Short answer: the zone does not decide the bonding — the shutdown state does. Anything the UPS keeps energized after the emergency shutdown, PA loudspeakers included, must meet at least the zone 2 rules, construction and bonding both, under IEC 61892-1:2019, the electrical standard for offshore units. The bonding detail lives in IEC 60079-14:2013, which lets a gland that clamps the cable's screen or armour act as the equipotential connection on a metal enclosure. Your remediation per item is three questions: does it stay live through the trip, does its certificate reach zone 2, and does the meter confirm the gland is actually gripping.
Why shutdown, not zone, decides the bonding
Zones 0, 1 and 2 you already bond. The unclassified area is where the sorting happens, and the sort runs on shutdown state. The emergency trip exists to strip the plant of ignition sources during a release, and a UPS-fed loudspeaker with a nicked cable or a loose gland is the one item still able to spark at exactly that moment. That is why shutdown-live gear gets its own category. IEC 61892-1:2019 draws the line: equipment that stays energized after emergency shutdown meets at least the zone 2 rules.
Two documents sort every item: the shutdown cause-and-effect chart and the single-line diagram. Where the trip drops the UPS feed, the item is ordinary unclassified equipment and follows general equipotential practice — the route the grounding and bonding guide walks through for the NEC side. Where the feed stays made, the item goes on the zone 2 list in the checklist below. The opposite case, certified gear sitting outside any zone, is covered in using a Class I Div 1 enclosure in an unclassified area.
What IEC 60079-14 gives you
IEC 60079-14 is the design standard for electrical installations in explosive atmospheres. Its scope names earthing, equipotential bonding and the prevention of electrostatic charge build-up among its jobs. Its equipotential-bonding requirements are the ones your finding sheet cites, and they contain the sentence that shortens the job. A cable gland with strain relief that clamps the screen or armour of the cable can serve as the equipotential connection. The conditions are physical, not paperwork. The housing must be metal, or plastic fitted with an earthing plate or equivalent bonding point, and the entry must be the type the equipment certificate names.
So on an Ex d loudspeaker with an armour-compression gland tightened into a metal housing, the gland is the bond — measure it and move on. The structure-scale side of the same standard is its own discipline, laid out in offshore metallic structure equipotential bonding under IEC 60079-14. Dust-zoned parts of the plant follow different entry rules again; zone 22 junction box wiring covers that side.
The checklist: sort, check, measure
Work the three groups in order. Every item in the unclassified area lands on exactly one path through them.
Sort by shutdown state
- Read the cause-and-effect chart and the single-line diagram for each item.
- Feed drops with the trip: ordinary equipment. Bond it to plant practice. On the NEC side, the equipment grounding conductor is sized from the overcurrent device ahead of it; 12 AWG copper covers a 20 A circuit (Table 250.122).
- Feed stays made: a zone 2 item — next group.
Zone 2 checks on live items
- The certificate and marking reach zone 2 (EPL Gc or better).
- The housing is metal, or plastic with an earthing plate.
- The entry is the certified type, the gland clamps screen or armour, and the metal at the entry is clean.
- An item with no zone-2-suitable certificate needs replacement or the call of the person responsible for explosion safety on your site. A copper strap never upgrades a certificate.
Read the gland, then the meter
| What you find | What it means | What you do |
|---|---|---|
| Armour or screen under the gland cone, entry clean and tight | The gland is the equipotential bond | Measure, record, close |
| Armour cut back, gland gripping only the sheath | No bond through the cable | External bond now, re-termination booked |
| Plastic housing with no earthing plate | The gland cannot bond the housing | Bonded housing or certified bonding point |
| Paint or corrosion at a metal entry | Contact is unreliable | Clean, re-seat, measure again |
One safety line before the meter: isolate the item and apply your lockout, because the UPS-fed circuits you are sorting are precisely the ones that stay live. Then measure from the housing to structural steel or the equipotential bar with a low-resistance ohmmeter. Compare the reading against a value you can calculate yourself (next section), and record the reading, the gland type and the housing material.
Proving the bond on a 60 m UPS-fed loudspeaker circuit
The case: one passageway loudspeaker fed from the UPS board, 60 m of cable away. The cause-and-effect chart shows its feed stays made at shutdown, so the zone 2 minimum of IEC 61892-1:2019 applies to it. The housing is metal and the gland is the certified armour type. The original installer cut the armour back, though. The cone grips only sheath, so as a bond that gland fails the equipotential rule of IEC 60079-14. Today's fix is a 16 mm² copper bond conductor on the same 60 m route, lugged at the speaker's bonding boss and at the bar.
The arithmetic anchor is the conductor. IEC 60228, the conductor standard, caps 16 mm² annealed copper at 1.15 Ω/km at 20 C, and copper resistance moves about 0.39 % per kelvin.
