Feeder tap conductors from a junction box: sizing by the tap rule

Tap conductors out of a junction box take their ampacity floor from the upstream device, not the load: 10% of a 600 A breaker within 10 ft (60 A) and one-third within 25 ft (200 A). Each tap also needs an ampacity at or above the breaker it lands on — 150 A, 500 A or 40 A here — and the EGC in each run follows NEC Table 250.122 for the 600 A device: 1 AWG copper, capped at the phase size.

NEMA4 Enclosure engineering team · Published November 24, 2026 · 8 min read

Size each tap conductor from the device protecting the feeder, not from the load it runs. Within the short length [3 m] of the splice, the ampacity floor is one-tenth of that rating — 60 A on the example feeder — and within the long length [7.5 m] it is one-third, 200 A. Every tap then needs an ampacity at or above the breaker it lands on, so a run feeding a 500 A breaker is a 500 A conductor however short it is. The worked example below sizes three runs out of one feeder junction box: a 150 A motor tap, a 500 A motor tap and a 40 A lighting tap. The equipment grounding conductor in each raceway comes from NEC Table 250.122, sized on that same upstream device.

The two tap rules and their floors

The NEC tap rules let a conductor smaller than the feeder's protection leave the feeder at a splice or a lug set. The upstream device still stands behind the run; the rules trade ampacity for length, raceway and termination limits.

A tap up to the short length [3 m]:

  • runs inside a raceway for its whole length
  • ends in the gear it feeds and goes no further
  • carries at least the calculated load
  • carries at least the rating of the breaker at its end
  • carries at least one-tenth of the rating of the device protecting the feeder

A tap up to the long length [7.5 m]:

  • runs inside a raceway for its whole length
  • carries at least one-third of the rating of the device protecting the feeder
  • ends on a single set of fuses or breakers that limits the load to the conductor's ampacity

Both floors come off the upstream device, so the same run sizes differently on different feeders:

Device protecting the feeder Short-run floor (one-tenth) Long-run floor (one-third)
200 A 20 A 66.7 A
400 A 40 A 133.3 A
600 A 60 A 200 A
800 A 80 A 266.7 A
1,200 A 120 A 400 A

Round the floor up to the next conductor: a 66.7 A floor lands on 4 AWG, at 85 A, rather than 6 AWG at 65 A. Every ampacity in this article is copper, read from the NEC ampacity table at 75 °C [167 °F], which assumes terminations marked 75 °C.

Which number wins for each breaker

Three numbers set each tap, and the largest wins: the calculated load, the rating of the breaker at its end, and the length floor above. Short runs to small breakers ride on the floor; big breakers push the conductor up on their own. On the example feeder the flip looks like this:

Tap lands on Short run needs Long run needs
40 A breaker 60 A — the floor 200 A — the floor
150 A breaker 150 A — the device 200 A — the floor
500 A breaker 500 A — the device 500 A — the device

The same arithmetic sizes any tap near the switchboard, down to an enclosure AC unit fed from a panel disconnect. Voltage drop rarely decides a tap at these lengths; size on ampacity first, then confirm the drop.

Sizing three taps from a 600 A feeder in one junction box

The case: a 600 A breaker protects the feeder, and the feeder lands on lugs in a wall-mount stainless junction box. Three conduit runs leave the box. The first runs 25 ft to a 150 A breaker feeding a 50 hp motor. The second runs the same length to a 500 A breaker feeding a 250 hp motor. The third runs 10 ft to a 40 A breaker that feeds a lighting transformer and a small panel.

The rule in words: required ampacity equals the largest of the load, the breaker at the tap's end, and the length floor — one-tenth of the feeder rating at the short length, one-third at the long length. The floors work out to 600 A × 0.10 = 60 A, and × one-third = 200 A.

Tap A, 25 ft to the 150 A breaker: the one-third floor beats the 150 A device rating, so the run needs 200 A. That is 3/0 copper exactly, and "not less than" makes the exact hit legal. Step to 4/0 at 225 A if you want margin for a motor change.

Tap B, the long run to the 500 A breaker: the device rating wins at 500 A. Two parallel sets of 250 kcmil give 2 × 255 A = 510 A, and 250 kcmil clears the 1/0 AWG minimum the NEC sets for paralleling. The single-conductor alternative is 900 kcmil at 520 A. Run each set in its own conduit, three phases per conduit, and the full table ampacity stands.

Tap C, 10 ft to the 40 A breaker: the floor beats the device, so the run needs 60 A. That is 6 AWG copper at 65 A. If the breaker's lugs carry a 60 °C [140 °F] marking only, the 60 °C column reads 6 AWG at 55 A — under the floor — so the run steps to 4 AWG, 70 A at 60 °C. Keep this tap short: the same route at the long length carries the one-third floor and jumps to 3/0 to serve 40 A of lighting.

Every raceway also carries an EGC, sized from the feeder's protective device. NEC Table 250.122 gives 1 AWG copper. An EGC never has to be larger than its phase conductors, so the motor runs take 1 AWG each and the lighting run takes 6 AWG, green: insulated EGCs of 6 AWG and smaller must be green or green with a yellow stripe (NEC 250.119).

Tap Length What decides Required ampacity Copper EGC
50 hp motor long run the floor 200 A 3/0 1 AWG
250 hp motor long run the device 500 A 2 × 250 kcmil 1 AWG
Lighting panel short run the floor 60 A 6 AWG 6 AWG

The lighting tap is where the floor bites: a conductor picked for the 40 A load alone, #8 at 50 A, fails the feeder floor and has only the feeder's protection behind it. The two motor taps ride on their breakers.

