Bond every analog field-cable shield at one end only, on the cabinet's earth bar, and connect the instrument earth to protective earth at a single point. When the same I/O card fails after each thunderstorm, the damage path is almost never the card. It is storm equalization current between two earth points, riding on shields bonded at both ends. It can also ride on a field device that bridges the functional and protective earth networks.
Why do I/O cards keep failing after thunderstorms?
A strike raises the earth potential at one point thousands of volts above another point tens of metres away. Every conductor joining those points carries part of the equalizing current. A field cable shield bonded at both ends is exactly such a conductor. The current induced on it couples into the signal pairs and into the card's front-end electronics.
The mechanism is geometry, not a weak earth. "Reasonably good" earth resistance at power frequency says nothing about the high-frequency path a strike takes. What decides the damage is how long and how inductive the loop is, and which conductors bridge it. A shield running 30 m between a cabinet and a field junction box, bonded at both ends, is a tuned pickup for that transient. Cards fail, you replace them, and the next storm fails them again, because the path is still there.
What symptoms point to surge instead of a bad card?
Record the failure pattern before swapping hardware. These symptoms, taken together, point at the field wiring and earthing rather than at the slot:
- The same card type fails, often in the same rack position, within hours of a storm.
- Failures cluster on cards wired to long field cables, while cards on short internal wiring survive.
- Diagnostics show channel-level faults on several channels of one card at once.
- Field-side checks find drain wires landed at both cable ends, or a 4-20 mA device whose housing, conduit and shield all land on different earth networks.
- The nearby surge protector has not operated, or keeps failing for its own grounding reasons.
Replacing the card restores the system and proves nothing about the path. Use the replacement only to get back online, and make the wiring and earth checks below the actual investigation.
How much current can a both-ends shield carry during a strike?
Enough to destroy a card: in the worked example below, a 2 Ω shield loop across a 10 kV earth potential difference carries a 5,000 A pulse. Both numbers are hypothetical worked-example assumptions chosen to be typical of a nearby strike and a 30 m drain wire. Replace the resistance with your measured value before selecting anything.
Worked example. A 30 m analog cable runs from the control cabinet to a field junction box. Its drain wire measures 2 Ω end to end. A strike 100 m away raises the junction-box earth 10 kV above the cabinet earth for the duration of the transient.
- Loop current: I = V / R = 10,000 V / 2 Ω = 5,000 A.
- Even a modest 500 V difference across the same loop gives 500 / 2 = 250 A, three orders of magnitude above the tens of milliamps a signal shield is meant to see.
- If that shield is also folded around the signal pairs, tens of amps couple inductively into the loop side of a 4-20 mA input. That is well past a card front-end rated around 30 to 50 mA with clamping rated for joules, not kiloamperes.
Bond the same cable at the cabinet end only and the loop does not exist: the open end carries no net current, and the shield still shields. That single change removes the dominant path.
What checks find the shield and earth faults?
Isolate and verify absence of voltage on the field circuits and the card before opening anything. Then work through this list with both ends of each cable disconnected:
- Trace every shield. Walk each cable from card terminal to field device. Record where each drain wire lands. Anything bonded at both ends, or bonded through a gland, a device body or a junction-box wall, is a loop.
- Measure the drain wire. An end-to-end resistance above a few ohms on a 30 m run suggests a corroded or undersized drain, which concentrates rather than carries the transient.
- Test the field wiring. At 250 to 500 V DC with electronics disconnected, take 1 MΩ conductor-to-ground as a pass for this example. A cable measuring kilohms feeds moisture faults into the card long after the storm work is done.
- Check the FE-to-PE separation. Follow the instrument earth from the card to its single connection with protective earth. A second bond re-creates the bridge, often hidden in a field device that mounts its housing on grounded structure while its signal reference returns to the instrument earth.
- Inspect the slot. Bent or carbonized backplane contacts can hold a fault in one position. Compare against an unaffected identical channel before blaming the wiring.
For where the shield drain should land relative to the supply reference, see cable shield to earth ground or power supply negative, and the fundamentals in the grounding and bonding guide.
Where should each shield be bonded?
At the panel, on the designated earth bar, one end per shield, with the far end cut back and taped so it cannot touch anything. The shield's job is electrostatic screening of the pairs; its surge job is to be a non-path. Grounding the shield at both ends maximizes screening at power frequency but buys the storm current a route. So the trade goes to the single-point bond, unless a parallel equipotential conductor sized for fault and surge current runs with the cable.
