Short answer: take the ground block off the conduit face and give it a real home — a stainless box rated NEMA 4X / IP66 by the manufacturer, not UL listed, with each coax through its own gland and a drip loop below the entries. Bond the block to the service grounding electrode system with #10 AWG copper in one straight run under 10 ft [3 m]. A bare block on a wall fails two ways: water sits in the F-joints until a freeze splits them, and a bonding wire looped around the building is too long to carry a surge. You fix both in an afternoon with the box, two glands and a short green wire, and the checks at the end prove the job.
What the job needs
Order the box with its two gland holes cut at the factory. A punched, deburred hole gives the gland nut a flat seat, which a field-drilled hole rarely does. Your list:
- One stainless junction box from the stainless junction boxes range; the smallest size in it carries a block, a bonding lug and a service loop with room to spare. Salt water or winter road salt on the wall means 316L; inland walls serve with 304.
- Two coax-rated M20 glands with 5-10 mm sealing inserts. RG-6 quad-shield jacket runs about 6.9 mm [0.27 in] outside diameter, so the insert grips mid-range. The cutouts and glands guide carries the hole dimensions.
- Compression F-connectors on both cable ends, and the ground block itself: an F-barrel with a bonding tab, the bond point every coax entry needs.
- 12 ft [3.7 m] of green #10 AWG copper — NEC 250.119 keeps insulated grounding conductors of 6 AWG and smaller green or green with a yellow stripe — plus two ring lugs, emery cloth and a socket wrench.
- A multimeter with a low-ohms range for the checks at the end.
Power entering the same wall? Plan the two entries apart before you drill; coax and power sharing one weatherproof box covers what works when they must meet.
Mount the box and the block
- Choose the wall by distance first: within 10 ft [3 m] of the intersystem bonding termination, the listed bar at your service where telephone, CATV and satellite bonding conductors land. Everything else follows from that.
- Fasten the box plumb with the gland holes in the bottom wall. Bottom entries put gravity on your side and leave the lid unbroken; a lid hole collects water even with a gland in it.
- Fit compression F-connectors on both cable ends with the tool made for them, before the cables go near the box.
- Pass each cable through its gland body, set the bodies in the factory-cut holes, and lock the nuts. Leave about 6 in [150 mm] of service loop inside so the connectors reach the block without strain.
- Screw both connectors onto the block hand-tight, then a light wrench seat. F threads are brass, and more force strips them.
- Screw the block to the mounting panel with two screws and toothed washers. A block swinging on its coax works its own joints loose within a season.
Bond the shield in one short run
The enclosure grounding and bonding guide covers the fundamentals; here is the coax-specific sequence.
- Cut the green #10 AWG to reach the intersystem bonding termination in one piece. The NEC calls for a copper bonding conductor of #10 AWG minimum on CATV and antenna coax, run in one length, as straight and short as the building allows.
- Ring-lug both ends, with the strands visible past the barrel before you crimp or screw.
- Brighten both landing surfaces with emery cloth first. NEC 250.12 requires paint, lacquer and enamel removed from threads and contact surfaces at grounding and bonding connections, and outdoor paint is the usual offender.
- Land one lug on the block's tab and the other on the intersystem bonding termination. Sweep the run in gentle curves; a sharp kink behaves like a turn of coil.
- Bond the box itself: a #10 jumper from the box's ground stud to the same point as the block's lug, so shell and gland plate ride the same path. Cable gland bonding in stainless boxes covers what the plate and fittings carry.
- Metallic conduit on the same wall gets a listed bonding bushing where it meets the box, biting through the coating. A clamp sitting on paint carries almost nothing at surge speed.
Why 10 ft is the working limit
A surge on the shield looks for the shortest metal route to earth, and the wire's own inductance is the obstacle. Straight #10 AWG carries about 1.3 µH per metre [0.4 µH per ft], and every bend adds more. The driving voltage is V = L × di/dt, and surge practice takes a lightning-induced front at 10 kA/µs.
