Run one ground wire. The NEC permits a single equipment grounding conductor to serve every circuit in a raceway, sized for the largest breaker protecting conductors there: 10 AWG copper covers four 30 A, 208 V circuits in one conduit. The four grounds on your drawings are a noise decision, not a code requirement. A clamp meter plus a multimeter settle it in ten minutes. Below are the sizing table, the voltage-drop arithmetic behind the rack-noise argument, and the cases where a second ground conductor earns its place on the order.
Do you need one ground wire per circuit in the same conduit?
No: the NEC permits one equipment grounding conductor for several circuits in the same raceway, sized for the largest overcurrent device protecting conductors there. The 25-60 A table row serves all four 30 A circuits of the example feed.
Table 250.122 sizes the conductor, and the NEC's grounding rules allow one conductor per raceway for exactly that job: where several circuits share a raceway, one EGC sized to the largest overcurrent device protects all of them. Fault clearing is why one works. A ground fault on any circuit needs a single low-impedance path back to the source. The copper conductor sized from the 30 A breakers provides it, and the breaker trips on fault current, not on the conductor count in the conduit.
Single-circuit habits carry over unchanged. Run the insulated ground with the phase conductors as you always have, and terminate it on the ground bar at each end it serves. Keep it distinct from the grounded (neutral) conductor, though: the ground wire carries fault and leakage current only. A neutral carries load current around the clock and lands on its own isolated block, with the two meeting only at the service disconnect. Shared neutrals between panels are a separate design question — parallel neutral current in metal raceways between panels and neutral-ground bonding at the service disconnect cover that ground.
What size does the single ground wire need to be?
Size the shared conductor from the largest breaker in the raceway: a 30 A device needs 10 AWG copper or 8 AWG aluminum under NEC Table 250.122, however many circuits ride behind it.
NEC Table 250.122 lists EGC size against the overcurrent-device rating, and a 30 A breaker falls between the 20 A and 60 A rows, so it takes the 60 A row. Every device from 25 A to 60 A lands there.
| Largest breaker in the raceway | Copper EGC | Aluminum EGC |
|---|---|---|
| 15 A | 14 AWG | 12 AWG |
| 20 A | 12 AWG | 10 AWG |
| 25-60 A | 10 AWG | 8 AWG |
| 100 A | 8 AWG | 6 AWG |
| 200 A | 6 AWG | 4 AWG |
The conduit itself changes the phase conductors more than the ground. Four 208 V line-to-line circuits put eight current-carrying conductors in one raceway, and the NEC adjustment factors take 70% at 7-9 conductors (80% at 4-6). A 10 AWG THHN hot starts at 40 A in the 90 °C column of the NEC ampacity table, and 40 A × 0.70 = 28 A, short of the 30 A trip. Move the hots to 8 AWG THHN and the math clears: 55 A × 0.70 = 38.5 A. The EGC keeps its table size through all of this, because Table 250.122 sizes it from the breaker, never from the phase size.
What happens to the ground wire when the circuits split into different conduits?
Each raceway gets its own ground: when the four circuits leave the trunk through smaller conduits, every one of those conduits carries a copper EGC sized for the largest breaker inside it. The box at the split bonds them together.
The one-conductor permission belongs to each raceway, not to the four circuits as a set. Trunk four circuits in one conduit and split them two-and-two at a pull box, and each outgoing conduit leaves with its own EGC. The 25-60 A row size applies where the largest breaker inside is 30 A, and the 20 A row size where a branch carries only a 20 A device. Four splits give four EGCs — that is the code minimum, and it is also where the per-circuit instinct on the drawings comes from.
Splice the grounds at the split and keep the path continuous. A stainless steel junction box is the natural point: land each EGC on a grounding terminal block or splice it with a listed connector, and bond the metal wall itself so the enclosure joins the fault path. The EGC may be spliced; it may never pass through a device that opens its continuity.
Why does IT equipment push leakage current onto the ground wire?
Every input filter carries small capacitors from each line to the chassis. Each device feeds a trickle of leakage current into the grounding system, and a row of filtered racks can return a couple of amperes on the shared EGC.
Switched-mode supplies almost all carry an EMI filter with capacitors from each line to ground. Those capacitors pass a small current continuously at the supply frequency and its harmonics. The leakages sum, because the devices sit in parallel: 250 devices leaking 8 mA each put 2 A on the common path. Filter capacitance also adds to the wiring system's own capacitance, so a longer run raises leakage a little along with the device count. A couple of amperes on the grounding path is the scale reported for large filtered rack rows; treat it as an example figure and measure your own raceway. The shared EGC is where that current belongs — it is the only intentional path, and it is doing its job.
How much voltage does a shared ground wire add between racks?
Ohm's law sets it: 2 A of leakage through 50 ft [15 m] of the example copper conductor at about 0.001 Ω/ft develops 0.1 V between the panel ground and the rack row. That is a floor value, because inductance and terminations push the real figure higher.
Worked example, with assumptions you replace with your own readings: a 50 ft [15 m] shared EGC of the 25-60 A table row size from panel to rack row, and 2 A of leakage measured on that EGC with the racks at full load.
- Resistance: the copper conductor runs about 1.0 Ω per 1000 ft at 20 °C, or 0.001 Ω/ft.
- Path resistance: 0.001 Ω/ft × 50 ft = 0.05 Ω.
- Drop along the conductor: V = I × R = 2 A × 0.05 Ω = 0.10 V.
The rack-row bonding point therefore sits 0.1 V from the panel ground while everything runs. Double the run to 100 ft [30 m] and the drop doubles to 0.2 V; 4 A of leakage doubles it the same way. At 60 Hz inside steel conduit, inductive reactance adds on top of the DC figure, and one loose lug can add milliohms on the scale of the whole 50 mΩ run — so read 0.1 V as a floor and expect more.