Land drain wires on an insulated earth bar mounted on the panel backplate, and run a single bond from that bar to the main earth terminal. Ten small shield bonds belong on a bar or a stud chosen for the count, a decision earth bar or one earth stud for ten panel earth cables walks through.
Should instrument earth be separate from protective earth?
Keep the two bars separate inside the cabinet and connect them at one point, usually near the incoming supply. Protective earth is sized to trip breakers on a fault, and its voltage moves during surges and load events. The instrument earth exists to hold a stable reference for signals. Mixing the two lets that movement ride into every analog channel.
The practical rule: one connection, deliberately made, labeled, and drawn. Every other FE-to-PE junction, including ones made accidentally through mounting hardware or conduit, is a storm-current bridge. Panel earth and shield earth as one grounding system with separate bars shows the bar arrangement, and clean earth bonded to protective earth at one point sets the one-grid-one-point rule.
What should the field junction box look like?
A small stainless wall-mount box, manufacturer-rated NEMA 4X / IP66 and not UL listed, with insulated gland plates and a small earth bar for the single shield bonds it hosts. Give the box its own bond back to the structure it serves. Keep any instrument-earth reference inside it tied back to the cabinet's instrument bar, not to local earth on its own. Our 316L junction boxes for washdown and coastal sites come in nine wall-mount sizes, each with a removable panel and gasketed hinged door, built to order and delivered in 10 business days from drawing approval.
A box that floats half-bonded, with shields landed on its wall and its door touching a grounded strut, is where both-ends bonds get created in the field.
How do you keep the next storm from doing the same damage?
Fix the paths, then prove the fix:
- Re-terminate every shield single-ended on the cabinet earth bar; tape and label the far ends.
- Remove every accidental FE-to-PE junction found at field devices, conduits and mounts.
- Replace any cable that failed the insulation test; a repaired wet cable fails again.
- Add surge protection on the field loops that leave the building, sized and grounded per its instructions.
- Restore circuits one at a time, checking diagnostics after each, so any reintroduced fault names itself.
- Keep a one-line earthing drawing in the panel door, updated after every change.
When should you re-specify the enclosure instead of rewiring it?
Re-specify when the box itself prevents a correct earthing layout: no space for a separate insulated instrument bar, gland entries that force shields onto the wall, or a depth too shallow for duct, terminals and the bend space at power terminals. A cabinet that cannot host one earth bar, one FE-PE link and clean gland terminations will drift back into loops with every maintenance visit. Our custom stainless enclosures let you set material, width, height, depth and every cutout from one piece. The gland plate, the bar positions and the door swing are on the drawing before anything is cut, with delivery in 10 business days from your approval of that drawing.
Decision. Same card failing after storms, shields bonded both ends: re-terminate single-ended on the cabinet bar and the failures stop. Shields correct but signals still erratic: hunt the accidental FE-to-PE junction at a field device. Card fault stays in one slot after the wiring checks: replace the rack hardware, not the cable. Box too small or wrongly glanded for a correct earthing scheme: order the layout you need rather than re-fighting the old one.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 6 × 6 × 4 in | 304 stainless | 6 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 8 × 6 × 4 in | 304 stainless | 8 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 10 × 8 × 4 in | 304 stainless | 10 x 8 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can I ground a cable shield at both ends in a control panel?
Ground a shield at both ends only where the design provides a parallel equipotential bonding conductor sized for fault and surge current, for example a 16 mm² copper bond run with the cable. Without that parallel path, a both-ends bond turns the shield into the only bridge between two earth points, and it carries the full equalization current during a strike. Bond at one end and leave the other insulated.
How much surge current can flow on a shield bonded at both ends?
It depends on the earth voltage difference, not on the shield. In the worked example here, a 10 kV potential difference between two earth points across a shield loop of 2 Ω drives 5,000 A for the microseconds of the strike. Even 500 V across that same 2 Ω loop is 250 A, far beyond the milliamp-level drain wire ratings a signal shield is sized for.
Should instrument earth be separate from protective earth?
Keep the bars separate and connect them at exactly one point, usually the main earth terminal near the incoming supply. Separation everywhere else keeps 24 V signal returns and shield drains off the heavy fault-current path. Two separate bonds, or a field device housing that touches both networks, re-creates the loop that storm current uses.
What insulation resistance should field signal wiring test to before a card is replaced?
For 24 V analog loops, test each conductor to ground and conductor to conductor at 250 to 500 V DC with all electronics disconnected, and take 1 MΩ or better as a pass in this example; your project cable specification sets the number that applies. A wet or crushed cable measuring kilohms will keep damaging cards even after the shield bonds are fixed.





