VFD 24V auxiliary power supply for a panel indicator

Read the VFD's 24 V auxiliary output limit before you wire the indicator. In the worked example a display drawing 60 mA overloads a 50 mA aux output by 20% (0.24 W short), so the display gets its own DIN-rail 24 VDC supply sized at 125% of the connected load — a 1 A / 24 W unit — and the 5 V pin on the RS485 RJ45 stays out of the power plan.

NEMA4 Enclosure engineering team · Published November 25, 2026 · 6 min read

Short answer: budget the VFD's 24 V auxiliary output before you land a wire on the indicator, and size a separate DIN-rail supply at the same voltage, set at 125% of the total connected load. In the worked example below, a setpoint display drawing 60 mA hangs on a drive whose aux output is limited to 50 mA. That is a 20% overload with 0.24 W missing, so the display moves to its own 1 A / 24 W supply with a 2 A fuse in the positive output leg. The 5 V pin on the drive's RJ45 communications connector stays out of the power plan: it is the wrong voltage, and its budget belongs to the bus.

Two numbers to read before you wire anything

Open the drive manual to the control-terminals page and find the auxiliary output's current limit. Manufacturers print it beside the aux output terminal; compact frames list 50 mA, larger frames list several times that. Then open the indicator datasheet and read two lines: the permitted supply-voltage range and the maximum current draw. Industrial indicator inputs commonly publish a band of ±20% around nominal, that is 19.2–28.8 V. Budget against the maximum current, quoted at full brightness; an indicator that dims draws less, until the day someone turns it back up.

The budget, as a worked example

Picture the panel: a VFD, a maintained start/stop selector, a spring-return raise/lower selector, and the setpoint display. The selectors are plain contacts, so the only load on the aux output is the display. Both numbers below are example inputs; read your own pair from the two datasheets and rerun the same lines.

  • Display maximum draw: 0.060 A at the aux-output voltage = 1.44 W
  • Aux output limit: 0.050 A = 1.20 W
  • Overload: the display wants 10 mA more than the output sources, which is 20% over
  • Shortfall: 1.44 W − 1.20 W = 0.24 W
Line item Value Where the number comes from
Display, maximum draw 60 mA at 24 V = 1.44 W indicator datasheet, full brightness
VFD aux output limit 50 mA at the same nominal = 1.20 W drive control-terminals page
Overload 10 mA / 20% 60 − 50 = 10; 10 ÷ 50 = 0.20
Power shortfall 0.24 W 1.44 − 1.20
Replacement supply 1 A / 24 W DIN-rail unit 0.060 A × 1.25 = 75 mA ≤ 1 A

The 125% rule sizes the replacement: 0.060 A × 1.25 = 75 mA. Catalog DIN-rail supplies start at 0.5 A / 12 W, so the smallest standard unit, a 1 A / 24 W model, carries the display at 6% of rating and leaves 940 mA of headroom for the next load. Efficiency, inrush and derating belong in the same budget; how to select a 24 VDC power supply for a control panel works them line by line.

Why the 5 V pin stays out of the plan

An RJ45 plug names a connector shape, not a protocol; on many VFDs it carries RS485 plus a low-voltage supply pin. The example drive offers 5 VDC there. For an indicator built for the aux-output voltage that fails twice over: the voltage is off by nearly a factor of five, and the pin's budget belongs to the keypad or the bus's terminating electronics. Pinouts also differ by maker — one RS485 RJ45 manual puts the aux output voltage on pin 4, another powers a keypad from pins 1, 2, 7 and 8 — so a cable copied from memory can land a supply pin on a data pair. Hang the indicator on that pin and the bus starts dropping frames; on one comms link, Modbus failed whenever the RJ45 was plugged in. Read the exact pinout from the drive manual and keep power loads off the comms connector.

Fit the DIN-rail supply

  1. Lock out the panel and confirm absence of voltage before opening the door.
  2. Click the supply onto its rail with end brackets; a DIN rail adapter seats a bare unit and stops it sliding. Leave the free-air gap many supply datasheets print: 15 mm (0.59 in) above and below the case.
  3. Feed the input from the control-power branch after the disconnect; which side of a panel breaker gets the supply settles the line and load terminals. Fuse the branch at the input rating the supply datasheet prints.
  4. Run 18 AWG (0.82 mm²) copper from the output to the indicator and fuse the positive leg at 2 A. The indicator's 60 mA is 3% of that, so the fuse sits in the circuit for faults, not for the load.
  5. Land the supply's PE terminal on the ground bus with a conductor sized to the upstream protection, as the grounding and bonding guide sets out.
  6. Bond the supply's 0 V terminal to the drive's control common at one point, so the RS485 signal reference is shared; the 0 V return is part of the circuit, and a floating reference reads as a device that never starts.
  7. Keep the aux output and the supply output as separate rails: the drive's aux output carries only the loads within its limit, or nothing at all.
  8. Mount the display in its cutout and support its cable, so the terminal board carries no wire weight; the display-module fit check covers cutout size and depth before you order.

