Short answer: the pressure switch wants the constant connection. Program the drive input for two-wire control and land the switch as a maintained contact: closed, the drive runs; open, it stops, on 2 conductors. Three terminals on the drawing mean three-wire pulse logic — a momentary start and a held stop — and a pressure switch wired there starts the drive and then never stops it. The forward/stop label on the terminal block names a two-wire level mode, but the manual's input-function parameter is what decides. This walkthrough covers the wiring and the programming, the sealed cable entry into a stainless enclosure, and a worked heat check that assumes a 60 W drive loss in a 30 C shop; replace both figures with your own before you order or cut anything.
What the forward/stop terminals expect
A pressure switch is a maintained contact. It sits closed below the cut-in pressure, opens at cut-out, and holds each state until pressure moves it back. That is a level signal, and two-wire control is built for it: input made means run, input dropped means stop, for as long as the switch holds. Motor-starter wiring diagrams treat pressure and float switches exactly this way, as two-wire control devices.
Three-wire control splits the command in two. A normally closed stop input sits made and opens to stop; a normally open start input closes for a moment, and the drive latches the run. Drive manuals describe the pair as a momentary start signal and a maintained stop signal. That is pushbutton logic, and it needs the drive's internal latch to hold the run after the start contact drops out.
Terminal count is a clue, not proof. Two terminals in use point to a level input; three point to start, stop and common. Programmable inputs blur the picture, because one drive can map the same terminals as run/stop, forward/reverse or forward/stop, all as levels, or hand a single input pulse behavior. The label names the direction mapping; the input-function parameter names level or pulse. Read that parameter before you land a wire.
| Question | Two-wire (level) | Three-wire (pulse) |
|---|---|---|
| Run command | Closed runs, open stops, held either way | Start pulse latches the run; opening the held stop stops it |
| Contact the switch gives | One maintained contact | A NO start and a NC stop |
| Terminals at the drive | 2: input and common | 3: start, stop, common |
| After a power cut | Runs again while the contact stays closed | Waits for a fresh start pulse |
| Pressure switch wired as-is | Correct behavior | Starts, then never stops when the contact opens |
Some drives let one two-wire input act as a level or as a pulse; the walkthrough on configuring two-wire VFD control with a momentary start covers that setting. The held stop versus pulse start split is the same normally closed and normally open logic an enclosure thermostat uses, and that article lays out the contact choices.
What you need
- The drive manual's control-terminal and input-function pages, from the drive maker or your distributor; a secondhand drive with no manual still gets one first, and the walkthrough on sizing and sealing an undocumented drive's enclosure shows what you can safely guess beyond it
- Lockout tags and a multimeter
- 2-conductor shielded twisted pair in 18 AWG for the run command
- A cord grip or cable gland matched to that cable's outside diameter, plus blanking plugs for unused holes
- A step drill or hole punch and a deburring tool for the enclosure wall
Wiring the pressure switch in six steps
- De-energize and bleed. Lock and tag the feeder, meter the drive's line terminals dead, and wait out the DC-bus discharge time printed on the drive's warning label: the bus holds a charge that can kill long after the power is off. Bleed the compressor's stored air before you open its pressure switch.
- Strip the old switch wiring. Remove every conductor from the pressure switch and meter to confirm. The old circuit may have switched mains voltage at that switch, and mains voltage on a logic input wrecks the drive's input stage.
- Prove the contact's state. With the switch isolated from every circuit, meter the contact pair: closed below the cut-in pressure and open at cut-out, for a compressor holding a tank. Work the switch by hand and watch the meter swing both ways.
- Cut and seal the entry. Drill or punch the wall, deburr the edge, and close the hole with a cord grip matched to the cable's outside diameter; the cutouts, glands and windows guide gives the sizing and the hole preparation. Every penetration holds the rating: our stainless boxes are rated NEMA 4X / IP66 by the manufacturer, not UL listed, and one open hole drags the whole assembly down. Cap unused holes, or skip the drilling — the enclosure builder cuts the gland holes for you, and a custom build arrives in 10 business days from drawing approval.
- Run the two conductors. Land one on the run input and one on the input common, exactly as the manual's two-wire diagram shows. Land the cable shield at the drive end only, and route the pair away from the motor leads; the article on running 24 V control wire beside power wiring gives the separations to keep.
- Program the level. Set the command source to the terminals, set the input function to the two-wire run/stop or forward/stop level, then set the speed reference and the ramps. Set restart-after-power-loss deliberately: with a level input, the drive starts the moment power returns and the contact is still closed, which is what pressure control wants and worth saying out loud at handover. The VFD enclosure wiring checklist covers the stop, bond and filter items that sit around this wiring.
Worked example: heat rise in a 20 x 16 x 10 in stainless box at 30 C shop air
Two-wire control runs the drive unattended, and every run dumps heat into a sealed box that sheds it only through its walls. Run this check before the first cycle. The figures below are example values: the drive's rated power loss from its manual, your measured shop air and the datasheet's air limit replace them.
