(A) requires metal parts serving as grounding conductors, enclosures included, to be bonded so they carry the fault current imposed on them. NEC 250.12 requires paint, lacquer and enamel removed from threads and contact surfaces at grounding connections, unless the fitting is designed to bite through them. The ground bus inside the cabinet bonds to the enclosure with its supplied screw, the same detail as any subpanel, and the enclosure grounding and bonding guide carries the full picture.
One electrode system, not two separate rods
During a discharge, your transformer insulation sees three voltages in series. The first is the arrester's discharge voltage. The second is the drop along the ground lead, and the third is the potential difference between the arrester's electrode and the tank electrode. The worked example below pins down the second term. Bonding removes the third: one electrode system, one bar, one down-conductor, so the arrester ground and the tank ground are the same point. Two rods driven at separate spots, each fed by its own lead with no bond between them, put the soil between those spots in series with the surge current. That earth term reaches kilovolts at real stroke currents, and no conductor sizing removes it.
The code reaches the same place from the other side. NEC 250.4(A)(5) treats the earth alone as ineffective as a fault-current path. NEC 250.54 allows the rod at a pole-mounted installation only as an auxiliary electrode. Connect it to the grounding conductor; it never stands as the system itself. Bond the cabinet into that same path, as in bonding a disconnect enclosure to the building ground ring, and when a transformer insulation fails, the missing bond is often where the fault current went looking for a way home — how a transformer insulation failure traces back to bonding walks that chain.
Lead drop on a 3 m #4 AWG lead at a 10 kA discharge
This is the arithmetic behind short and direct. Swap the two assumptions for your own numbers and the method holds.
Inputs, each with its source:
- Conductor: #4 AWG bare copper, 21 mm² — the lead size from field practice above.
- Run: 3 m [10 ft] from arrester base to the tank-ground bar — assumed; measure your own run.
- Copper resistance: 0.82 mΩ per metre at 20 °C for #4 AWG — handbook value.
- Discharge current: 10 kA — assumed; use your design discharge current, and the result scales line for line.
The rule in words: lead drop equals discharge current times lead resistance, and lead resistance equals per-metre resistance times run length.
Arithmetic:
- R = 0.82 mΩ/m × 3 m = 2.45 mΩ
- V = 10,000 A × 2.45 mΩ = 24.5 V, call it 25 V
- At 40 °C the same lead runs 7.8 % higher, from copper's +0.39 % per K: 2.45 mΩ × 1.078 = 2.64 mΩ, and the drop rises to 26.4 V
The result: about 8.2 V per metre of #4 at 10 kA, so this 3 m run adds 25 V to what the insulation sees. Run #2 AWG instead and the per-metre figure falls to about 5 V.
The decision: keep the bar at the tank and each arrester lead at 2 m [6.5 ft] or less, which holds the lead term under 17 V at 10 kA. Every extra metre costs about 8 V more. A 10 m run out to a distant rod starts at about 82 V before the earth term, so length, not gauge, is the number you control first.
Testing the arrester after a strike
De-energize and verify absence of voltage before you touch a lead, clamp or isolator.
Read the isolator on each phase first. A blown isolator with the lead hanging means the arrester failed conducting energy above its capability: replace the assembly, inspect the other two phases, and test them before the next storm. A housing that is cracked, burned or tracked gets replaced whatever the isolator shows. An intact isolator is not proof of health, because a small share of failures never blow it, so the leakage test makes the call.
The leakage test applies the nameplate MCOV and records the current drawn. Healthy territory for a typical arrester is the 1-5 mA band from the EPRI guidance above, and the decision comes from comparing against your own baseline and the two sibling phases. Run it as a bench check:
- De-energize, then disconnect the arrester from line and ground.
- Apply the nameplate MCOV and record the current drawn.
- Compare against the commissioning baseline, the sibling phases, and the 1-5 mA band.
- Treat an outlier or a rising trend across seasons as a failing unit.
Testers of this kind live in shops more than trucks, so record a baseline for every new arrester at commissioning and the later readings have a reference. A surge below the arrester's energy capability does not consume the unit, which is why a healthy reading returns it to service. For what degradation looks like on paper, an insulation-resistance analysis of a 220 kV arrester stack shows the failure inside the housing.
| Reading | Decision |
|---|---|
| Isolator operated | Replace the arrester |
| Housing cracked, burned or tracked | Replace |
| Isolator intact, leakage inside 1-5 mA and near the baseline | Reuse |
| Isolator intact, leakage high or an outlier among the three | Replace |
| Isolator intact, untested after a known hit | Test before reuse; replace when no tester is available |
Reworking the path and keeping it honest
Rework the path, not only the parts. Replace every failed arrester, run the leads bare at #4 AWG or larger, and bring each one short and straight to a common bar at the tank, bonded down to the one electrode the tank shares. Clean every lug face to bare metal, torque the hardware, then pull a low-resistance reading from arrester terminal to tank ground. Three metres of #4 reads 2-3 mΩ, so a measurement ten times that points at a joint rather than at the wire.
Keep the installation honest with a log. Photograph each isolator, record each leakage figure at commissioning, walk the leads every year before storm season, and reopen the record after every reported strike. Corrosion at a clamp is the failure that grows quietly between storms, and it is the one a five-minute look catches.
When to re-specify the cabinet
The ground bar usually lives in the cabinet beside the transformer, and the cabinet either protects that path or becomes it. Spec a gasketed stainless box with a bonded ground bar, entries through rated glands, and the mounting panel landed on the bar. Our wall-mount outdoor boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed. Pick the grade by location: 304 inland, 316L wherever salt spray reaches, because chloride deposits pit 304 even at room temperature and both grades cross into stress-corrosion cracking near 60 °C [140 °F]. Orders are delivered in 10 business days, counted from your order or, for custom work, from your approval of the drawing. The outdoor pedestal enclosure article covers a transformer on its own stand, the stainless junction boxes cover the small splice-and-bar cases, and our outdoor stainless enclosures are the starting point for the cabinet itself.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Is bare wire acceptable for a lightning arrester ground lead?
Yes, and it is the better inspection tool. Field practice runs #4 AWG bare copper [21 mm²] as the working minimum, and #2 AWG cuts the resistance about a third below that. Bare metal shows you green corrosion and burned clamps at a glance; insulation hides both between storms. Spend the effort on a short, straight run and a bonded lower end instead of a jacket.
How many volts does a long arrester ground lead add during a strike?
At an assumed 10 kA discharge, #4 AWG bare copper adds about 8.2 V per metre. A 3 m run costs roughly 25 V and a 10 m run about 82 V, on top of the discharge voltage your insulation already sees. A strike at ten times that current multiplies every figure by ten, which is why run length is the number you control.
The transformer instructions ask for one insulated lead per arrester to its own rod. What now?
Follow the written instruction while you resolve it, and ask the manufacturer in writing whether its rods are bonded to the tank ground. Insulation changes little for a discharge path; electrode topology changes a lot. NEC 250.54 treats the pole-mounted rod as an auxiliary electrode that connects to the grounding conductor and never stands alone, the same one-electrode rule this article applies.