Yes — you wire it with two enable contacts in series with the solenoid commands, one per bank, plus a third contact on the pump motor: three single-pole blocks on one maintained three position selector. Center enables neither valve bank, left enables bank 1 and right enables bank 2, and each bank's enable contact sits in series with that bank's up and down solenoid commands, so the joystick can only reach one bank at a time. The motor permissive goes in series with the shared pump motor's command, so the pump cannot run dead-headed in neutral. Each enable contact carries 1.04 A at 24 V DC against a 10 A rating. Before any of it sees power, measure every contact in all three physical positions — nine readings with a meter — because a block drawn N.C. can behave N.O. once the cam drives it.
What should each selector position do?
Center is neutral with both valve banks off, left enables bank 1 only, right enables bank 2 only, and the same joystick keeps commanding up or down for whichever bank is live.
The selector answers "which machine"; the joystick answers "which direction". Keep those two jobs on two devices and the wiring on your backplate stays readable for the next person. A maintained selector also stays where you set it, which is what makes it a bank selector rather than a jog control.
| Selector position | Bank 1 enable | Bank 2 enable | Motor permissive | Result |
|---|---|---|---|---|
| Center (neutral) | Open | Open | Open | No solenoid can energize; pump held off |
| Left (bank 1) | Closed | Open | Closed | Joystick drives bank 1 up and down |
| Right (bank 2) | Open | Closed | Closed | Joystick drives bank 2 up and down |
During the turn from left to right you want one enable open before the other closes: break-before-make, which is the standard cam on a maintained selector. Overlap cams exist for make-before-break duties; one industrial line documents its KH4 cam for exactly that. An exclusive interlock wants the opposite, the standard break-before-make cam, so the two banks never share a command even mid-turn.
How many contact blocks do you need on the selector?
Three single-pole blocks: one enable contact per bank, plus the motor permissive that stops the pump in neutral — a stack a 30 mm selector carries with room to spare.
A block marked A600 is rated 10 A at 600 V AC, an order of magnitude above a hydraulic solenoid command. The one spec to read before ordering is the DC rating: some special contacts, late-break N.C. blocks for example, carry no DC rating at all in their maker's tables, and 24 V DC coils need a block that has one. When a block meters correctly on the bench but stops actuating once the door closes, the usual culprit is the coupling piece between operator and block, and the coupling piece failure guide walks that check.
How do you wire the selector into the solenoid commands?
Run the joystick's up command through both enable contacts, one per bank, and land it on each bank's up coil; do the same with down, so the selector picks the machine and the joystick picks the direction.
- Open the disconnect, lock it, and check that the 24 V DC solenoid branch and the motor branch read dead before you land a wire.
- Tag the three blocks on the door: bank 1 enable (the 1-2 terminals on your drawing), bank 2 enable (3-4), and the motor permissive.
- Meter each contact in all three positions and record the nine readings against the table above before anything is wired.
- Wire joystick UP through the bank 1 enable to bank 1's up coil, and through the bank 2 enable to bank 2's up coil; repeat for DOWN.
- Fit the coil suppression the valve maker supplies, wired at the coil terminals.
- Run the command wires in duct on 1.5 mm² [16 AWG] wire, ample for a 1 A command circuit. Keep the fill at 50% of the duct's cross-section: that is the limit one duct maker's fill tables set citing NFPA 79-2012 section 13.5.2, and the air gaps between round cables mean 50% is all a duct really holds.
- Land the door-side wires on terminal blocks and take the backplate jumpers from there, the way door-mounted controls are wired to terminal blocks rather than flown across the hinge.
Worked example, the arithmetic that sizes the contacts: each bank has an up and a down coil, 24 V DC at 25 W each. Current per coil is I = P / V = 25 W / 24 V = 1.04 A. The joystick commands one direction at a time, so each enable contact carries one coil, 1.04 A, against its 10 A A600 rating — a margin of about 9.6 to 1. Even a fault that commanded up and down together still puts only 1.04 A through each contact, because the two coils are parallel branches that split the current.
Why does the 1-2 block read differently than the drawing shows?
Because N.O. and N.C. name the contact before it mounts on the cam: once a two-plunger mechanism drives that block, it can sit open in neutral and close only at its end of the throw.
