Yes — a web based HMI panel exists as a standard product category, and it changes less at the machine than most buyers expect. It is an ordinary panel HMI with an HTML5 web server built in: the touchscreen keeps running at the cabinet, and any browser on the plant network opens the same screens as a second display endpoint. Plan on 0.5 to 1 s screen refresh for that browser view on a switched 100 Mbit/s link, and keep the control rights where they sit today, inside the HMI project's access levels. The enclosure barely notices: you add one glanded Ethernet entry, keep the sealing discipline you already had, and order the housing around the display as before.
Can an HMI panel be web based?
Yes: a web based HMI panel is an ordinary panel HMI with an HTML5 web server built in, so the touchscreen stays at the machine and any browser on the plant network opens the same screens as a second display.
Two architectures carry the label, and they are not interchangeable:
| Panel HMI with built-in web server | Server-hosted HMI | |
|---|---|---|
| Where the project lives | Inside the panel | On a central server |
| What the browser opens | The panel's own screens and tags | The server's application |
| Controller connection | One driver, at the panel | The server's drivers |
| Typical fit | One machine, a handful of viewers | Plant-wide dashboards, many clients |
A server-hosted system runs the HMI software on a central computer, and engineers open it through a browser, which is how plant-wide installations scale. For one machine with a few viewers, the panel version wins: no server to license, maintain or reboot, and the screen keeps working when the server room does not.
Web access is a property you select on the device, not a screen you add later to an ordinary panel. Confirm the browser view in the model's feature list before you buy, and the rest of the installation is ordinary panel work. Before you commit, it is worth a scan of the wider field of HTML5 HMI approaches, from pages served by the panel to full web platforms.
What does the web server inside the panel actually serve?
It serves the panel's own project, not a copy: the HMI tag database and screen graphics you configured once, published over HTTP or HTTPS so the browser renders a second view of the same application the local touchscreen runs.
It publishes the screens, tags, alarms and recipes of the project you already built, over the panel's own network address. The browser is a client of the panel, not a peer of the controller. It renders the page, sends your clicks back, and waits for the next refresh; every driver, tag address and script stays in the panel.
Three boundaries follow from that, and they settle most web-HMI arguments before they start:
- The browser holds nothing: no tag database, no driver, no history file.
- It sends back what the touchscreen would: the same screen presses and entries.
- It reaches the controller only through the panel; there is no second path to close off.
That division is your diagnostic map. Anything the browser shows wrongly is a rendering or binding question; anything both screens show wrongly is a data question at the driver or the controller.
How does controller data reach the browser?
Down one path: the controller value moves through the HMI's communication driver into its tag, the screen object binds to that tag, and the panel's web server pushes the result to the browser exactly as it draws it on the local display.
Walk the path once in your project and fault-finding turns into reading:
- The controller register changes.
- The panel's communication driver reads it into the HMI tag.
- The screen object bound to that tag picks up the new value.
- The panel's web server renders the page.
- The browser fetches the page over the plant network.
Each boundary fails in its own way, which is what makes the path useful:
| What you see | Where the break sits | What to touch |
|---|---|---|
| Local screen live, browser page fails to open | Network path or the panel's web service | Reachability and the panel's address, not the controller |
| Page opens, values frozen or wrong | The object-to-tag binding | Compare with the local screen and fix the binding |
| Local and browser both wrong | The driver or the controller tag | The shared data path, before you blame the browser |
A working local touchscreen is your test instrument. It proves the driver, the tags and the bindings in one glance, so commission the browser view only after the panel has run against live data.
How fast does a web based HMI panel update?
Plan on 0.5 to 1 s screen refresh for a browser view on a switched 100 Mbit/s link, because the update pace is set by the HMI's scan and tag-poll cycle, not by bandwidth: the example below uses about 0.03% of the link.
The panel's scan cycle sets the pace, and the network rarely enters the picture. Each loop reads the controller, updates the tags, redraws the local screen and serves the web page; the browser sees a new frame at the end of every loop. A 500 ms loop gives two updates per second, which reads as live to anyone standing at the line.
Work the arithmetic for a mixing line with a 30-object web screen. The page weighs 40 kB and each browser fetches it once at login; every refresh after that moves about 2 kB of changed values:
- Data per client: 2 kB × 2 refreshes/s = 4 kB/s, and 4 × 8 = 32 kbit/s.
- Share of one switched 100 Mbit/s port: 32 ÷ 100,000 = 0.032%.
- Ten viewers at once: 0.32% of the port, still rounding error.
Bandwidth does not decide the refresh rate; your scan and tag-poll settings do. Set the screen at 500 ms to 1 s as the baseline. Where a value must not sit stale — a filling weight, a temperature ramp — give that tag its own poll of 100 to 200 ms where the driver supports per-tag rates, and it outruns the screen cadence.
Heavy graphics are a client question, not a panel question. Published tests of 3D WebGL HMIs hold 60 frames/s with 500-800 simple solids, a frame budget of 1 s ÷ 60 = 16.7 ms. Panel HMIs keep screens flat and simple, so the 0.5 to 1 s cadence covers every value you can read at a glance.
Can a browser user start and stop the machine?
Only if the HMI project's access levels allow it: publish read-only screens for the browser and keep Start, Stop and reset objects behind a user level you never hand to a remote client; the control rights stay inside the panel project.
