Short answer: fit a dedicated three-stage load cell/RTD surge protector on the field cable, one that protects all six conductors plus the shield, and mount it in a metal junction enclosure where the outdoor run enters the protected area. A bridge-input module reads millivolts and survives only tens of volts at its terminals, so nothing on the rack itself rides out a strike. The 4-20 mA loop protector from the old transmitter path guards two conductors, not six, and it has no role in the new run. The worked example assumes a rack-mounted bridge-input module whose datasheet lists a ±15 V survivable input and a 250 V operating common-mode limit; substitute the figures printed on the module you fit.
Why doesn't the module input survive a strike on its own?
It cannot: the example module's datasheet allows a ±15 V survivable input and 250 V of operating common-mode, while air breaks down at about 30 kV per centimetre, so one 10 mm spark across a terminal strip puts roughly 30,000 V on an input built for 15. The measuring span is smaller still. The bridge delivers its standard 2 mV/V of rated output, so 10 V of excitation gives a 20 mV full-scale signal. Those figures describe what the front end tolerates while measuring; they are not energy it can absorb.
A strike on or near the conveyor structure drives kiloamperes through the cable loop and lifts one end of the run against the other. Protection therefore lives on the wiring, ahead of the module, and its job is to hold every conductor near one potential while the event passes.
What do the six conductors carry?
Six conductors in three pairs plus a shield: an excitation pair powering the bridge at 10 V DC in the example, a signal pair carrying the 20 mV output, and a sense pair that lets the module measure excitation at the cell and correct for voltage drop in the cable. The sense pair earns its keep on long runs, and the arithmetic is easy to run. A 100 m route in 20 AWG copper adds about 0.033 Ω per metre per conductor, so the round trip is 6.7 Ω.
The bridge draws 10 V / 350 Ω = 28.6 mA, so the excitation drop is 28.6 mA × 6.7 Ω ≈ 0.19 V, about 2% of the supply. That is the error remote sense exists to cancel, which makes sense continuity part of the protection spec: a protector that opens or heavily loads the sense loop reinstates the drop the wiring was laid to remove. The shield is the seventh conductor, and it takes a controlled path through the protector rather than a floating end.
Why can't the old 4-20 mA loop protector stay in the circuit?
It covers the wrong circuit: a 4-20 mA protector guards two loop conductors powered from a 24 V supply, while this path needs six conductors clamped low and a sense loop left unbroken, so the loop device leaves half the circuit bare. Removing the transmitter also removes the loop the puck lived in; there is no 4-20 mA pair left to guard.
Three mismatches decide it. Conductor count: 2 versus 6 plus shield. Signal tolerance: a loop receiver reads current, so a few volts of residual across the pair passes unnoticed, while a bridge output of this size reads every microvolt of difference. Series impedance: loop protectors use series elements freely, and a series element sitting in a sense line corrupts the excitation feedback.
The replacement is a device made for the job. Load cell/RTD protectors are built for weighbridges, strain gauge bridges and RTD runs, and they clamp all six wires plus the shield in one housing. For circuits that genuinely stay on 4-20 mA, the placement logic is the same, and it is set out in SPD placement for 4-20 mA analog inputs.
Which protector ratings decide the selection?
Coverage and let-through decide it: the protector must clamp all six conductors plus the shield in three stages, and its residual voltage at rated discharge current must sit below the module's 15 V survivable-input limit, not merely below a nominal clamp voltage printed larger on the page.
Multi-stage signal protectors work as a cascade: a gas discharge stage takes the bulk energy, a series decoupling element forces the drop across it, and a silicon clamp stage finishes at a level electronics survive. The ratings are measured under the surge test of IEC 61000-4-5, which applies a 1.2/50 µs open-circuit voltage wave with a matching 8/20 µs short-circuit current wave. Read three lines off the datasheet: residual voltage at that current, leakage at working voltage, and series resistance per path.
The excitation path must carry the bridge's 28.6 mA without a meaningful drop, and the sense path must stay a sound continuity check. Protectors built for weighing cover 1-4 load cells in parallel on 4- or 6-wire wiring, shield included. The words surge and lightning get used loosely on signal datasheets; the distinction is laid out on surge protector versus lightning protector for industrial signal cables.
What does the protector's leakage current cost in weight?
Convert leakage into weight before you buy: 1 µA across the signal pair of a 350 Ω bridge produces 350 µV of offset on a 20 mV signal, a 1.75% zero shift that reads as 175 kg on a 10 t scale. Run the example with its assumptions on the table: a 350 Ω bridge, 2 mV/V output, 10 V excitation, 10 t capacity and 1 µA of datasheet leakage.
- Full-scale signal: 2 mV/V × 10 V = 20 mV.
- Offset: 1 µA × 350 Ω = 350 µV = 0.35 mV.
- Share of span: 0.35 mV / 20 mV = 1.75%.
- Weight error: 1.75% × 10,000 kg = 175 kg of zero shift.
Leakage from each line to ground mostly shifts common-mode, which the module's 250 V range swallows at microamp currents. The damaging path runs straight across the signal pair, where the source impedance is roughly the bridge resistance. Three inputs move the answer: a 1000 Ω bridge doubles the offset per µA, a higher excitation raises the span, and leakage that drifts with temperature turns a fixed error into a wandering zero.
For a scale read to 0.1% of full scale, the budget is 20 µV of offset: 20 µV / 350 Ω ≈ 0.06 µA of leakage. That is a tight figure, and it is why weighing-class protectors exist as a product family of their own. Take the leakage line from the datasheet in front of you and run the same four lines of arithmetic.
