VFD derating for single phase input explained

On single-phase input, a three-phase-input drive is typically allowed 50-67% of its rated output current: its rectifier and DC-link capacitors see about 1.73 times the line current and two charging pulses per cycle instead of six. Pick the drive by permitted amperes, then size its sealed enclosure from the heat at 3-4% of the load kW.

NEMA4 Enclosure engineering team · Published November 11, 2026 · 7 min read

Short answer: a drive built for three-phase input, run on single-phase power, is typically allowed 50-67% of its rated output current, and the maker's single-phase table gives the exact amperes. The input rectifier and DC-link capacitors set that limit, not the output inverter. Single-phase input hands them two charging pulses per cycle instead of six, with about 1.73 times the line current to absorb. So you pick the drive by permitted amperes against your motor's full-load current, and you size its enclosure from the heat, which runs 3-4% of the load kW.

What derating is

A rating is what the drive's maker allows at stated conditions: this supply, this ambient, this duty. Derating is the correction you apply when you run outside that basis. In practice it means buying a drive one frame larger and using part of it, on purpose, so the input side stays inside its thermal limits. Single-phase input is exactly such a departure, unless the nameplate already covers it.

Plenty of small drives cover it from the factory. Most 230 V drives at 3 hp and below ship rated for both single- and three-phase input, so their printed amps apply on either supply. From 5 hp upward you work from the table.

What you have What you size with
Nameplate rates single-phase input at your horsepower Its printed single-phase output amps, no extra factor
Three-phase-input drive on a single-phase line The maker's single-phase table: typically 50-67% of output current
No single-phase table for that model A different drive, one factory-rated for single-phase input

Why single-phase input limits the drive

A conventional drive splits into three parts: a rectifier at the front, a DC-link capacitor bank in the middle, an inverter at the output. The rectifier charges the link to about 325 V on a 230 V drive and about 650 V on a 480 V drive. The inverter then draws from that bank to build the motor's three-phase, so the input and output sides carry separate current and thermal limits.

On three-phase the bridge delivers six charging pulses per cycle; on single-phase, two. The capacitors hold the load through longer gaps between peaks, so they see more ripple current and run hotter. The conducting diodes take the whole line current in fewer, taller pulses, and the line current itself is higher: the same power arrives through one conductor instead of three, a factor of √3, or 1.73. A load drawing 20 A per line on a three-phase supply pulls about 35 A from a single-phase line.

That is why the front end gives out before the output stage does. Makers who build single-phase-input drives size the rectifier and capacitor bank one frame up: a 5 hp single-phase-input drive carries roughly the front end of a 7.5 hp three-phase unit, and 5 over 7.5 is 0.67, the top of the typical band. Your inverter could still deliver rated amps; the input side overheats first.

The number you select by

Select by amperes, not horsepower. The motor's full-load current is on its nameplate, and the NEC motor tables print the same class of values: 15.2 A at 5 hp and 230 V, 22 A at 7.5 hp, 28 A at 10 hp, 42 A at 15 hp. The single-phase allowance is the maker's to state, 33-50% off, leaving 50-67% of rated output current, and it lives in that model's single-phase table.

Read the percentage's basis while you are in there. "Derate 33%" can mean keep 67% or lose 33% depending on who wrote it, so take the resulting amps from the table and compare amps to amps. Two more columns matter: ambient, where drives carry a 40 C rating unless the datasheet allows more, and overload, since some single-phase ratings trim the momentary overload too. When the permitted amps meet your motor's full-load current, the drive is in. When they fall short, step one frame up and re-read that model's table, because the band moves with the drive's design.

What the derate changes in your panel

Three things move. Your supply: single-phase line current runs near 1.73 times, so breaker and conductors follow the drive's single-phase input data, about 38 A from the line in the example below against about 22 A per line on three-phase. Your heat load: losses track the load at 3-4% of load kW, the mirror of the 96-97% efficiency drives post at rated load, and the datasheet figure wins where it differs. Derating protects the drive's own capacitors; it barely changes the watts landing in your enclosure.

Your enclosure is sized from that heat, not from horsepower, which is the method behind sizing large drives from heat loss and the rating and cooling walkthrough for one drive. You can watch the whole single-phase chain applied to a 10 hp fan fed from single-phase power. Inside a sealed box, the drive's 40 C ambient limit is your temperature budget: drive overheating in a sealed enclosure shows up as overtemperature trips on hot afternoons, and the fix starts with the heat number this page produces.

Sizing the enclosure: 7.5 hp pump on 230 V single-phase at 35 C ambient

The inputs:

  • Supply: 230 V single-phase, 35 C ambient, pump near full load
  • Motor: 7.5 hp, three-phase, 22 A full-load current (NEC motor tables)
  • Drive allowance: 50-67% of output current on single-phase input, per the maker's table
  • Enclosure: sealed 316L stainless, wall-mounted; stainless sheds heat at k = 3.7 W/m²K
  • Drive limit: 40 C ambient, so the allowed rise is 40 − 35 = 5 K

The rules, in words: the drive's three-phase output rating must reach your 22 A divided by the allowance; drive heat is 3-4% of load kW, and load kW is horsepower times 746 W; a sealed box passes k x A x ΔT watts through its free surface.

