Email us

Este artículo está en inglés. Ver el sitio en español

Cet article est en anglais. Voir le site en français

Dieser Artikel ist auf Englisch. Website auf Deutsch ansehen

Este artigo está em inglês. Ver o site em português

本文为英文。 查看中文网站

VFD phase loss fault on single phase input: causes and fixes

A phase-loss fault on single-phase input is the drive detecting the leg that is not there: bus ripple falls from 360 Hz to 120 Hz and dips about three times deeper. Pick a drive the maker rates for single-phase input, derate its output 35-50% (a 5 hp, 16 A load needs a 25-32 A output rating at 230 V), and set the protection through the drive's documented parameter. Each input line then carries about 26 A; never jumper a terminal.

NEMA4 Enclosure engineering team · Published November 12, 2026 · 8 min read

Short answer: the fault is real. On single-phase input your drive's rectifier charges its DC bus 120 times per second instead of the 360 it was built for, the ripple dips about three times deeper, and the phase-loss detection or the sagging bus trips. Fix it at selection: pick a drive the maker rates for single-phase input, and size it for the 35-50% output derating their manuals impose. Land the two hot legs on the input terminals, and set phase-loss protection through the documented parameter. Jumpering a live leg onto the third terminal silences the message and changes none of the physics. The worked example below sizes the fix for a 5 hp load: 25-32 A of output rating at 230 V, with each input line carrying about 26 A.

Why single-phase input trips the fault

A three-phase drive charges its bus through a six-pulse bridge: six diodes deliver six charge humps per line cycle. At a 60 Hz supply that is a 360 Hz ripple (300 Hz at 50 Hz), leaving 2.8 ms between humps. On single phase, two diode pairs do the work of six. The bus is charged twice per cycle — 120 Hz at 60 Hz, 100 Hz at 50 Hz — and the capacitors carry the load alone for 8.3 ms between humps.

The discharge depth follows ΔV ≈ I/(f·C). Your load current I and the drive's capacitance C stay the same, but the ripple frequency f falls to a third, so every dip is about three times deeper. The capacitors take more ripple current and run hotter, which shortens their life. The two working diode pairs conduct for roughly half of each cycle instead of a third, so the input stage heats more too. Hold-up time shrinks with all of it, which is why a drive that ran all day on three phase starts throwing undervoltage messages on single phase.

Phase-loss detection reads this directly. Many drives measure each input leg; others infer a missing phase from the low-frequency ripple pattern on the bus. Either way, a three-phase-only model is designed to trip within seconds of power-up, and it is right.

Symptoms and what each one points to

Match your symptom to a cause before you touch anything:

  • Phase-loss message seconds after power-up, motor never turning. A three-phase-only drive doing its job; you are at cause 1.
  • Runs fine unloaded, trips during acceleration or a load step. The 3× deeper ripple dip grows with load current; the drive is undersized for single phase or above its single-phase rating (cause 2).
  • Weeks of good running, then trips on hot afternoons or when another machine starts. A real supply problem: a cleared fuse in one leg, a loose lug or a sagging feeder. The drive is right to trip (cause 3).
  • Phase-loss and undervoltage messages alternate under load. The bus dips are reaching the undervoltage trip; watch the keypad's DC-bus readout through a start.
  • Trips immediately while the panel voltmeter reads 240 V. One leg is dead between the meter and the drive terminals: a fuse, a contactor pole or a lug.

The causes, most likely first

  1. Three-phase-only drive on a two-line feed. Most makers list separate single-phase and three-phase input models under about 10 hp, and the three-phase-only unit is designed to refuse this feed. This is the most common reason a freshly wired drive shows the fault.
  2. A dual-rated drive run above its single-phase rating. The manual's single-phase output rating already carries the 35-50% derate; a 5 hp load on a 5 hp frame trips the moment the load rises.
  3. A dead or sagging leg on the supply side. Blown fuse, loose lug, a contactor pole that no longer pulls in. The detection is doing exactly what it is for.
  4. Detection too fast for the feed on a dual-rated model. Protections live in parameters, and they are set only as the manual documents. One maker's technical note, for example, enables its motor-disconnect detection by setting parameter 95.26 to 1; it works by monitoring current on all three motor phases. Your drive's input phase-loss function has its own number, valid values and time delay in the manual's protection group.

How to check each cause

Work top to bottom; the first two checks settle most cases.

  1. Read the input table in the manual. A dual-rated model lists 1-phase 200-240 V ±10%, 50/60 Hz alongside the three-phase entry; a three-phase-only model lists three phases only. One page ends the question.
  2. Measure line-to-line at the drive's input terminals with it energized. Both legs should sit within ±10% of nominal — 207-253 V on a 230 V feed. A leg at 0 V is a cleared fuse or a dead lug; a leg at the low edge on hot afternoons is a sag.
  3. Check each hot-line fuse under load. A volt or more across the fuse body means it has cleared.
  4. Note when the fault appears. At rest points to cause 1; during the ramp to cause 2 or 4; hours into a shift to cause 3.
  5. Watch the keypad DC-bus readout through a loaded start. A 230 V single-phase feed charges the bus to about 325 V DC (230 × √2). Compare the dip under load against the undervoltage trip value the manual prints; a dip that reaches it on every start means the frame is too small.
  6. Open the parameter list before changing anything. Note the phase-loss function's number, value and time delay. When the manual offers no single-phase setting, that model has answered you.