Work the numbers for a block 8 ft [2.4 m] from the service, run straight:
- 2.4 m × 1.3 µH/m = 3.1 µH of conductor
- 3.1 µH × 10 kA/µs = 31 kV developed along the run
That 31 kV adds to whatever the block clamps, and it sits on the shield your equipment ties to. Route the same wire 20 ft [6.1 m] around the garage: 6.1 m × 1.3 µH/m = 7.9 µH, and 7.9 µH × 10 kA/µs = 79 kV. Each metre of extra run costs about 13 kV at that rate of rise, and halving the rate halves every figure with it. That is why "bonded" and "bonded close" are different installations.
| Service electrode position | What you do |
|---|---|
| Within 10 ft [3 m] of the entry | Straight #10 AWG run to the intersystem bonding termination |
| 10-20 ft [3-6 m] | Same run along the wall in gentle sweeps; accept the added inductance |
| Beyond 20 ft [6 m] | Move the entry point, or add an auxiliary electrode at the wall tied to block and service |
| No metal route available | Run copper to the electrode system anyway; NEC 250.4(A)(5) keeps the earth off the fault path |
NEC 250.54 lets you connect that auxiliary electrode to your bonding conductor, and the copper run stays regardless.
Seal the entry and keep it sealed
- Drip loop: route your cables so each falls at least 4 in [100 mm] below the gland before it rises into the box. Water runs off the bottom of the loop instead of following the jacket into the seal.
- Gland compression: run each seal nut down hand-tight plus a quarter turn, the instruction metric gland packs carry. The insert grips the jacket at that point; past a quarter turn it starts to cut, and short of it the seal breathes with the day-night cycle.
- Keep the jacket unbroken to the gland. Braid or foil under the insert wicks water straight into the box, so seal on jacket.
- The rating belongs to the whole assembly. IP66's second digit means the box held a 12.5 mm nozzle delivering 100 L/min from 2.5-3 m for at least 3 min under IEC 60529; a drain hole, a vent or an empty spare hole drops the assembly to that part's level. Where drainage is wanted, glands, drip loops and drains on an outdoor box shows the Type 3R approach instead.
- A sealed box still breathes slightly as day turns to night. A desiccant sachet at install costs nothing; the outdoor enclosure guide covers heaters and condensation if the box will carry electronics.
Water that reaches an F-joint expands about 9 % when it freezes and pushes the joint apart, which is why the block lives behind the gasket. If a coax join must stay outside any box, weatherproofing coax connections outdoors shows the wrap-and-boot method that survives.
Checks when the job is done
- Continuity: low-ohms meter between the block's tab and the intersystem bonding termination. You want well under 1 Ω, tenths on a decent meter; wiggle the wire while you read, and a rising number means a loose lug.
- Live check at the service: hot-to-bonded-metal reads 120 V, neutral-to-bonded-metal reads 0 V. Treat the service as live, meter it from a dry stance with insulated probes, and keep this the only live work in the job.
- Hose check: spray the closed box from 2-3 ft [0.6-0.9 m] for 2-3 min, then open it. A dry gasket track and dry connectors pass.
- Pull check: a firm hand pull on each cable at its gland. Any movement means the quarter turn went short.
Mistakes that cost the rating
- Gland holes in the lid or top wall: rain pools on the gland face for the whole storm.
- A drain drilled in the bottom for peace of mind: it turns a 4X assembly into an open one and aims hose water at the block.
- The insert clamping braid because the jacket was stripped back too far.
- The bonding conductor coiled for neatness: every turn is an inductor, so shorten the run instead of dressing it.
- The block hanging on its coax with an empty tab: the tab is the entire point of the part.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Does an indoor outlet strip with a coax jack add protection once the block is bonded?
Almost none. A retail strip has no earth path for its coax port, so the surge current it clamps has nowhere to flow. A coax protector earns its place at the entry: mount it beside the block inside the box and bond its tab to the same lug, through a run under 10 ft [3 m]. Inside the house, the bonded block is the protection.
Can I land the bonding conductor on a ground rod at the entry wall?
Only as an addition. A rod at the wall is an auxiliary electrode under NEC 250.54: connect it to the block and to the service electrode system, and keep the copper run in place. The earth between two rods carries surge current badly and slowly, and NEC 250.4(A)(5) keeps fault current on the metal path. The rod supplements the bond; it does not replace it.
What gland size fits RG-6 coax?
An M20 gland with a 5-10 mm sealing insert. At roughly 6.9 mm [0.27 in] outside diameter, a quad-shield jacket lands mid-range in that insert, so the seal rides the jacket, never the braid. Measure your jacket before ordering inserts; the foil layers add a few tenths of a millimetre between brands.
Is 304 stainless fine for a rooftop or coastal mast?
Inland rooftops: 304 holds. Where salt water or winter road salt reaches the box, order 316L; its molybdenum raises pitting and crevice resistance. The chloride stress-corrosion threshold sits near 60 C [140 F] for both grades, far above anything an outdoor box sees, so temperature picks neither grade. Salt picks 316L.