The rule in words: expected reading equals 1.15 Ω/km times the route in kilometres, adjusted 0.39 % per kelvin away from 20 C.
- Route: 60 m = 0.060 km
- At 20 C: 1.15 × 0.060 = 0.069 Ω
- In a 5 C passageway: 0.069 × (1 − 0.0039 × 15) = 0.069 × 0.9415 ≈ 0.065 Ω
A healthy run reads 0.065–0.07 Ω plus whatever the two lugs add, which is small next to the conductor. On this route, close the finding below 0.1 Ω. A meter showing whole ohms, or a value that drifts when you flex the cable, is a joint that is not making contact — fix the joint and measure again. The rule scales with the route: the same conductor over 120 m should read 1.15 × 0.120 = 0.138 Ω.
When the re-termination is done and the strap comes off, measure again through the armour. A steady reading in the tenths of an ohm over tens of metres is a healthy armour path; drift or an open circuit says the cone is still not biting.
Strap today, re-terminate after
Split the repair the way the equipment register needs it. Temporary: an external bond conductor, lugged at the housing's bonding point and at the bar, tagged and dated for follow-up, so the item runs while you book the re-termination. Permanent: re-terminate the armour so the gland cone clamps it, replace any plastic housing that lacks an earthing plate, and record the bonding method against the item.
Then prove the repair. Repeat the reading after the re-termination and write it beside the first one, check that the marking and entry components still match the certificate, and re-inspect at the interval your inspection plan sets. Treat the strap as a bridge: left beside a failed clamp it hides the finding, because the loose armour can still float and discharge on its own.
Where a stock enclosure fits, and where it does not
Keep the boundary plain. We build stainless enclosures for ordinary locations, rated NEMA 4X / IP66 by the manufacturer and not UL listed, and we do not build hazardous-location enclosures — NEMA 7, 8 or 9 types, explosion-proof or Ex certified. A shutdown-live item's housing arrives as part of the certified equipment, with entries and bonding points inside that approval. That duty is not a box you bolt on afterwards.
Our boxes earn their place on the dead-at-shutdown side of your list: the junction and pull boxes carrying PA and UPS wiring through unclassified passageways, the isolator enclosures that drop with the trip. Offshore, order 316L for the salt air; sheltered indoor runs can take 304. Those boxes still need their bonding done properly — an earth boss on the backplate and a gland plate that carries the bond, since earth continuity through a gasketed gland plate is what keeps the plate in the path. The NEMA 4X wall-mount range and the stainless junction boxes cover the standard shapes.
What to put on the order
Send this with the quote request for the ordinary-location boxes:
- Material and environment: 316L offshore or anywhere salt and chlorides reach, 304 for indoor passageways.
- Width, height and depth, with room for the terminations plus spare.
- Gland plate position and the cutout list from the cable schedule; gland plates for conduit-fed junction boxes walk that case.
- Bonding hardware: earth bosses or studs, and bare-metal contact faces — NEC 250.12 wants paint, lacquer and enamel off the threads and contact surfaces at grounding connections.
- Door furniture, latches and any window an HMI needs.
Sizes and cutouts you cannot find in the standard shapes go through the custom enclosure builder. Delivery is 10 business days from your order, anywhere in the world; for custom work, from your approval of the drawing.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 14 × 8 in | 304 stainless | 16 x 14 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Does an armour-clamping gland replace the external bonding conductor on Ex d equipment?
Yes, where the gland's cone clamps the screen or armour and the housing is metal, or plastic with an earthing plate: IEC 60079-14:2013 lets that gland serve as the equipotential connection. A gland gripping only the outer sheath gives strain relief and no bond. Prove it with a low-resistance reading, because paint or corrosion at the entry can break the metal-to-metal path the rule depends on.
Do you have to bond equipment in an unclassified area?
Only the items that stay energized after emergency shutdown. Those carry a zone 2 minimum under IEC 61892-1:2019, with bonding to IEC 60079-14:2013. Equipment that dies with the trip is ordinary gear: bond it to plant practice, which on the NEC side means an equipment grounding conductor sized from the overcurrent device ahead of it, 12 AWG copper for a 20 A circuit, per Table 250.122.
Does a UPS-fed PA loudspeaker count as energized after shutdown?
Yes, whenever the emergency trip drops the mains feed while the UPS keeps its output made. Two documents settle it item by item: the shutdown cause-and-effect chart and the single-line diagram. If the chart shows the UPS feeder tripping with everything else, that loudspeaker is ordinary unclassified equipment and the zone 2 rules never engage.
Can shutdown-live equipment stay in a plastic enclosure?
Only with an earthing plate or an equivalent certified bonding point in the housing. Without one there is no metal-to-metal path from the gland into the enclosure, so the clamping gland cannot act as the equipotential connection and the installation fails the IEC 60079-14 check however clean the cable looks. On metal housings, paint on the entry threads shows up as a high reading on the meter.