If the cabinet is tight, rerun the depth with the supply included; enclosure size for a drive, power supply and wiring adds a supply to a drive layout line by line.

Checks before you close the door

  • Meter the supply output at the display terminals with everything running: about 24.0 V, inside the display's published band. At the indicator's draw over 2 m of 18 AWG the drop is roughly 5 mV — 18 AWG runs about 21 mΩ per metre, so a 4 m loop at that current wastes 5 mV — and the trim pot matters little.
  • Meter the display's draw in series at full brightness and expect the reading within a few milliamps of the datasheet value.
  • Poll the drive over RS485 while the panel's contactors switch, and watch for framing errors or dropouts.
  • Walk the VFD panel inspection checklist for torque, routing and labels before the first start.
  • Weigh the heat: the supply's loss at 1.44 W output stays under 1 W even at low-load efficiency, rounding error next to a small drive's tens of watts; the enclosure heat calculation shows where it lands in the sum.

Mistakes that cost the panel later

  • Budgeting at a dimmed brightness. The trim cuts the draw today; the first operator who turns the indicator up puts the load back over the limit.
  • Paralleling the two output rails. Regulated sources fight each other, the display browns out, and both units run hot.
  • Borrowing from the comms connector. The 5 V pin starves, the bus drops frames, and the fault reads like a software problem when it is a power budget.
  • Leaving the positive leg unfused once more loads join the panel. One shorted indicator then drops every device on that rail.
  • Cutting the display opening on site. A field-cut hole in a gasketed door gives up the seal, so order the cabinet cut. Our custom 304 and 316L stainless boxes arrive with the cutout in the drawing, rated NEMA 4X / IP66 by the manufacturer and not UL listed; the custom enclosure builder takes the dimensions with the order, delivered in 10 business days from your approval of the drawing.
  • Modifying a listed panel on paper only. When the assembly is listed to UL 508A, the supply and its fuse belong on the drawing; the NEC also requires the enclosure type number marked on the panel (NEC 409.110).

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
60 × 36 × 16 in304 stainless60 x 36 x 16 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
48 × 36 × 16 in304 stainless48 x 36 x 16 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
60 × 36 × 12 in304 stainless60 x 36 x 12 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
10.1" HMI enclosure304 stainless8.72 x 12.66 x 3.48 inIP65-type front seal with the display installed, manufacturer rated; not UL listed

Questions

Can the drive's 24 V auxiliary output power a panel indicator?

Only when the datasheet limit covers every connected load with margin — the drive manual's aux rating is the total for that terminal, so anything already hanging on it counts first. The worked example fails: the indicator wants 1.44 W at 24 V and the aux output is limited to 1.20 W, a 20% overload with 0.24 W missing. Fit a DIN-rail supply at the same voltage, sized at 125% of the total connected load, and leave the aux output to the loads it can carry.

Can I power a 24 V indicator from the 5 V pin on the drive's RJ45 RS485 connector?

Leave that pin out of the plan. The example drive offers 5 VDC there while the indicator runs on the aux-output voltage, so the display sits outside its input range and never starts. The pin's job is the keypad or the bus's terminating electronics; hang a load on it and the network itself begins dropping frames. Take indicator power from the DIN-rail supply and read the exact pinout from the drive manual before wiring the connector.

How much margin does a DIN-rail 24 V supply need?

Size it at 125% of the total connected load — 75 mA for the example panel's 60 mA display. Catalog sizes start at 0.5 A / 12 W, so the practical pick is the smallest standard unit, a 1 A / 24 W supply, loaded to 6%. Some industrial units supply 130% of rated current briefly to cover inrush; read the curve before counting on it.

Does adding the supply overheat the enclosure?

At the example load it is noise: 1.44 W out at roughly 85% efficiency wastes about 0.25 W, against tens of watts from a small drive. Size the enclosure cooling for the drive and check the sum in the enclosure heat calculation. Most DIN-rail supplies hold full rating to 40 °C (104 °F) ambient and derate above it — read the derating curve before you close the door.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Start from the plant-floor PLC cabinet buildRequest a custom quote

NEMA 4X enclosures: sizes for this job · HMI panel cutout dimensions by series

Keep reading

Related engineering answers

All articles

Buying guides

The guides behind this answer

All guides