Where does the protector mount, and how do you bond it?
Mount the protector where the outdoor field cable becomes protected wiring, inside a metal junction enclosure at the scale or wall entry, and bond its ground terminal to the enclosure's ground bar with a copper strap kept under 100 mm. Bond length is a calculation, not a tidy-up detail. A straight conductor carries about 1 µH of inductance per metre, and the example surge drives 1 kA into an 8 µs rise, so di/dt is 125 A/µs. The strap adds V = L × di/dt = 1 µH × 125 A/µs = 125 V per metre of lead. A 300 mm strap adds about 38 V on top of the clamp, more than double the module's survivable-input budget; a 100 mm strap adds about 12 V. Keep the bond short, wide and flat, and land it on a ground terminal rather than a hinge or a cover screw.
For the box, the stainless wall-mount junction boxes fit this duty: manufacturer-rated NEMA 4X / IP66; not UL listed, with a hinged gasketed door, a removable mounting panel and wall-mount feet. Run a copper conductor from the box's ground terminal back to the panel's ground bar; the stainless wall is not a ground conductor, and conductor sizing and electrode rules are covered in the enclosure grounding and bonding guide. A protector left in its own plastic housing outside the box gives up hose-down protection and invites the bonding gaps described in grounding a surge protector in a non-metallic box. And when the strap lands badly, the protector clamps happily while the module dies anyway, the failure mode behind a 4-20 mA surge protector that kept failing after lightning.
Route the field cable to one end of the box and the module run out the other, with no shared duct between them, so the surge cannot couple around the clamps. Enter through glands matched to the cable OD; cutouts made to the drawing keep the box's rating, as the cutouts, glands and HMI windows guide sets out. Terminate the shield through the protector's shield terminal, and take the one-end-or-both decision the way the RTD and thermocouple shield grounding article works it.
What goes on the order?
Order three things: a three-stage load cell/RTD protector specified by the lines in this table, a metal junction enclosure with the cutouts already made, and a short flat copper strap for the bond.
| Order line | Spec to write | The number behind it |
|---|---|---|
| Protector type | Three-stage load cell/RTD surge protector, 6 conductors + shield, 4- or 6-wire wiring | excitation, signal and sense pairs |
| Let-through | Residual voltage below the module's survivable input at its rated discharge current | ±15 V example budget |
| Working point | Carries the 10 V excitation without conducting; leakage inside the zero-shift budget | 28.6 mA excitation; 0.06 µA for 0.1% of span |
| Cell count | Rated 1-4 cells in parallel when the scale has more than one | weighing-class protector spec |
| Junction box | Stainless wall-mount, manufacturer-rated NEMA 4X / IP66, removable panel, glands cut to the cable OD | outdoor entry, washdown |
| Bond | Flat copper strap, under 100 mm protector-to-bar | 125 V per metre of lead |
| Power and network | SPDs on the rack supply and communications entries, matched to each port | selections separate from this protector |
Decision, by installation. On an outdoor scale hung on a steel structure with a strike history, the full package goes in: protector at the cable entry, stainless junction box, sub-100 mm bond, shield through the device. On an indoor run inside one bonded structure, the same protector moves to the panel entry where the cable first meets the building's ground. Wherever the run shares a route with power, protect the power side too, as laid out in surge protection for a 240 V single-phase machine panel. Send the protector supplier the cell count, the wiring (4- or 6-wire), the excitation voltage and the cable length. Send the enclosure order with gland positions and sizes and we cut each hole to the drawing; the box is delivered in 10 business days from your order, and for custom work from your approval of the drawing.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 6 × 6 × 4 in | 304 stainless | 6 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 8 × 6 × 4 in | 304 stainless | 8 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 10 × 8 × 4 in | 304 stainless | 10 x 8 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Does any of this protection help if lightning hits the conveyor structure directly?
No. A signal-line protector diverts what it is rated for, 1 kA in the 8/20 µs example wave, and a direct strike carries tens of kiloamperes into the steel itself. Direct-strike control belongs to the structure's air terminals, down conductors and bonding. The protector then handles only what couples into the six conductors and the shield.
Can one protector cover a scale with more than one load cell?
Yes, when the device is rated for parallel cells. Protectors built for weighing commonly accept 1-4 load cells in parallel on 4- or 6-wire wiring, with all six conductors and the shield protected. Add the cells' excitation currents when you check the series path, and keep the parallel junction inside the protected zone.
What size junction enclosure does the protector need?
Size for separation and glands rather than volume. The field cable enters one end, the load-side run to the module leaves the other, and the two wiring groups never share a duct. The stainless wall-mount junction boxes come in nine sizes with a hinged gasketed door, a removable panel and wall-mount feet, delivered in 10 business days.
Where should the cable shield land now that the protector sits in line?
Through the protector's shield terminal, per its installation instructions, so the shield joins the controlled discharge path instead of floating as an antenna. At the module end, follow the module's own shield rule. For the one-end-or-both decision on long instrument runs, the RTD and thermocouple shield grounding article works through the trade-off.
Does the load cell protector also cover the rack's supply and network ports?
No. It clamps the six signal conductors and the shield only. A transient on the rack's 24 V DC supply, its AC feed or its network entries needs a device matched to that port, selected for the job. Power-side selection for a machine panel is its own exercise, set out in the 240 V single-phase surge article.