Signal cables hand that 0.1 V a second, unintended path: shield drains and signal references bridge two points at different potentials. The current that flows is the noise your design engineers are worried about. How much 0.1 V matters depends on the signal — a thermocouple input cares about millivolts, a 24 V discrete input does not.
When should you run more than one ground wire in the conduit?
Only on a measurement, never as routine. If a clamp meter reads amperes on the shared EGC and you can measure tens of millivolts between rack bonding points under load, cut the impedance — a second ground of the same size halves the example drop from 0.1 V to 0.05 V.
Measure first. Clamp a leakage ammeter around the EGC alone at the panel with the racks at full load. Read the millivolts between rack bonding points with a multimeter, and watch whether the noise complaint tracks the millivolts as loads switch. You are measuring live by design, so suit up to the arc-flash label on the panel before you open a door. The code tests the fault path and sets no noise number; the millivolt reading is the test that decides this part of the design.
| Fix | Example drop (2 A over 50 ft, from 0.1 V) | Basis |
|---|---|---|
| Second EGC in parallel, same size | 0.025 Ω → 0.05 V | two equal conductors halve the resistance |
| One 6 AWG instead of the trunk size | 0.02 Ω → 0.04 V | 6 AWG runs about 0.4 Ω/1000 ft |
| Bond the steel conduit at both ends | adds a parallel raceway path | metal raceway as an equipment grounding conductor explains when the conduit itself counts |
| Four home runs, one per circuit | removes the shared path | 12 conductors in four raceways against 9 in one |
For the rack side — keeping ESD and signal grounds apart from protective earth — the ESD-grounding-versus-protective-earth article for metal racks covers the part the conduit cannot fix.
The rule the example sets: one EGC per raceway is the code minimum, and every conductor beyond it buys impedance. Buy it when the millivolts show up and the noise follows them; skip it when the rack grounds read zero and nothing tracks the load.
How do the ground wires land inside the panel and junction boxes?
Every EGC terminates on the enclosure's ground bar with its own lug, neutrals stay on the isolated neutral block, and the metal enclosure itself joins the bar through a bonding lug in the box wall.
NEC 250.96(A) requires metal parts intended to serve as equipment grounding conductors — raceways, enclosures, fittings — to be bonded together so they carry the fault current likely to be imposed on them. NEC 250.12 sends paint, lacquer and enamel off the threads and contact surfaces at those connections unless the fitting is designed to bite through. On a painted back panel that means scraped bright metal or star washers under every ground lug; on the stainless boxes we build, the wall is bare metal, so the bond is a lug and a screw away. The fundamentals of bar sizing, bonding jumpers and splices are in the enclosure grounding and bonding guide.
The landing plan for the example trunk takes few terminals: one lug for the trunk EGC, one for the enclosure bond, and one per device ground — count them before you order the ground bar. Neutrals, if the circuits ever grow 120 V loads, land on the isolated neutral block so neutral current never rides the enclosure metal, which is what NEC 250.6 intends.
What do you specify when the conduit carries four circuits?
Specify one copper EGC per raceway sized for its largest breaker, eight 8 AWG THHN hots for the 70% derating, bonded enclosures at every split, and — for IT rack rows only — the leakage measurement that decides any second ground.
- Ground: one EGC per raceway, the 25-60 A row (10 AWG copper, 8 AWG aluminum) for any 25-60 A breaker; 12 AWG copper where the largest device in that raceway is 20 A.
- Phases: 8 AWG copper THHN for the eight hots in the shared trunk; 70% adjustment at 7-9 current-carrying conductors.
- Splits: each new raceway carries its own EGC, sized to its own largest breaker; junction boxes bonded at the wall.
- Terminations: one lug per conductor on the ground bar; bonding surfaces cleared of paint on painted panels.
- IT rows: clamp the EGC, read rack-to-rack millivolts, and let those two numbers decide any second conductor.
Decision by case:
- Commercial and mixed loads, no noise on the logs: one trunk EGC from the table, per-raceway EGCs after the splits. Done.
- IT rack rows with the millivolts tracking noise: buy impedance — a second EGC of the same size takes the example drop to 0.05 V, a 6 AWG upgrade to 0.04 V, and bonded conduit or home runs close the rest of the gap.
- Any mix of breaker sizes: size each raceway's ground to the largest breaker inside it; the single trunk ground stays right while every breaker inside stays at or under 60 A.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 14 × 8 in | 304 stainless | 16 x 14 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Does the equipment grounding conductor count toward ampacity derating?
No. The adjustment factors count conductors that carry load current, and the EGC carries none in normal operation. Four 30 A, 208 V circuits put eight current-carrying conductors in the raceway, so the 70% factor for 7-9 conductors applies to the hots, and the copper ground rides along without changing the count.
What color does the insulated ground wire have to be?
Green or green with one or more yellow stripes: NEC 250.119 sets that for insulated equipment grounding conductors 6 AWG and smaller, which covers the shared conductor in the example trunk. Phase conductors keep their own colors, and the ground wire's color never changes with the number of circuits it serves.
Would separate home runs remove the shared-ground question entirely?
Mostly. Four home runs put two hots plus one copper EGC in each conduit — 12 conductors in four raceways against 9 in the shared trunk of 8 hots plus 1 EGC. Each circuit returns its own leakage on its own ground, so the trunk IR drop of the example disappears; the cost is more conduit, fittings and pull time.
How do you measure leakage current on a shared ground wire?
Clamp a leakage ammeter around the EGC alone at the panel with the load at full draw, and read rack-to-rack bonding points in millivolts with a multimeter. The example is the yardstick: 2 A through 50 ft of the example copper conductor is 0.1 V. Repeat both readings after any grounding change, at the same load.





