Cable grips in conduit: when a metallic grip needs to be nonmagnetic

Short answer: a metallic grip around every conductor of one circuit is safe because the fields cancel; a ferromagnetic steel grip around a single conductor carries that conductor's full field and heats, worst case by tens of degrees on a 200 A feeder. Order bronze or 300-series stainless mesh grips for single-conductor runs, and bond the metallic conduit as one continuous path per NEC 250.96(A).

NEMA4 Enclosure engineering team · Published November 13, 2026 · 8 min read

Short answer: conductivity was never the problem — magnetism is. A metallic cable grip that passes every conductor of one circuit runs cool, because the fields cancel. A ferromagnetic steel grip around a single conductor carries that conductor's full alternating field, heats by induction, and bakes the insulation at one spot. On a single-conductor medium-voltage run, order bronze or 300-series stainless mesh, keep every fitting around the conductor nonmagnetic, and bond the metallic conduit as one continuous path, with a ground connection at least every 100 ft [30 m] as the working rule of thumb.

When does a metallic cable grip need to be nonmagnetic?

You need a nonmagnetic grip whenever the mesh surrounds fewer conductors than the circuit carries: one conductor per conduit, the standard medium-voltage layout, pushes that conductor's whole magnetic field through the grip, and ferromagnetic steel converts the field into heat.

Group the circuit and the metal is innocent. Send all phases and the neutral through one grip and their instantaneous currents sum to about zero, so the mesh sits in almost no flux; steel, bronze or stainless all behave. That is the same cancellation that keeps grouped conductors cool running parallel conductors through a steel enclosure. One conductor per conduit destroys the cancellation: each conduit and each grip sees a net current, and every ferrous part around that conductor works the field — the grip is simply the piece touching the insulation.

What the grip surrounds Order this Why
All conductors of one circuit, phases plus neutral Any metallic mesh, steel included Fields cancel; almost no flux in the weave
One conductor of a circuit, one per conduit Bronze or 300-series stainless mesh Full field in the weave; ferromagnetic steel heats
Parallel sets, one sub-conductor per conduit Bronze or 300-series stainless mesh Each conduit still carries a net phase current
A jacket group with no net current Match the material to the circuit it feeds Confirm the grouping before you trust steel

The conduit itself shares the problem, which is why single-conductor medium-voltage runs are commonly specified in aluminum or nonmetallic conduit rather than steel. The grip is the shortest ferrous sleeve on the cable; the conduit is the longest one.

Why does a ferromagnetic grip overheat around one conductor?

The alternating field of a single conductor circulates through the mesh as flux; a ferromagnetic weave concentrates it and dissipates hysteresis and eddy losses that grow with the square of the current, so a 300 A feeder heats a steel grip nine times harder than a 100 A one.

Inside the weave, two losses burn: hysteresis, the work of reversing the magnetization 120 times a second on a 60 Hz supply, and eddy currents circulating in the mesh wires themselves. Both fall steeply with current — a loss that follows the square of current drops to a quarter at half load. A bench induction heater drives steel past 800 °C [1472 °F] in seconds, the same physics at a far stronger field than a feeder grip sees, so the failure at 60 Hz is a slow cook, not a fast burn. The grip is short, so it builds almost no induced voltage even at fault current: a heat problem, not a shock or shielding problem.

Worked example (illustrative inputs: replace the temperature rise with your own infrared scan or the maker's test data). A 15 kV feeder carries 200 A per phase, one conductor per conduit, with a galvanized steel grip at the top of each riser. Say the grip runs 25 °C [45 °F] above ambient at that load. At 100 A the same grip runs 25 × (100/200)² = 6 °C [11 °F] above ambient. At full load, the insulation surface at the grip sits near 90 + 25 = 115 °C [239 °F], against a 90 °C [194 °F] normal-duty rating for XLPE. Insulation life roughly halves for every 10 K of sustained extra heat, so a 25 K hotspot shortens local life by 2^(25/10) ≈ 5.7 — that spot ages about six times faster than the run beside it.

What grip material do you order for a single-conductor run?

Order bronze or 300-series austenitic stainless mesh: both are nonmagnetic, both are standard grip constructions, and a pocket magnet settles the question in seconds because it sticks to steel and 400-series stainless but not to bronze, 304 or 316L.

Bronze is the traditional pick, and it earns the place the way it earns it on valves: the service — here, a nonmagnetic path around a live conductor — selects the material, not the price (bronze material selection by service). Stainless works when it is the right family: 300-series austenitic grades such as 304 and 316L are essentially nonmagnetic, while 400-series grades behave like carbon steel, and heavy cold work adds a little magnetism even to 300-series. A polymer weave is a valid order too; what decides is the rated holding strength and jacket compatibility, not conductivity.

Read the maker's sheet for three values: cable outside-diameter range, rated holding strength, and installation method. A strain-relief grip spreads pull along the braid; a support grip adds a rated holding value for a cable that hangs. The cable gland vs cord grip terminology page covers how US specifications name these parts.

How do you install a support grip on a vertical run?

De-energize first, then fit the grip so the weave bears evenly over its full braid length on clean jacket, with the hang weight inside the maker's rated holding strength: 100 ft [30 m] of 15 kV, 500 kcmil copper hangs about 150 to 200 lb [70 to 90 kg].

