Single compression vs double compression gland for enclosure entry

Order a single compression gland for unarmoured cable: one elastomer seal compresses on the jacket and, with the maker's gasket and locknut, holds IP66 / NEMA 4X. Specify double compression only for armoured or screened cable, where the second compression clamps the armour. Neither term means stuffing gland: that packing seal runs on a moving shaft, not a cable.

NEMA4 Enclosure engineering team · Published November 24, 2026 · 8 min read

Order a single compression gland for every unarmoured cable: one elastomer seal compresses onto the jacket and carries the sealing and the grip together. Order a double compression gland when the cable is armoured or screened: the second compression clamps the armour or the screen, and that clamp is what keeps the entry at the box's rating. Neither term is another name for a stuffing gland. A stuffing gland packs a seal around a moving shaft - a valve stem or a propeller shaft - and belongs to valve and marine work, not to a cable entry schedule.

Our stainless boxes are rated NEMA 4X / IP66 by the manufacturer; they are not UL listed. Every gland that enters one needs the same claim on its own datasheet, mounted with its gasket and locknut. Below are the anatomy, the tests behind the rating, and six cables worked into one washdown box.

What each compression actually compresses

Single compression names the gland's action, not a loose way of packing. The gland is a body, an elastomer seal insert and a clamping cap. Tightening the cap compresses that one seal onto the cable's outer jacket. The seal does two jobs at once: it closes the entry against water and dust, and it grips the jacket so the cable's pull lands on the gland instead of on the terminals. Its territory is unarmoured round cable: tray cable, jacketed control cable, flexible cord and sensor cable.

Double compression exists for cable that carries metal under the jacket. The inner seal compresses the inner sheath and closes the entry. The outer compression squeezes the armour wires, or the screen braid, between a cone and the gland body. That clamp takes the mechanical load off the sheath, and with the maker's earth tag it bonds the armour into the panel's grounding path. NEC 250.96(A) requires metal parts serving as equipment grounding conductors - raceways, cable armour and enclosures among them - to be bonded so they can safely conduct the fault current likely to be imposed on them. The earth tag is where the armour joins that path.

The single seal does its work only where it bears on the cable's outer sheath - why a gland seal must contact the cable outer sheath - so the clamping range has to match the jacket, not an intermediate layer. Armoured cable brings rating questions of its own; armoured cable glands and the rating they leave you works through them combination by combination.

Single compression Double compression
Cable it takes Unarmoured, round jacket Armoured (SWA) or screened
Sealing points One, on the outer jacket Two: inner sheath, then armour or screen
Mechanical grip Jacket only Sheath plus armour wires or braid
Bonding Through the enclosure's grounding only Armour bonded through the gland's earth tag
Datasheet claim it can back IP66 / NEMA 4X with gasket and locknut IP66 / NEMA 4X with the armour clamped and sealed

What the tests cover, and what they miss

IEC 60529 puts the digits to work. First digit 6 means dust-tight: no dust ingress. Second digit 6 means powerful jets: a 12.5 mm nozzle throws 100 L/min at the enclosure from 2.5 to 3 m, from every practical direction, for at least 3 minutes. IP66 is not an immersion rating; temporary immersion is IPX7, 1 m of water for 30 minutes.

NEMA 250 Type 4X keeps the watertight, hose-down duty of Type 4 and adds corrosion. Under NEMA 250's Table 5-1D, a Type 4X enclosure takes another 200 hours of salt spray beside an AISI 304 stainless specimen and is compared against it. That test is the X, and it is why washdown and coastal specifications ask for 4X rather than 4.

Gland makers document the rating the same way, as an installed assembly. One tray cable gland brochure puts IP66 and NEMA 4X on its standard gland when it is mounted with the gasket and the locknut. The gasket seals body to wall, the locknut holds the compression, and the gland's clamping range has to match the cable before the hole is cut.

The box keeps its rating only while every entry keeps it: the weakest part sets the assembly. What a panel keeps after you cut it and mount devices walks that logic entry by entry. In US installations, NEC 110.28 says IP ratings do not replace enclosure type ratings, so a specification that asks for Type 4X wants the type number on the line item; NEMA 4 vs 4X vs IP66 untangles the pairs.

Beyond jets, one boundary is hard. Immersion is Type 6P / IP68 territory, and it starts with a custom design review that names the depth, the duration and the fluid. Locations classified for combustible gas or dust need enclosures carrying that specific location approval; we do not build them.

A stuffing gland seals a moving shaft

A stuffing gland - the stuffing box of valve and marine work - grips a stem that moves. On a rising-stem control valve, packing compressed by a gland lets the stem rise and fall while it retains the process fluid. On a boat, packing around the propeller shaft lets the shaft spin while it limits the seawater that follows it into the hull; that class of seal is meant to weep a controlled drip while it runs.

A cable entry is the opposite problem. The cable never moves after commissioning, and the gland has to seal it dead. Both parts are called glands because the word crossed disciplines long ago: electrical entries, compression fittings on tube, valve packing hardware and marine shaft seals all carry it, and the usage shifts with region - British practice says gland for cable entries far more often than US practice does. A valve handbook will even write screwed gland for the hardware that holds the packing follower on a rising stem.