The arithmetic:

  • Drive: 22 ÷ 0.50 = 44 A needed; 22 ÷ 0.67 = 33 A. A 15 hp class drive carries an output rating around the 42 A motor-table value, so at 50% it gives 21 A, one amp short, and at 67% it gives 28 A and passes. One frame up, the 20 hp class (54 A in the motor tables) gives 54 x 0.50 = 27 A and passes on either allowance.
  • Heat: 7.5 hp x 746 W/hp = 5,595 W, about 5.6 kW of load; x 0.03 = 168 W and x 0.04 = 224 W. Design at 224 W.
  • Box: the largest stainless wall-mount size is 60 x 36 x 16 in [1524 x 914 x 406 mm] (H x W x D). Its six faces total 4.77 m²; drop the 1.39 m² back that sits against the wall and 3.37 m² dissipates. Passive capacity: 3.37 m² x 3.7 W/m²K x 5 K = 62 W.
  • Check: 224 W ÷ (3.37 x 3.7) = 224 ÷ 12.5 = 18 K of rise, so 53 C inside at 35 C ambient, 13 K over the drive's limit.

The drive decision: at a 50% allowance order the 20 hp class; at 67% the 15 hp class holds. That one frame of spread is exactly why you read the model's table rather than a blanket percentage.

The cooling decision: sealed stainless at this 5 K budget passes 3.7 x 5 = 18.5 W per square metre of free surface, about 62 W even in the largest box, so above roughly 60 W of drive heat plan closed-loop cooling. An air-to-air heat exchanger or enclosure air conditioner rated at least 224 W at 35 C covers it, rounded to a 300 W class for margin. Keep it closed-loop: a fan-and-filter kit is typically IP54 / NEMA 12 class, and the weakest part sets the assembly's rating. Indoors at 25 C the budget widens to 15 K and the same box sheds 3.37 x 3.7 x 15 = 187 W, still short of 224 W. Cutting the load works instead: at 60% speed the pump's power falls to 0.6³ ≈ 22%, about 1.2 kW and 50 W of drive heat, and the sealed box holds.

What to specify

Item What to write
Drive Model whose single-phase table permits at least your motor's full-load amps (22 A here); note the frame you landed on
Supply 230 V single-phase; breaker and conductors from the drive's single-phase input rating, about 38 A here
Enclosure 316L stainless for washdown or coastal duty, 304 for general plant air; rated NEMA 4X / IP66 by the manufacturer, not UL listed
Cooling Closed-loop heat exchanger or air conditioner rated at or above the heat load at design ambient (224 W at 35 C here)
Layout Drive clearances per its manual, mounting panel, and gland cutouts for the single-phase input and the motor output
Order Your exact height, width, depth and cutouts; delivered in 10 business days, counted from your approval of the drawing

Pick the grade and size in the stainless size finder, or run the enclosure selector while the environment or DIN count is still open. The enclosure sizing guide covers the wire-bending and working-space numbers that sit beside the heat load. Make one habit fixed: kill and lock the supply before the door opens, because single-phase line voltage at this level is not a control level.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
60 × 36 × 16 in304 stainless60 x 36 x 16 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
48 × 36 × 16 in304 stainless48 x 36 x 16 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
60 × 36 × 12 in304 stainless60 x 36 x 12 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
16 × 12 × 8 in304 stainless16 x 12 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Can a 5 hp three-phase-input drive run a 5 hp motor on single phase?

Usually no. The single-phase table typically permits 50-67% of output current, so a 5 hp drive gives about 8-10 A against a motor that needs 15.2 A. Take a 7.5-10 hp class drive whose single-phase rating reaches at least 15.2 A, or a model factory-rated for single-phase input at 5 hp.

Does derating make the drive dump more heat into the enclosure?

No. Losses track the load at 3-4% of load kW, so the 7.5 hp example sheds 168-224 W whether the frame is 15 or 20 hp. The derate protects the drive's rectifier and DC-link capacitors from the 1.73 times single-phase line current; your enclosure cooling is sized from the load, not from the frame.

Why is the single-phase line current 1.73 times higher?

The same power flows through one conductor instead of three. Single-phase current is power divided by voltage times power factor, while three-phase current divides by 1.73 times voltage, so the ratio is 1.73. A 22 A three-phase load pulls about 38 A from the single-phase line, which is what your breaker and conductors carry.

My pump runs well below full load, so do I still need the derate?

Compare amps, not horsepower. At 60% speed a pump needs about 22% of full-load power by the cube law, but current falls less because the magnetizing current stays, so figure 9-13 A on a 22 A motor. A 50% allowance of 21-27 A covers that. Constant-torque loads are the exception: current sits near full-load amps at any speed, so derate for full current.

Do small drives need derating on single-phase input?

Mostly not below 5 hp. Small drives in the 3 hp class and under are commonly factory-rated for either supply, so the printed amps apply as they stand. From 5 hp upward, expect to use the single-phase table and usually a frame one size larger than the motor.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Start from the plant-floor PLC cabinet buildRequest a custom quote

Check the heat load in the calculator · NEMA 4X enclosures: sizes for this job