Short answer: keep one drive on one machine when you can. If a single VFD must feed two machines, switch the branches only as a dead-output selector: drive stopped, run input open, and the DC bus discharged for the interval the manual states, five minutes in several manuals, before anyone turns the switch. Match the drive's rated output current to the largest motor's nameplate full-load current, and set the drive's motor protection to the motor that is actually running. The enclosure side stays simple: a sealed, glanded stainless wall-mount box, sized from heat loss rather than the drive's footprint. The worked example below puts a 60 W drive in a 24 x 20 x 10 in box at 35 C (95 F) ambient and shows why the wall area decides the size.
Choose how the drive feeds the machines
A VFD output is a synthesized, current-limited waveform, not a utility three-phase bus. Opening a switch while the inverter regulates motor current forces the output overcurrent protection to trip, and repeated trips stress the output devices. The switching device on a drive output either carries no load, because the drive is stopped every time, or it belongs somewhere else.
A generator or UPS transfer mechanism is built to move a live circuit between two sources. On a drive output you want the opposite action: a motor-rated rotary cam switch that opens the running branch fully before the next one closes, with a true OFF position. Select it from motor current, not drive rating. A 3 hp motor at 230 V three-phase draws about 9.6 A full-load, the value the NEC motor full-load current tables list, so a 16 A or 25 A switch rated AC-3 covers it with margin.
| Arrangement | Where it works | The numbers that govern it |
|---|---|---|
| One drive per machine | Every job the budget allows | Drive rated output current at or above motor nameplate FLC; one parameter set per motor |
| Break-before-make selector, dead switching | Two similar machines, one at a time | Selector AC-3 rating at or above motor FLC; auxiliary contact in the run input; 5 min bus discharge before each turn |
| Interlocked receptacles | Branches that change often | NEMA L15-30 (250 V, 30 A, three phases plus ground); receptacle dead unless selected |
| Switching under load | Nowhere | An output overcurrent trip every time; repeated trips stress the inverter |
With one parameter set and two motor sizes, set the electronic overload to the smaller motor's FLC. The larger machine then draws less relative to that setting and stays protected. A drive that stores two parameter sets handles mixed sizes more cleanly.
What you need
- The drive manual, for the rated output current, the heat-loss table, the DC bus discharge interval and the motor-cable rules.
- A break-before-make rotary cam switch, AC-3 rated above the motor's FLC, with an auxiliary contact.
- A sealed stainless wall-mount box; ours is rated NEMA 4X / IP66 by the manufacturer; not UL listed. Pick from stainless wall-mount enclosures or shortlist by size and environment with the enclosure selector.
- Cable glands matched to each cable's outside diameter, plus plugs for spare holes.
- Shielded motor cable where the manual calls for it.
- A meter that proves the DC bus is dead before output work.
- An equipment grounding conductor sized from the overcurrent device ahead of the drive, per NEC Table 250.122.
Install and interlock it
- Hang the box on 2 in [50 mm] standoffs so air moves over the back wall. Keep the highest handle at or below 2.0 m (6 ft 7 in) above the floor, the height NEC 240.24(A) sets for operable handles; the mounting guide covers placement and working space.
- Mount the drive with the clearances its installation drawing gives, fan inlet and outlet clear. The drive's bottom fan only recirculates air in a sealed box; where that heat goes traces the full path.
- Feed the input through a disconnect and fusing sized from the drive's rated input current; VFD supply components are sized by rated input current walks that side of the cabinet.
- Bond the enclosure, the raceway and the machine frames into one fault-current path; the grounding and bonding guide covers conductor sizing and contact surfaces.
- Run each machine's motor cable to its own selector position, with power and control wiring separated as the manual sets out.
- Wire the selector's auxiliary contact in series with the drive's run or enable input, so the command drops before the power contacts move.
- Enter the running motor's nameplate FLC into the drive's motor-protection parameter.
- Commission every changeover the same way: stop the drive, wait the bus-discharge interval (five minutes in several manuals), measure the bus with a meter, turn the selector, restart.
- Gland every entry, plug every spare hole, and seat the door gasket clean and dry.
Worked example: 60 W of drive heat in a 24 x 20 x 10 in box at 35 C
The inputs, and where each one comes from:
- Drive loss of 60 W: a worked-example assumption. Take the real figure from your drive manual's loss table and add anything else that heats the box; how to total component losses shows the method.
