Short answer: fill both jumper slots when you chain three or more blocks, and for no other reason. The middle block of the chain takes one 2-pole bar in its upper channel and a second in its lower channel, and its internal metal ties the two together. The second slot buys you reach, not amps. On the block class this page works with — 32 A nominal, 41 A maximum load current in its datasheet — the listed 2-pole bar is rated the same as the block's nominal, and that number caps the whole bridged group however many bars you seat. The bar nearest the feed carries the sum of every load beyond it, so that sum is what you size. Order the bar the accessory list names, seat it with the power isolated, and prove the group with a meter before you load it.
Why the block has two slots
A 2-pole jumper bar bridges exactly two adjacent blocks, in one of the two channels the block body provides. To common three blocks, seat the first bar in the upper channel between blocks 1 and 2 and the second in the lower channel between blocks 2 and 3. Block 2 now carries one bar per channel, its internal conductor joins them, and all three blocks sit at one potential. Extend the chain one block at a time, alternating channels: each added block costs one bar and zero extra panel space.
Longer bars do the same job in one piece. One documented terminal family lists a 4-pole bar rated 65 A for its 65 A block, and smaller blocks take 2-pole bars in the 20 to 24 A class. Alternating channels earns its keep when 2-pole bars are what you hold, which is the default stock in most panel shops.
The second slot is not a current upgrade. Two bars across the same two blocks give the current two routes, and current divides by resistance: contact resistance differs between bars with seating and surface condition, so one bar takes most of the amps. Heating rises with the square of current, so the bar that grabs the load runs hottest, and no terminal maker rates that pair at double.
| What you build with both slots | Bars used | Result |
|---|---|---|
| Chain of three or more blocks | One 2-pole bar per link, alternating channels | One common potential across the chain, each bar at its own rating |
| Two bars across one link | Two | The same two blocks common, still at the single bar's rating |
The bar you order is the one the accessory list names
Start from the marking on the block in front of you, then its accessory print. A bar that seats can still be the wrong part: pitch, well shape and contact geometry all have to match. A look-alike from a search page is the classic wrong pick. The rating rule sits on the terminal maker's own specification pages — one states that its side jumpers carry the same current rating as the block they fit. So on the 32 A nominal block above, the listed 2-pole bar is a part of the same rating, and that figure is the working ceiling for the group. The block's 41 A figure belongs to its own wire clamp; the lower number governs the common.
On your bench you want the block's accessory print, the bar's part number written on the order, a screwdriver to suit the clamps, a meter for continuity and millivolt drops, and labels for the group. UL 508A is the standard for listing an industrial control panel, and a build whose every accessory traces to its block's print reads cleanly at inspection. If the panel's terminal count is still open, how many terminal blocks you need: counting points, not blocks settles it before you buy bars.
Fitting a commoned group, step by step
Where the strip sits on the plate and how much duct it gets is the backplate and DIN rail layout guide's subject; this page stays at the strip itself. Work the group in this order:
- Isolate every source that can reach the strip and prove absence of voltage at the blocks, including a second supply that can backfeed through a bar the moment it seats.
- Read the block's part marking, open its accessory list, and order the bar it names — for this class, the 2-pole bar in the same rating class as the block.
- Mark which terminals share the potential and which neighbours stay separate; bars overlap across a gap if you let them.
- Add up the simultaneous loads each bar will carry, remembering that the bar nearest the feed carries the sum of the loads beyond it.
- Seat the bars in alternating channels — first link upper, second link lower — so each middle block holds one bar per channel, and check that every bar foot bottoms in its well.
- Land one conductor per clamp and label the group; two wires on one terminal is its own subject, and the clamp is a one-conductor place.
- Record the common on the schematic, then prove it dead: every block of the group one node, no continuity into the next group.
Where neighbouring rows crowd the strip, terminal block row spacing and finger duct clearance sets the gaps that keep your fingers and the duct clear of the bars.
Sizing the bars on a five-terminal 28 A common
The case: five blocks of that 32 A class, the feed conductor on terminal 5, loads on terminals 1 to 4. The bar ratings come from the datasheet values above — the block's nominal figure and its listed 2-pole bar of the same rating. The load currents are this example's inputs, a typical control-panel load list: 2 A on terminal 1, 8 A on terminal 2, 12 A on terminal 3 and 6 A on terminal 4, for 28 A simultaneous.