The fix, with the sizing arithmetic

Fix by case. A three-phase-only drive gets replaced: the honest routes are the same family's single-phase-input model, a dual-rated drive sized below, or a real three-phase feed. A rotary converter works too; size it from the converter maker's table. A dual-rated drive gets wired right: two hots on the input terminals the manual designates, ground on the ground lug, neutral left out. On a 120/240 V split-phase panel the two hots are the feed; the neutral has no business at a drive terminal. Bond the enclosure and the drive ground the way the grounding and bonding guide sets out. A jumper across two input terminals is not an option: it fakes the healthy-phase signal while the capacitors and diode pairs carry the same overload as before.

Then sizing, where most single-phase trips are actually won or lost:

Sizing step Value Arithmetic
Motor load 5 hp, 16 A at 230 V drive selection tables for a 230 V motor
Output rating at 35% derate 25 A 16 ÷ 0.65 ≈ 25 A → 10 hp frame (28 A)
Output rating at 50% derate 32 A 16 ÷ 0.5 = 32 A → 15 hp frame (42 A)
Input per line, three phase 15 A typical 5 hp, 230 V drive datasheet
Input per line, single phase 26 A 15 × 1.7 ≈ 26 A; datasheets list 1.7-2×
Feeder floor 33 A 26 × 1.25 = 32.5 A
Feeder copper 8 AWG 50 A at 75 °C covers 33 A

Take the 10 hp frame when the manual's single-phase figure is the 35% derate. At 50% the 28 A frame falls 4 A short of the needed 32 A, and the 15 hp frame is the answer. Size the feeder on input current, not motor hp: the NEC sets drive feeder conductors at 125% of the drive's rated input current, so 26 A becomes a 33 A floor, and 8 AWG copper carries 50 A at 75 °C with margin. Count the heat as well: 3.7 kW at the shaft is about 4.1 kW into the motor at 90% efficiency, and drive losses of 3-5% of that throughput are 125-200 W at full load (datasheets list efficiency). That wattage goes into your box's heat budget, not into the motor column. The derating basics sit in the single-phase derating explainer, and a worked 10 hp single-phase enclosure is specified in the fan-duty article.

Keeping the fault from coming back

  • Size on input current and heat, never on hp alone: about 26 A per line and 125-200 W of loss for this 5 hp example, whatever the frame's label says.
  • Protect both hot lines at the fuse or breaker sizes the drive manual lists; a cleared fuse in one leg is cause 3 wearing a phase-loss mask.
  • Torque the lugs and recheck after the first month of thermal cycling; a loose input lug reads exactly like a lost phase.
  • Keep the drive at or below 40 °C [104 °F] ambient unless its datasheet allows more. At a 35 °C [95 °F] plant that leaves 5 K of margin, so the 125-200 W gets planned before the box is chosen; the sealed-box recovery steps are in the overheating fix.
  • Record the bus dip at commissioning. Next year's loaded-start reading tells you whether the capacitors are aging before they fail.
  • Derate for altitude on high sites: most drive manuals add roughly 1% per 100 m [330 ft] above 1,000 m [3,300 ft].
  • Take the fault-reset pushbutton through the door so a sealed enclosure stays sealed the next time this trips; the external reset article shows the parts and the hole.

When to re-specify the enclosure

The derated frame usually runs one or two sizes larger, so the panel that fit the 5 hp drive rarely fits the 10 hp one without a layout pass: rail length, working depth in front of the drive, and gland room for two 8 AWG feeders with their bending space. Heat is the harder half: 125-200 W inside a sealed box is a cooling question, and the cooling has to stay inside the rating. Our stainless boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed.

If you start from the box instead of the drive, the enclosure selector sorts candidates by environment and inside dimensions, and the IP20-drive article shows how an open drive sets the minimum rating. For odd depth, off-center gland positions or factory-cut terminal entries sized to the new feeders, a custom enclosure beats a field-drilled one; the custom stainless page takes the drawing with the quote. The sizing guide carries the wall and heat math for the bigger frame.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
60 × 36 × 16 in304 stainless60 x 36 x 16 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
48 × 36 × 16 in304 stainless48 x 36 x 16 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
60 × 36 × 12 in304 stainless60 x 36 x 12 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Can I jumper the third input terminal to stop the phase-loss fault?

A jumper only fools the detector. The rectifier still conducts through the same two diode pairs, the bus still sees 120 Hz ripple with dips three times deeper, and the jumpered terminal sits live on a wiring diagram the next service person expects to be dead. Fix it with hardware: a drive the maker rates for single-phase input, sized for the 35-50% derate.

How much do you derate a three-phase drive for single-phase input?

Plan on 35-50% of the three-phase output rating unless the manual states its own single-phase figure. For a 5 hp motor (16 A at 230 V): 16 ÷ 0.65 ≈ 25 A calls for a 10 hp frame (28 A); at a 50% derate, 32 A calls for the 15 hp frame (42 A). Input current rises from 15 A to about 26 A per line, so the feeder floor is 33 A and 8 AWG copper covers it.

Why does the phase-loss fault appear only when the motor accelerates?

Ripple depth follows ΔV ≈ I/(f·C): at 120 Hz instead of 360 Hz the bus dips about three times deeper, and the dip grows with load current. It reaches the trip window exactly when the motor pulls hardest. On a dual-rated drive, extend the acceleration ramp one step and retest; continued trips mean the frame is above its single-phase rating.

Does a single-phase-rated drive change the enclosure?

Usually yes. The derated frame runs one or two sizes larger, the two feeders grow to 8 AWG copper, and the drive adds 125-200 W at full load inside a sealed box. Recheck rail length, gland size and the heat budget, and take the reset pushbutton through the door rather than opening the enclosure after every trip.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Start from the plant-floor PLC cabinet buildRequest a custom quote

NEMA 4X enclosures: sizes for this job

Keep reading

Related engineering answers

All articles

Buying guides

The guides behind this answer

All guides