- Drive power loss: 60 W — example assumption; read the rated loss at your operating point from the drive's manual
- Warmest shop air: 30 C — example; measure beside the enclosure
- Air limit at the drive: 40 C (104 F), the figure drives are built for unless the datasheet allows more
- Box: 20 x 16 x 10 in [508 x 406 x 254 mm] stainless, wall-mounted with the back against the wall — example size
- Wall conductance: k = 3.7 W/m²K for stainless, the value this site's heat guides use
The rule in words: a sealed box sheds heat through its surface, so temperature rise equals heat load divided by wall conductance times exposed area. The arithmetic:
- Exposed wall, back excluded: front 0.508 x 0.406 = 0.206 m²; top 0.508 x 0.254 = 0.129 m²; bottom 0.406 x 0.254 = 0.103 m²; two sides 2 x 0.103 = 0.206 m²; total 0.64 m²
- Rise: 60 W ÷ (3.7 W/m²K x 0.64 m²) = 60 ÷ 2.37 = 25 C of rise [45 F]
- Air at the drive: 30 + 25 = 55 C, which is 15 C over the 40 C limit
The threshold falls out of the same equation: 3.7 x 0.64 x 10 = about 24 W. Under 24 W of loss, this sealed box holds the drive's air at 40 C in a 30 C shop; at 60 W it runs 15 C hot. Move the air or add wall. Fit a fan-and-filter kit the enclosure maker rates for the box's own type; a kit rated lower pulls the whole assembly down to its rating. A fan also brings its own wiring question, covered in the two-wire versus four-wire enclosure fans article. Or step the box up until the exposed wall doubles; the watts it sheds at the same rise double with it. The walkthrough on sizing a VFD enclosure from heat and clearance runs the full check with your drive's real numbers.
Checks when the switch cycles
- Input status. The drive's I/O or status screen shows the run input change state as the switch changes; the keypad keeps working separately until you switch the command source.
- One full pressure cycle. The contact closes at cut-in and the drive accelerates on its ramp; the contact opens at cut-out and the drive stops in its programmed stop mode.
- The stop stops. With the compressor unloaded and the drive running, open the switch by hand and watch the run request drop and the output ramp or coast down.
- Heat under load. After 30 minutes near full demand, the air next to the drive reads 40 C or less unless the datasheet allows more; the worked example above sets up this number. A drive that faults hot with the door closed has a heat story, and the article on drive faults with the enclosure door closed traces it.
- Seal tight. Gland nuts torqued, gasket seated evenly in its channel, blanking plugs in every unused hole.
Mistakes that cost the run command or the rating
- Level switch on a pulse input. The drive starts when the contact closes, latches, and keeps running when the contact opens — the compressor that will not stop. The fix is the two-wire level function, one parameter away.
- Wiring from the label. Forward/stop names a direction mapping; the input-function parameter names level or pulse. Terminal count helps, the parameter decides.
- Mains-voltage leftovers. Conductors from the old starter circuit put mains voltage where a dry contact belongs; strip the switch and start with fresh control cable.
- One hole, no gland. A field-cut hole left open or stuffed drops a Type 4X assembly to open-air duty; seal every penetration with a rated cord grip or cap it.
- Quiet restarts. A two-wire drive restarts when power returns with the contact closed, so a crew member expecting a dead panel meets a live compressor. Set the restart parameters and say so at handover.
- Shared bundles. The run pair bundled with motor leads picks up enough noise to ghost a command; keep the shield single-ended and the routes apart.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 20 × 16 × 10 in | 304 stainless | 20 x 16 x 10 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
What happens after a power cut with two-wire control?
The drive restarts by itself once power returns and the pressure switch is still closed, because a two-wire input is a level, not a pulse. That is the behavior pressure control wants, so set the drive's restart and fault-reset parameters to allow it and tell the crew the compressor starts the moment power comes back. A three-wire input does the opposite: it waits for a fresh start pulse.
How far can the pressure switch sit from the drive?
Voltage drop barely matters at logic levels. Standard copper conductor tables give 18 AWG about 6.4 Ω per 1000 ft, so a 100 ft run is a 200 ft loop at 1.28 Ω. For an input drawing 8 mA — an example figure; read your drive's spec — that is roughly 10 mV of drop, which no logic input notices. Shield integrity and a route away from the motor leads matter far more than length.
Does drilling a hole for the switch cable cost the enclosure its rating?
Not when the hole is deburred and closed with a cord grip or gland matched to the cable's outside diameter and rated for the same sealing level. Every penetration holds the assembly's rating together: one open or badly filled hole drags the whole box down to that part's level. Cap unused holes with rated blanking plugs and the box stays as ordered.
Can I add a manual stop switch beside the pressure switch?
Yes, and two-wire logic makes it simple: put a maintained toggle or selector in series with the pressure switch on the same two conductors. Both closed runs the drive; either one open stops it, because contacts in series combine as an AND. Leave momentary pushbuttons out of the series circuit — they cannot hold a level — or move to a three-wire input set with dedicated start and stop terminals.