A hand-off-auto selector is this exact device wearing different labels. One maker's C-cam three position switch closes a contact at the left, another at the right, and neither in the middle, using two blocks marked the same way. Cam selection guides say it in print: check the contact configuration and the block mounting positions before wiring, because the designations describe the contact off the mechanism. So the 1-2 contact drawn N.C. can genuinely need an N.O. block in your switch, and the meter is the fact the drawing only claims.
| Block | Center | Left | Right |
|---|---|---|---|
| Bank 1 enable | Open | Closed | Open |
| Bank 2 enable | Open | Open | Closed |
| Motor permissive | Open | Closed | Closed |
When the meter agrees with all nine cells, wire it. When a cell disagrees, swap that block for the opposite designation and meter again.
How do you keep the shared pump from dead-heading?
Break the motor's command with the third selector contact so the pump only runs with a bank selected: in neutral the command path opens, and the dead-head question disappears with it.
Without that contact, neutral plus a joystick command means real heat. The pump delivers into blocked ports and all flow crosses the relief valve. At 10 US gpm against a 1,500 psi relief setting, the power is (10 × 1,500) / 1,714 = 8.7 hp, about 6.5 kW, and all of it lands in the oil as heat. In a 40 US gal [150 L] reservoir that is roughly 1.7 °C [3 °F] per minute with no cooling, a short road to cooked oil and a hot box.
If your selector line offers no single contact that closes at both ends of the throw, parallel the spare poles of the two enable blocks for the motor permissive: either one closed lets the motor run, and both open in neutral stop it. Put that permissive in the starter's control circuit, where two wire and three wire motor control shows the seal-in path it belongs in. The motor's power feed still leaves the enclosure on its own conductors; bonding the enclosure to the motor casing covers when that wire is needed, and NEC 312.6 sets the bending space those feed conductors need at the starter terminals.
What tests prove the finished interlock?
Six function tests, one for each combination of three selector positions and two joystick directions, and in every active row exactly one solenoid may pick; in the two neutral rows, none.
- Power on, selector centered: command UP, then DOWN. No solenoid picks, and the motor command reads dead at the starter coil.
- Selector left: UP picks bank 1's up coil only; DOWN picks bank 1's down coil only.
- Selector right: the same two tests on bank 2's coils.
- Turn slowly from left to right with a meter across both enable contacts; the two are never closed at the same instant, and that is your break-before-make proof.
Label the three positions where the operator sees them, and carry the same tags onto the terminal blocks inside the door.
Where does the selector mount, and how do its wires reach the panel?
Through a 22.5 mm [0.89 in] door hole for a 22 mm operator or a 30.5 mm [1.20 in] hole for a 30 mm one, with the contact stack inside the enclosure and every door wire landed on terminal blocks.
Have the hole cut when the box is built rather than in the field: on a washdown door a factory cutout seals better, and the cutout, gland and window guide shows what to put on the drawing. Picking the selector family and laying out its holes is the same job as choosing a seven position selector and cutting the panel, one family of 22 mm or 30 mm devices at a time. In a washdown plant that door is 304 stainless rated NEMA 4X / IP66 by the manufacturer and not UL listed, and the custom stainless cutout options put the selector, joystick and E-stop holes on the build drawing in one pass.
Count your terminal points before the plate is drilled: four coils at two points each, plus the joystick outputs and the motor permissive, and counting points rather than blocks gets you the rail length. Space the duct and DIN rail to the clearances in the backplate layout guide so the solenoid bundles and the motor feed keep their own lanes up the panel.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can one selector switch control two hydraulic valve banks exclusively?
Yes. A maintained three position selector gives you neutral with both banks off, one active position per bank, and two enable contacts wired in series with each bank's up and down solenoid commands. With the motor permissive added, the whole interlock lives on three contact blocks.
Should the 1-2 contact block be normally open or normally closed?
Whichever your meter says. The N.O. and N.C. designations describe a contact before the block mounts on the cam, and on a two-plunger three position mechanism a block labelled N.C. can read open in neutral. Nine readings, three contacts in three positions, settle it before power.
How hot does a dead-headed hydraulic pump get?
Fast enough to matter. 10 US gpm pushed across a 1,500 psi relief valve is (10 × 1,500) / 1,714 = 8.7 hp, about 6.5 kW, and all of it becomes heat in the oil. In a 40 US gal [150 L] reservoir that is roughly 1.7 °C [3 °F] per minute, which is why the motor permissive earns its contact block.
Do the valve solenoids need suppression diodes?
On 24 V DC coils, yes. An unsuppressed coil throws a spike of several hundred volts when the enable contact opens, and the arc pits that contact until the interlock turns intermittent. A suppression diode or TVS wired straight at the coil lugs stops the spike at its source.