Rights live in the project, not in the browser. The web view presents the same screens, so the user level you assign decides which buttons render at all. Publish a read-only screen set for viewers and keep the write screens at the panel's levels. Where a remote setpoint change is genuinely needed, put that one object behind its own level and log it.
Prove commands with feedback, not with colours. During commissioning, issue one command at a safe point in the operating procedure and watch the controller's feedback bit arrive; a button that changes shade told you only that the browser sent a click. Then repeat the test from every network segment your viewers will use, because a success from the office network proves nothing about the line-side one. The view-versus-control split at the panel's Ethernet port works through that boundary in detail.
Does browser access change the enclosure?
Hardly: the HMI draws its numbers over the same machine network, so the enclosure change is one more glanded cable entry and nothing about the sealing logic — keep every entry as tightly sealed as the box itself.
The panel reads the same controller over the same cable it always did. Browser clients add load to the Ethernet port, not to the wiring. One cable in, one gland: a Cat 6 patch lead runs about 6 mm [0.24 in] outside diameter, which sits in the clamping range of a standard M20 gland, so one spare cutout position covers the change.
Keep the entry as tightly sealed as the box. The lowest-rated part sets the assembly rating: a gland or blanking plug rated below the housing drags the whole enclosure down to its figure, so match every entry to the housing rather than to the cable. The cutouts, glands and HMI windows guide works through the sizing, and NEMA 4 vs 4X vs IP66 untangles the IP digit on a gland from the enclosure type on a spec sheet.
Our housings close the loop at the display itself: an IP65-type front seal with the display installed, manufacturer rated; not UL listed. The gasketed rear cover, the glands and any window you add carry the same duty as the front, and none of it changes because the screen now has two audiences.
What do you order for a web based HMI panel?
Three things: the panel PC or HMI whose firmware serves the HTML5 page, a stainless housing sized to its display — our HMI housings take panel PCs from 7 in to 23.8 in — and the gland for the Ethernet run, with the cutouts on the drawing.
The list is short, and only the first line is new:
- The HMI device with the web server in its firmware. Browser access is selected on the device, so confirm it in the model's feature list before anything else.
- The display size. A 10.1 in panel PC HMI housing suits a machine-mounted view, and a 15.6 in housing suits a shared position.
- The housing itself. 304 stainless, VESA 100 mounting at the rear, gasketed rear cover; pick the exact device in the configurator and every cutout lands where you draw it.
- One gland entry for the Ethernet run, sized to the cable as in the section above, plus programming access if the panel sits behind a sealed cover — remote USB programming access at an HMI enclosure shows the ways that keep the rating intact.
Depth is the dimension buyers get wrong at panel PCs. If the wall is tight, how shallow an HMI enclosure can be for an 8 in panel gives the stacking arithmetic before you order. We build to your drawing and deliver in 10 business days, anywhere in the world — counted from your order, or from your approval of the drawing for custom work. The stainless HMI enclosures range holds the sizes, and the configurator takes the device and the cutouts from there.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 10.1" HMI enclosure | 304 stainless | 8.72 x 12.66 x 3.48 in | IP65-type front seal with the display installed, manufacturer rated; not UL listed |
| 15.6" HMI enclosure | 304 stainless | 11.69 x 17.64 x 4.13 in | IP65-type front seal with the display installed, manufacturer rated; not UL listed |
| 7" HMI enclosure | 304 stainless | 7.43 x 9.96 x 3.7 in | IP65-type front seal with the display installed, manufacturer rated; not UL listed |
| 23.8" HMI enclosure | 304 stainless | 15.91 x 24.96 x 4.02 in | IP65-type front seal with the display installed, manufacturer rated; not UL listed |
Questions
Does the touchscreen stop working when the network is down?
It keeps running. The local screen reads the controller through its own driver, so the panel works with the Ethernet cable unplugged; only the browser view goes stale. Reconnect and the page returns at its 0.5 to 1 s refresh, because the web service lives inside the panel.
How much bandwidth does a browser view need?
Far less than the link: in the worked example, a 30-object screen at 500 ms refresh moved 4 kB/s, which is 32 kbit/s, about 0.032% of one switched 100 Mbit/s port. Ten concurrent clients still sit under 0.32%, so one panel serves a shift of viewers without touching the machine network's headroom.
Can I run the browser on a phone or tablet?
Yes, any current HTML5 browser renders the page. A phone works for a supervisor walking past; a fixed viewing position wants a screen near the panel's own size. Our housings take panel PCs from 7 in to 23.8 in, and the 10.1 in and 15.6 in housings suit a wall or pedestal at eye height.
Can the browser session start a pump or change a setpoint?
Only where you allow it: the web view shows the same screens but rights follow the HMI project's access levels, so keep Start, Stop and setpoint objects on screens the remote user level never opens. If a screen must write remotely, issue one command during commissioning and confirm the controller's feedback bit, not just the button colour.
What refresh rate can a critical tag reach?
Set the web screen to 0.5 to 1 s overall, then give a critical tag its own poll of 100 to 200 ms where the driver supports per-tag rates. Bandwidth is never the limit — each refresh moves about 2 kB — so the tag-poll setting you choose sets the floor, not the link.