The rule in words: with one feed at one end, each bar carries the sum of the loads on the far side of it.
| Bar | Loads beyond it | Current |
|---|---|---|
| Terminal 5 to 4 | T4 | 6 A |
| Terminal 4 to 3 | T4 + T3 | 6 + 12 = 18 A |
| Terminal 3 to 2 | T4 + T3 + T2 | 6 + 12 + 8 = 26 A |
| Terminal 2 to 1 | T4 + T3 + T2 + T1 | 6 + 12 + 8 + 2 = 28 A |
The feed block itself carries the full 28 A. The heaviest bar sits at 28 A against its 32 A rating, a 4 A margin (12.5 %), and the feed block sits at 28 A against the block's nominal. Build it as drawn, and set the feed protection at 30 A so nothing downstream ever relies on that margin.
The decision this leads to: hold every bar segment at or below the bar's rating, and the feed block at or below its nominal. Grow the load list to 36 A and the bar nearest the feed is the first thing over the line — land the feed on the middle block instead. With the feed on terminal 3, the bars to its left carry 2 A and 10 A, the bar to its right carries 6 A, and the heaviest segment falls from 28 A to 10 A while the feed block still carries 28 A. When the total itself passes the block's nominal figure through one block, split the common into two groups with two feed conductors.
Proving the group before you load it
- With the group dead, confirm one node across all five blocks and separation from the next group; landed loads can give your meter a parallel path, so read both measurements with that in mind.
- Under the real load, measure the millivolt drop across each bridged joint and compare like with like: a joint reading more than double its identical twin is your seating fault.
- Scan the strip thermally after the first loaded hour. A joint about 10 C above an identical loaded neighbour flags the same fault by heat.
- A bad joint spends its heat inside the box. In one of our stainless junction boxes the wall passes about 3.7 W per square metre per kelvin to ambient, this site's reference value for stainless, so the wasted watts from one contact stay local and the scan is what finds them.
Mistakes that cost the group
- The look-alike bar. It seats, it bridges, it has the wrong contact geometry. Order from the accessory list and put the part number on the order.
- Reading double into two bars. The pair shares unevenly, and the hotter bar heats with the square of its current: a 40 % overload puts about twice the heat into a joint, because 1.4 squared is 1.96. Move to a bigger block family or a second feed conductor instead.
- Reading the block's 41 A as the group limit. The bar governs, and the bar is the part whose work you cannot see.
- Commoning two circuits by accident. Bars overlap across a gap; trace the potentials on the drawing before you seat anything.
- Leaving the common off the drawing. Mark the group on the schematic — when to use terminal blocks in a panel and what goes on the schematic shows where it belongs.
- Forgetting the fault path. A short on a load at the far end pulls its fault current through every bar back to the feed; terminal block SCCR in a control panel covers what sets that number.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 6 × 6 × 4 in | 304 stainless | 6 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 8 × 6 × 4 in | 304 stainless | 8 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 10 × 8 × 4 in | 304 stainless | 10 x 8 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Does a jumper in both slots double the current a commoned group can carry?
No. The two slots exist so 2-pole bars can overlap on a middle block and chain three or more blocks into one common. The ceiling stays the single bar's rating: 32 A on the documented 2-pole accessory for the 32 A block class. Two bars across the same two blocks share unevenly because their contact resistances differ, and no terminal maker rates the pair at double.
How much current can a bridged terminal group carry?
The lowest-rated part in the path sets it. On a block rated 32 A nominal with a 41 A maximum load current, the listed 2-pole bar matches the block's nominal rating, so hold every bar segment at or below that figure. The bar nearest the feed carries the sum of the loads beyond it — on a 28 A load list, that bar sees the full 28 A.
Can I common protective earth terminals with jumper bars?
Use PE blocks for protective earth: they bond to the DIN rail through their metal foot, which is what that terminal type is built for. Size whatever carries the earth path from the rating of the overcurrent device ahead of it, per NEC Table 250.122, and keep neutral current off the metalwork so the rail stays at ground potential.
How warm is too warm for a jumper bar in service?
Compare like with like. A bar joint about 10 C above an identical loaded neighbour on a thermal scan, or a millivolt drop more than double its twin's, marks a seating fault or a wrong bar. Isolate, reseat or replace with the listed part, and repeat the loaded check before you call it fixed.