- Shop air at 35 C (95 F).
- Drive ambient limit of 40 C (104 F), the rating drives and most electronics carry unless their datasheet allows more.
- Wall heat transfer of 3.7 W/m²K for stainless walls.
- A 24 x 20 x 10 in [610 x 508 x 254 mm] box from the catalog, outside surface 1.19 m².
The rule in words: a sealed wall rejects heat at wall conductivity × surface area × (inside air − ambient). Turned around, the temperature rise is the heat load ÷ (conductivity × area).
The arithmetic:
- Area = 2 × (0.610 × 0.508 + 0.610 × 0.254 + 0.508 × 0.254) m² = 1.19 m²
- Rise = 60 W ÷ (3.7 W/m²K × 1.19 m²) = 60 ÷ 4.4 = 13.6 K
- Inside air = 35 C + 13.6 K = 48.6 C, which is 8.6 K past the drive's 40 C limit.
The decision: at the 5 K rise the limit allows, this wall carries 3.7 × 1.19 × 5 = 22 W. The 24 x 20 x 10 in 304 stainless box therefore suits drives that lose about 22 W or less at 35 C ambient. A 60 W drive needs 60 ÷ (3.7 × 5) = 3.24 m² of stainless, and the 60 x 36 x 16 in box offers 4.77 m²: the rise falls to 60 ÷ (3.7 × 4.77) = 3.4 K and the inside air lands at 38.4 C.
Where the wall alone falls short, keep the box sealed and move the heat with a cooling unit rated above the load. For a corrosive or washdown corner, the 316L version of the same 24 x 20 x 10 in size carries the same 1.19 m² of wall.
Checks when it's done
- With the drive at full load for an hour on a 35 C day, air at the drive's inlet reads 40 C (104 F) or less. Anything higher means more wall, deeper standoffs or sealed cooling.
- Cycle the selector with the drive enabled and read the fault log afterward. An empty log shows the auxiliary contact opens the run command before the power contacts move.
- Compare the drive's displayed output current with each motor's nameplate full-load current under load.
- Measure the bus on the first few changeovers until the five-minute habit holds without the meter.
- Hose the gasket line and gland entries, then open the door onto a dry box.
Mistakes that trip the drive or cost the rating
- Ventilation slots or a fan-filter kit on a Type 4X box hand the whole assembly that part's lower rating. A sealed cooling unit moves heat and keeps the rating.
- A make-before-break transfer action puts both motors on one output for an instant, and the drive trips on the combined inrush.
- Motor protection entered from the larger nameplate leaves the smaller motor outside its protection; set the parameter to whichever motor is running.
- Mounting the box flat against the wall takes the back wall out of the heat path, so keep the 2 in standoff from step 1.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 24 × 20 × 10 in | 304 stainless | 24 x 20 x 10 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 10 in | 316L stainless | 24 x 20 x 10 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
How long should I wait before switching a VFD output between motors?
Stop the drive, open its run or enable input, and wait the DC bus discharge interval the manual states; five minutes is the figure in several manuals, and larger drives can specify more. After the wait, measure the bus terminals with a meter before touching any output wiring. The wait protects you; the break-before-make selector with the drive stopped protects the output stage.
Can a generator transfer switch work on a VFD output?
Only when it switches dead and breaks before it makes. A generator or UPS transfer mechanism is built to move a live circuit between sources, and a make-before-break overlap would parallel two motors on one drive output and trip it. Use a motor-rated rotary cam switch with a true OFF position, an auxiliary contact in the run input, and the stopped-drive, five-minute sequence every time.
Which receptacle fits machine tools on a 240 V VFD output?
NEMA L15-30 is the standard locking device for 250 V, 30 A three-phase machine tools: three phases plus a ground, 30 A. L14-30 looks similar but carries 125/250 V split-phase, two hots and a neutral, so it suits generator and welder circuits rather than three-phase motors. Whatever you fit, keep the receptacle dead unless that branch is selected, and cord only the motor circuit.
How much heat does a sealed stainless enclosure reject passively?
At 35 C (95 F) ambient with the drive's 40 C (104 F) limit, a 24 x 20 x 10 in stainless box sheds about 22 W through 1.19 m2 of wall. The 60 x 36 x 16 in box reaches about 88 W through 4.77 m2. Above those figures, add a sealed cooling unit sized above the load so the NEMA 4X / IP66 rating survives.