  1. De-energize the feeder, lock it out, and confirm absence of voltage before any jacket or mesh is handled.
  2. Walk the route and record what passes each part: which conduit carries which conductor, where each riser starts, and where every grip will sit.
  3. Magnet-test each grip on the bench. Anything that sticks stays out of a single-conductor run, whatever the label says.
  4. Match the grip's cable outside-diameter range to the jacket, and read its rated holding strength from the maker's sheet rather than the braid's looks.
  5. Size the hang: height times weight per foot. The 100 ft [30 m] drop above puts roughly 150 to 200 lb [70 to 90 kg] on the top grip plus its attachment, before any installation pull.
  6. Slide the mesh over the jacket and seat it over its full braid length, square and untwisted, with the maker's wedge or clamp capturing the mesh end.
  7. Terminate each conduit end with a grounding bushing or a listed hub, and bond across every joint of the run.
  8. Record the grip model, material, position and magnet-test result with the as-built notes, so the next crew never has to re-derive the material choice.

How do you bond and ground the conduit itself?

Bond the raceway as one continuous conductor path: NEC 250.96(A) requires metal raceways to be bonded so they can safely carry any fault current likely to be imposed on them, and MV practice adds a ground connection at least every 100 ft [30 m] as a rule of thumb.

The grounding design of the job sets the exact interval; the rule of thumb puts a ground connection at both ends of the run and at least every 100 ft [30 m] between them. Each end takes a grounding bushing or a listed conduit hub; where threads, coatings or joints break continuity, fit a bonding jumper, and NEC 250.12 requires paint, lacquer and enamel removed from the contact surfaces that carry grounding.

Rigid metal conduit can itself serve as the equipment grounding conductor — rigid conduit as a grounding conductor with NEMA 4X boxes and metal conduit as an equipment ground between metering points cover that role, and the grounding and bonding guide carries the fundamentals. NEC 250.4(A)(5) names the required fault path the effective ground-fault current path and keeps the earth out of it: the metal path carries the fault, the earth carries none of it.

What checks prove the run before you energize it?

Three readings settle it: continuity from each conduit end back to the ground bus, an infrared scan one hour into full load, and a recorded magnet test on every grip — any point more than 10 °C [18 °F] above its neighbours marks a ferromagnetic part worth replacing.

Measure continuity with a low-resistance ohmmeter: a sound threaded joint adds only a few milliohms, so a high reading points at paint, corrosion or a loose bushing. Run the feeder at full load for an hour, then scan: every grip and fitting should sit within a few degrees of the cable beside it, and the 10 °C [18 °F] neighbour rule is the thermography triage flag for a ferromagnetic part. Look at the seating too: mesh flat on the jacket, no twist, no cut strands. Replace a hot ferromagnetic part rather than re-torquing it, because the heat follows the material, not the tension.

Which mistakes cost the cable or the rating?

The expensive ones are a steel mesh around a single conductor, a 400-series stainless grip bought because the label said stainless only, a strain-relief grip carrying a hang it was never rated to hold, and a single conductor passing through a ferrous plate without breaking the magnetic path around it.

  • A steel mesh carried over from a grouped-circuit job onto a single-conductor run: the hotspot shows up months later as a discoloured jacket at the grip.
  • A 400-series stainless mesh ordered on the label alone; the magnet test costs seconds and closes that door.
  • A strain-relief grip asked to hold a hang that only a rated support grip should carry.
  • A single conductor through a ferrous plate or wall at feeder currents: break the magnetic path around the opening with a slit or a nonmagnetic spacer.
  • A ground rod driven beside the run and treated as the fault path: NEC 250.54 makes it an auxiliary electrode that may be connected to the equipment grounding conductor, and the conductor still carries the path.

The same rule reaches the box around the run. Our stainless steel junction boxes are 304 or 316L — austenitic, essentially nonmagnetic — so the wall around a gland never adds a ferromagnetic path to the conductors entering. They are rated NEMA 4X / IP66 by the manufacturer; not UL listed. They serve low-voltage splices, terminal blocks and pull points; medium-voltage terminations belong on equipment designed for the voltage. They are cut to your drawing and delivered in 10 business days.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
12 × 10 × 6 in304 stainless12 x 10 x 6 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
16 × 14 × 8 in304 stainless16 x 14 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
20 × 16 × 8 in304 stainless20 x 16 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
16 × 12 × 8 in304 stainless16 x 12 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Does a stainless steel cable grip count as nonmagnetic?

Only when the weave is 300-series austenitic stainless, the family that covers 304 and 316L. 400-series stainless is magnetic and heats around a single conductor just as carbon steel does, and heavy cold work can add a little magnetism to 300-series. A pocket magnet settles it in seconds; record what the magnet showed and which mesh you installed.

Why does the same steel grip stay cool on a three-phase bundle?

The three phase currents sit 120 degrees apart and sum to about zero at every instant, so the net flux through the weave nearly vanishes. Loss grows with the square of the current, so the cancellation that saves a bundle at 100 A is worth nine times more at 300 A: steel stays cool only while the sum stays near zero.

Can a mesh grip double as a shield or a fault path?

It can do neither job. A short grip develops negligible induced voltage even at fault current, and it carries no rated fault-clearing role; the bonding job belongs to the conduit, terminated with grounding bushings or listed hubs at each end. NEC 250.4(A)(5) calls the required fault path the effective ground-fault current path and leaves the earth out of it.

How much weight can a grip carry on a vertical run?

Whatever the maker's rated holding strength says for that mesh size and jacket diameter; take it from the datasheet rather than the braid's appearance. For scale, 100 ft [30 m] of 15 kV, 500 kcmil copper single-conductor cable weighs roughly 150 to 200 lb [70 to 90 kg], and the top grip carries that plus any installation pull.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Build it from 12 × 10 × 6 inRequest a custom quote

Check the heat load in the calculator · NEMA 4X enclosures: sizes for this job

Keep reading

More on layout and installation

All articles

Buying guides

The guides behind this answer

All guides