Yes, ground both parts: run one 10 AWG copper conductor from the enclosure's ground screw and a second one from the coax lightning arrestor, and land the two on the same ground bar or grounding electrode system. The screw hole at the bottom of the box is the enclosure's bonding point. The factory screw in it is usually too short to carry a crimped lug, so plan a longer one from the start. NEC Article 810 sets the antenna side's wire floor at 10 AWG copper, and the same size serves the box bond. The whole job is two wires, two crimped lugs, one bar and about an hour at the pole.
Is that screw at the bottom a grounding point?
Yes: that screw bonds the enclosure metal itself to the grounding system, and NEC 250.96(A) requires exactly that — metal parts bonded together so they can safely conduct any fault current likely to be imposed on them.
In a stainless box the screw normally bites a tapped boss in the wall or floor panel, so the bond lands on bare metal with no prep. Painted steel is the opposite. NEC 250.12 requires nonconductive coatings such as paint and enamel removed from threads and contact surfaces at grounding connections, so scrape behind the lug before you torque it. Give the removable mounting panel a path too: a bonding jumper to the bar, or standoffs that land on a bonded surface. The panel then stops floating at surge time.
A stainless box helps the job along. The outdoor wall-mount boxes we build are manufacturer-rated NEMA 4X / IP66 — not UL listed — and they arrive with a hinged gasketed door, a removable mounting panel and wall-mount feet. The bond points are bare stainless from the first turn of the screw. If the fundamentals need a refresher, the enclosure grounding and bonding guide covers fault paths. Its key line here is NEC 250.4(A)(5): the earth is not considered part of the effective ground-fault current path.
Do you ground the enclosure, the arrestor, or both?
Ground both, with two separate conductors landing on one bar. The enclosure bond carries power-system faults, the arrestor run shunts surge off the coax, and one loose lug then cannot leave either part unbonded.
The two conductors do different jobs, so one wire from screw to arrestor is a compromise rather than a saving. A coaxial arrestor is a gas tube between the antenna connector and the radio; when it fires, it dumps the pulse into its ground lug. If that lug shares a daisy-chain with the enclosure bond, the pulse rides the shared wire to the box, the panel and anything clamped to them. Two separate runs also match the logic that keeps mast and coax grounded apart: they are two entry points for the same storm.
| Part | Its conductor's job | Minimum size | Lands on |
|---|---|---|---|
| Enclosure ground screw | carry power-system fault current | sized to the overcurrent device ahead of it (NEC Table 250.122) | the ground bar |
| Coax arrestor ground lug | shunt the pulse the arrestor fires | 10 AWG copper (NEC Article 810) | the ground bar |
| Metal mast over the box | carry a strike on the antenna itself | same size, routed straight | the same electrode system |
| Rod driven at the pole | give the surge a local path into soil | 6 AWG copper bond to the main system | the main grounding electrode system |
Where the bar sits decides how short the runs can be. The ground-bar mounting article for outdoor NEMA 3R enclosures covers hardware that survives weather, and the wall-versus-plate placement article covers where a bar does the most good inside a box.
What conductor size does the code ask for?
NEC Article 810 sets the antenna system's grounding conductor floor at 10 AWG copper — 17 AWG copper-clad steel or bronze also passes. That size is the sensible one for the enclosure bond on a small outdoor box too.
Bigger wire is always allowed; length and turns hurt a surge run more than gauge does. Surge current moves in microseconds, so the inductance of a coiled or sharply bent conductor dominates the math. NFPA 780's lightning-protection rules keep conductor bends at a radius of 8 in [200 mm] or more; give both runs that radius where the route turns.
Insulated equipment grounding conductors of 6 AWG and smaller must be green or green with yellow stripes under NEC 250.119, so buy the spool in green. The IEC side frames the same two jobs as IEC 62305-3 for the structure, touch and step voltage included, and IEC 62305-4 for the electronics. Both lean on short, straight down-conductors, which is the same reason these runs stay direct.
Getting a conductor through the wall without shredding it is its own step, and the enclosure-entry connector and bond article covers landing a grounding conductor right where it enters the box.
Where does the ground bar land?
Land both conductors on one bar tied to the building's grounding electrode system. At a pole-mounted box a driven rod is an auxiliary electrode under NEC 250.54 — it may join the equipment grounding conductor, but it never takes the conductor's place.
During a strike, two parts of an installation at different potentials flash to each other, and that side-flash is what kills radios and Ethernet ports. One bar gives the surge one place to arrive. Put the arrestor where the coax enters — the wall penetration or the box itself — because grounding the coax as close as possible to its entry point shunts the pulse before it runs indoors. The outdoor coax entry article covers keeping that entry bonded and dry at the same time.
A rod at the pole supplements the run back to the service ground, a point the ground rod and grounding bushing question makes for a machine with its own electrode. When the bar's tail lands on the grounding electrode conductor itself, the GEC-to-service-enclosure article shows how that connection is made on a box.
What screw and lug fit the ground hole?
The factory screw is usually a 10-32 machine screw only about 3/8 in [10 mm] long — 10-32 being the standard North American ground-screw thread. Fit a 10-32 stainless screw 3/4 in [19 mm] long, M5 x 16 mm on metric hardware, to carry a #10 crimped ring lug.
The arithmetic: a #10 ring lug stacks about 1/4 in [6 mm] of tongue and washer against the wall, and a 10-32 screw needs two or three full threads past that, so 3/4 in [19 mm] of thread does the job with margin. Typical machine-screw torque tables put a 10-32 screw near 20 in-lb [2.3 N·m]; on stainless hardware, snug plus a quarter turn is the practical equivalent. An external-tooth lock washer under the lug keeps the joint tight through freeze-thaw. The screw-thread and lug-fit article covers thread engagement and lug selection in depth.