So let the words do the sorting on the order. Cable gland plus the cable type, the jacket diameter and the rating claim quotes an electrical entry every time. Stuffing gland, asked alone, quotes packing hardware for a stem. If the job truly is a valve stem or a propeller shaft, order it from the valve or marine side and keep it off the cable entry schedule.

Six cables into a washdown box: the worked example

The case: one stainless wall-mount junction box from the stainless junction box range, serving a washdown conveyor control station. Six cables enter from below through a bottom gland plate; stainless enclosures with a gland plate explains why one replaceable plate beats six wall cutouts. The cable set is an example - read your cable schedule before ordering: four 12 AWG tray cables with a 10.5 mm jacket, and two 4-core 10 AWG SWA cables with a 15.0 mm inner sheath and 18.5 mm over the armour.

The rule in words: every entry must carry the box's rating, and each cable sets the number of sealing points it needs. An unarmoured jacket needs one seal. An armoured cable needs two - inner sheath first, armour second - and each sealing point must come from a gland whose datasheet claims IP66 / NEMA 4X with its gasket and locknut fitted.

The arithmetic, on the example cable counts:

  • Sealing points needed: (4 x 1) + (2 x 2) = 8 sealing points across 6 glands.
  • Sealing points delivered if the order says single compression for all six, or says only the word stuffing: (4 x 1) + (2 x 1) = 6.
  • Shortfall: 8 - 6 = 2, and both missing points are the armour clamps. The two SWA entries then carry no datasheet rating and no bonding on the armour, and the weakest entry sets the whole assembly.

What the shortfall costs in the wash: the digit 6 test is 100 L/min from a 12.5 mm nozzle for at least 3 minutes, from every direction. An entry with loose, unbonded armour behind a single jacket seal is the entry with nothing documented to say it survives that. Unclamped armour also lets the cable's pull work the seal loose over time.

The result, and the order it produces: four single compression glands whose datasheet clamping range covers a 10.5 mm jacket - a 9 to 12 mm range leaves 1.5 mm of margin at each end, those ranges being example figures until you read the datasheet - and two double compression glands listed for a 15.0 mm inner sheath and 18.5 mm over armour. Example datasheet ranges there: 13 to 17 mm on the seal and 17 to 21 mm on the armour, clearing both cable numbers by 2.0 mm and 1.5 mm. Each armoured entry takes its earth tag.

The threshold that decides the purchase is simple: an entry whose gland datasheet does not claim IP66 / NEMA 4X for that cable is a rejected entry, and one such entry out of six is enough to drop the whole box below its rating.

What goes on the order

Two lines quote the worked example without a phone call:

Match the body material to the wash the way you match the box: 316 stainless where the wash carries chlorides - the NEMA 4X wall-mount range comes in 304 and 316L - and nickel-plated brass for a mild indoor wash. Screened cable takes the double compression variant that clamps the screen over 360 degrees; the datasheet names the screen diameters the clamp accepts.

Order the holes with the box through the custom stainless cutouts builder, each hole sized to the gland datasheet, and the assembly is delivered in 10 business days - counted from the order, or from your approval of the drawing when the plate is drawn custom. Keep one cable per gland; two cables through one gland covers the narrow exceptions.

The decisions, by case:

  • Unarmoured round cable: single compression, datasheet IP66 / NEMA 4X, gasket and locknut fitted.
  • SWA or any other armoured cable: double compression with an earth tag.
  • Screened cable: double compression with a screen clamp sized to the screen.
  • A moving stem or shaft: a stuffing box, ordered from the valve or marine side, and off the cable schedule.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
12 × 10 × 6 in304 stainless12 x 10 x 6 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
16 × 14 × 8 in304 stainless16 x 14 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
20 × 16 × 8 in304 stainless20 x 16 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Is a single compression gland the same as a stuffing gland?

No. A single compression gland grips a stationary cable: one elastomer seal compresses onto the jacket and holds IP66 / NEMA 4X on unarmoured cable when the datasheet and gasket back it. A stuffing gland packs sealing rings around a moving shaft, such as a valve stem or a propeller shaft, and is built to let a controlled drip past the motion. Write cable gland, the jacket diameter and the rating into the order instead.

Is a compression gland the same as a compression fitting on tube?

No, though suppliers hear both. A compression fitting bites a ferrule into a metal tube to seal a fluid line; a compression cable gland compresses an elastomer seal onto a cable jacket to hold out water and dust. On a panel order, write cable gland plus the jacket diameter and the IP66 / NEMA 4X claim, and the quote comes back for the electrical entry.

Does a double compression gland also clamp a cable screen?

Only the variant built for it. On screened cable the second compression must clamp the braid or wires over 360 degrees, the way it clamps wire armour on an SWA gland; a plain armour gland leaves the screen unclamped and the screen termination floats. The datasheet names the screen diameters the clamp takes, so match the screen to that range the way you match the inner sheath to the seal.

What does the assembly rate if one of six glands is only IP54?

IP54. The weakest entry sets the rating for the whole enclosure, so the box delivers dust-protected splashing resistance - first digit 5, second digit 4 - no matter what the stainless body is rated. Swap the single off-spec gland before the box goes on the wall; at 100 L/min of wash water, one IP54 entry is where the water goes in.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Build it from 12 × 10 × 6 inRequest a custom quote

NEMA 4X enclosures: sizes for this job