The box you splice in

The junction box holds the tap splices or lug blocks and starts every length. Splicing feeder conductors in a junction box is common practice, and the box then has to hold the splice bodies, the conductor tails and the conduit entries. That makes the pull-box dimensions for 4 AWG and larger conductors a separate check. Two motor taps and a lighting tap share one box legally; the rules for multiple motor circuits in one junction box cover that layout. Pick 304 stainless for a dry room and 316L for washdown or corrosive air: our stainless junction boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed.

Running the taps

  1. Lock the feeder out and verify absence of voltage before you open the box or land a lug.
  2. Measure each run from the splice or lug set in the box to the line-side lugs of its breaker, through every bend and drop. Within the short length the one-tenth floor applies; beyond it, up to the long length, the one-third floor.
  3. Write each tap's required ampacity as the largest of its load, its breaker and its length floor.
  4. Pick copper from the NEC ampacity table at 75 °C and confirm the breaker and box lugs carry a 75 °C marking; on a 60 °C-lug breaker, size from the 60 °C column.
  5. Parallel conductors only from 1/0 AWG up, one set per conduit. When a conduit carries more than three current-carrying conductors, apply the correction factors — the fill rules and derating for junction boxes versus wireway work them through.
  6. Size each EGC from NEC Table 250.122 on the feeder's protective device, cap it at the phase size, and land a full-size EGC in every conduit of a parallel run. The grounding and bonding guide carries the fundamentals.
  7. Keep every tap inside a raceway for its full length, and end a long run on the single set of breakers that limits the load to the conductor's ampacity.
  8. Bond the box to both raceway entries so the fault path crosses the box; bonding a feeder tap enclosure: EGC size and EMT lays out the bushings and jumpers. Clear paint from threads and contact surfaces at grounding connections (NEC 250.12).
  9. Give each lug the wire-bending space NEC 312.6 sets for its conductor size; the enclosure sizing guide walks the two bending-space tables.

Checks when done

  • Lengths: every tap measures within its allowed length, splice to lugs, bends and drops included.
  • Ampacity: each conductor clears both its floor and its breaker rating; the 3/0 motor tap sits exactly on its floor, which "not less than" allows.
  • EGCs: the size from the table above lands in every raceway, green at 6 AWG and smaller.
  • Bonding: jumpers or bond bushings on both entries, contact surfaces bare metal.
  • Voltage drop: the long motor tap carries 150 A on 3/0 copper, about 0.077 Ω per 1000 ft at 75 °C, so the drop over its 25 ft is 1.73 × 150 A × 0.077 Ω × 25 ÷ 1000 = 0.5 V, near 0.1% of 480 V — far under the NEC's recommended 3% ceiling for a branch circuit.
  • Labels: mark the tap length and the rule that sized it inside the box door, so the next resize starts from the feeder, not the load.

Mistakes that shrink the protection

  • Sizing from the load. #8 looks right for 40 A of lighting at 50 A, but the feeder floor sits higher, and the run fails with only the feeder's protection behind it. The floor picks the size, not the motor or the panel.
  • Paralleling small conductors. Two #4s total 170 A and look right for the 150 A breaker, but the NEC draws the parallel line at 1/0 AWG. One 3/0 carries the same run with no parallel set at all.
  • Losing count of length. A 28 ft route fails both rules however fat the copper. Shorten the route, move the box, or land the run on a breaker sized to the conductor so it is a protected feeder instead of a tap.
  • Splitting the tap end. A long run lands on one set of fuses or breakers; a run that splices again and splits to two small breakers leaves the rule behind. Put the split in a panel fed by a conductor sized to its own protection.
  • Treating the feeder as a tap. The feeder conductors from the switchboard are sized to the upstream device; the floors only ever reduce sizes below that protection.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
6 × 6 × 4 in304 stainless6 x 6 x 4 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
8 × 6 × 4 in304 stainless8 x 6 x 4 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
10 × 8 × 4 in304 stainless10 x 8 x 4 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

What size conductor does a 25 ft tap from a 600 A feeder need?

At least one-third of the upstream rating, 200 A on the example feeder, and never less than the breaker it lands on. A tap to a 150 A breaker takes 3/0 copper, 200 A at 75 °C, and a tap to a 500 A breaker takes 500 A at any length, met with two parallel sets of 250 kcmil for 510 A. The length runs splice to lugs and stays in raceway.

How small can a 40 A lighting tap be on a 600 A feeder?

Inside the short length the one-tenth floor applies, 60 A, so 6 AWG copper at 65 A carries the run to its 40 A breaker. Size from the breaker's lug marking: on a 60 °C-lug breaker the run steps to 4 AWG. At the long length the floor is the one-third value and the conductor jumps to 3/0.

What EGC goes in each tap raceway?

NEC Table 250.122 sizes it from the device protecting the feeder: 1 AWG copper in each motor run on the example feeder. The cap is the phase size, so the 6 AWG lighting tap carries a 6 AWG green EGC. A parallel run takes a full-size EGC in every conduit, and the box bonds to both raceway entries.

Can two #4 conductors parallel into a 150 A tap?

Paralleling starts at 1/0 AWG, so two #4s stay out even though they total 170 A. A single 3/0 clears the 150 A breaker on a long run at the one-third floor; within the short length the breaker rating alone makes 1/0, at 150 A, the minimum.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Start a junction box from 6 × 6 × 4 inRequest a custom quote

Stainless junction boxes: sizes for this job

Keep reading

More on layout and installation

All articles

Buying guides

The guides behind this answer

All guides