You need seven parts, none of them exotic:
- the same-size copper conductor, green insulated or bare, cut to length for each run
- two #10 ring-tongue crimped lugs, copper body
- one 10-32 x 3/4 in stainless machine screw (M5 x 16 mm metric equivalent) with an external-tooth lock washer
- a ground bar with #10 screw terminals, or a bonding hub where the run goes straight to the electrode conductor
- a ratcheting crimp tool sized for insulated #10 lugs
- a cable gland or hub for the conductor's wall entry, sized to hold the box's rating
- a hand driver or torque wrench that reads in in-lb
If the box itself is still on the order list, the outdoor wall-mount enclosures page covers material and rating choices, and the stainless junction boxes page covers the small sizes that work as splice and pull boxes beside the gateway.
How do you run and connect the two conductors?
Run each conductor as one straight piece from its part to the bar. 15 ft [4.6 m] of it adds about 0.015 Ω, while every coil, splice or loose joint adds exactly the voltage a fast surge converts into a flashover.
Power the gateway down and verify absence of voltage before any screw comes out of a live box. Then the steps run in order:
- Remove the factory screw from the ground hole and confirm the thread is 10-32; chase the hole clean if the box is painted.
- Cut both conductor runs to finished length, each one straight from its part to the bar.
- Crimp a #10 ring lug onto each end and pull-test every crimp by hand; a good ratchet crimp resists a firm tug.
- Fit the 10-32 x 3/4 in stainless screw through the enclosure lug with its external-tooth washer and torque it to about 20 in-lb [2.3 N·m].
- Mount the arrestor inline at the coax entry, antenna side out and radio side in, and land its ground lug on the bar with the second conductor.
- Land the bar's tail on the grounding electrode conductor or electrode system; where a rod is driven at the pole, bond rod to bar with 6 AWG copper.
- Bring the conductor into the box through a rated gland, seat the door gasket and close up.
What checks prove the bond works?
Meter from enclosure screw to bar and from arrestor lug to bar. A clean path reads about 0.1-0.3 Ω on a handheld meter, most of that is the leads, and a reading near 1 Ω points at a bad crimp, film under the lug or a loose screw.
Worked example, with the assumptions on the table: take a 15 ft [4.6 m] run of that conductor at about 1.0 Ω per 1,000 ft [3.3 Ω per km] at 20 C. The wire alone is 15 / 1,000 x 1.0 = 0.015 Ω, two crimped joints add roughly 0.0005 Ω each, and the metal path comes out near 0.016 Ω. If a nearby strike pushed an assumed 1,000 A down it, the peak drop along the run would be 1,000 x 0.016 = 16 V. Scale the current to the tens of kiloamps a direct strike carries and the same run drops hundreds of volts, which is the whole argument for short, straight runs into one shared bar.
The 0.1-0.3 Ω reading sits above the metal-path number because the meter's leads, clips and contact spots set the floor, so track change between visits. A reading that climbs from one season to the next means a crimp or screw is loosening. Weather cycles work small lugs loose, and arrestor ground lugs are the usual suspects after a season outdoors. The surge-arrestor ground lug failure page walks what that failure looks like and how to catch it early.
Recheck both screws after any nearby strike as well. Protectors and analog loops that misbehave after a storm usually trace back to a bond, as the surge-protector-after-lightning article shows.
Which mistakes undo the grounding?
The failures cluster around five causes: paint or oxide film under a lug, one daisy-chained wire instead of two runs, a coiled spare length, aluminum wire on a copper-only lug, and the coax shield asked to do a bonding conductor's job.
- Film under the lug: scrape lug face and wall surface to bare metal before the screw goes in.
- Daisy-chain wiring: run the second conductor, because one wire turns any loose joint into two unbonded parts.
- A coiled spare: the coil's inductance spikes exactly during the fast pulse the arrestor exists for, so cut both runs to length.
- Aluminum on a copper-only lug: outdoor aluminum terminations need hardware rated for aluminum, and the aluminum termination article covers the oxide film behind the trouble.
- Shield-as-ground: the coax braid is a surge path, not the bonding conductor; the arrestor's own copper run does that work.
The decision, one line: two 10 AWG copper runs, one ground bar tied to the electrode system, a 10-32 x 3/4 in stainless screw under each lug, a 6 AWG bond on any rod at the pole. A meter reading near 0.2 Ω from screw to bar, and you call it done.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can one conductor serve the ground screw and the arrestor together?
You can, but run two. A daisy-chain from screw to arrestor leaves both parts unbonded when one lug works loose, and the surge then hunts for the next path, usually the radio or the Ethernet run. Two separate copper conductors on one bar isolate each connection and cost no more than one longer wire.
How tight should the replacement ground screw be?
About 20 in-lb [2.3 N·m] on a 10-32 screw, the figure typical machine-screw torque tables list for that size; on stainless hardware, snug plus a quarter turn is the practical equivalent. Re-check the torque after the first winter outdoors, because freeze-thaw and vibration loosen small fasteners.
Does a metal antenna mast need its own ground conductor?
Yes. NEC Article 810 treats the mast as part of the antenna system, and it expects the same treatment as the coax: a grounding conductor of no less than 10 AWG copper, routed straight to the same electrode system. An antenna mounted on a grounded enclosure does not excuse a separate roof or tower mast.
What size wire bonds an extra ground rod to the building's main ground?
6 AWG copper, minimum. The NEC requires an additional electrode, such as a rod driven at the pole, to be bonded to the main grounding electrode system with no less than 6 AWG copper. The rod then works as an auxiliary electrode under NEC 250.54: it supplements the equipment grounding conductor, and the conductor back to the service ground stays in place.