Email us

Este artículo está en inglés. Ver el sitio en español

Cet article est en anglais. Voir le site en français

Dieser Artikel ist auf Englisch. Website auf Deutsch ansehen

Este artigo está em inglês. Ver o site em português

本文为英文。 查看中文网站

Why a control panel uses three 24 V DC power supplies

Split the 24 V DC load across three supplies when a field fault must not drop the PLC and HMI, the safety relay's instructions call for their own feed, or the I/O total outgrows one unit. In the worked panel that is 8 A, 2.5 A and 1 A on 10 A, 5 A and 2.5 A units, each loaded at 80% or less. Land a green ground wire from every PE terminal to the ground bar; the DIN rail clip carries no fault current.

NEMA4 Enclosure engineering team · Published November 23, 2026 · 6 min read

Short answer: three 24 V DC supplies in one panel buy fault isolation, not extra capacity. You split the load so a short in the field cannot drop the PLC, the HMI or the safety relay. You keep every unit at 80% of its rating or less. One duty follows every split: land a green ground wire from each PE terminal to the ground bar, because the DIN rail clip only locates the unit. The heat ends up the same as one supply's. The payoff arrives the day a crushed cable fails without blanking your screen.

Why three supplies instead of one

Fault containment comes first. A solenoid that shorts, a sensor cable crushed in a gate, water in a field junction box: any of them drags a supply into hiccup. With the field load on its own 10 A unit, the fault trips that unit alone. The 5 A controller unit keeps the PLC scanning and the HMI showing the alarm. On one shared supply, the same short browns out the whole 24 V system at once.

The safety circuit gets its own feed. Many safety relay manuals call for a supply reserved for the safety function; the device's instruction sheet is the source for that wording. When the safety load runs past what the relay's output contacts take, those manuals point to positive-guided auxiliary relays rather than a bigger shared supply. Gate switches, interlock modules and the relay then sit on a feed nothing else loads.

The third reason is plain arithmetic. When your I/O adds to more than one unit can carry with margin, split it by load group. Paralleling two units is a separate case with its own trap, covered below. Sizing a single unit to start from is the companion question how to select a 24 V DC power supply for a control panel answers.

The load budget in a worked panel

Here is a budget you can copy and rescale. Every unit carries no more than 80% of rating, the customary working ceiling for continuous duty on industrial DIN-rail supplies.

Supply Rating Feeds Continuous load Share of rating
PSU 1 10 A / 240 W Sensors, solenoid valves, stack lights 8.0 A 80%
PSU 2 5 A / 120 W PLC, HMI 2.5 A 50%
PSU 3 2.5 A / 60 W Safety relay, gate switches 1.0 A 40%
Total 17.5 A installed — 11.5 A 66% of installed

The heat works out the same either way. At 90% efficiency, the typical figure for single-phase DIN-rail switchers, the three losses run as follows. PSU 1 outputs 24 V × 8 A = 192 W, and 192 ÷ 0.9 - 192 = 21.3 W lost. PSU 2 outputs 24 V × 2.5 A = 60 W and loses 6.7 W. PSU 3 outputs 24 V × 1 A = 24 W and loses 2.7 W. Total loss: 30.7 W. One 15 A unit carrying everything outputs 24 V × 11.5 A = 276 W and loses 276 ÷ 0.9 - 276 = 30.7 W. The split moves where the loss sits on the rail, not how much enters the enclosure.

Each unit's manual names its own branch device on the mains side. The 240 W unit draws 240 ÷ 0.9 = 267 W, about 2.3 A from a 115 V branch, and its inrush figure picks the device class.

What the split changes and what stays the same

The heat stays the same. 31 W enters the enclosure whether one unit or three make it. What changes is concentration. Keep 2 in [50 mm] of empty rail above and below each unit so convection lifts its losses clear; that is the working clearance for units to 240 W, and a bigger unit takes the clearance its manual states. Design the compartment for a 40 C (104 F) interior: typical industrial DIN-rail datasheets hold full rating to 50 C (122 F) and derate above that. When supplies nest inside a secondary box, the heat picture stacks, and nested enclosure heat buildup with multiple power supplies works that case through.

The 0 V reference stays common. Tie the three 0 V terminals together at one point, usually a common terminal on the ground bar, so sensors, inputs and the HMI share one reference. Keep an analog loop on its own isolated supply only when a device's instructions call for it; page on isolating analog and digital I/O power supplies walks through that split.

Parallel wiring is the one trap. Do not wire two units in parallel for extra current unless that model's datasheet names parallel operation for power boost. Two hiccup-mode units fight over the load and neither holds it steady.

Bond every ground terminal

Run a green or green-yellow wire from each supply's PE terminal to the ground bar. Insulated equipment grounding conductors of 6 AWG and smaller are green or green with one or more yellow stripes under NEC 250.119. Size each wire from the branch device ahead of that supply with NEC Table 250.122: a 15 A branch takes 14 AWG copper.

NEC 250.96(A) requires the metal parts meant to carry fault current — enclosure, backplane, ground bar — to be bonded together so they can safely conduct it. NEC 250.12 adds the finishing step: paint, anodizing and other nonconductive coatings come off the threads and contact points unless the fitting is designed to cut through them. On a brushed stainless backplane, that means a star washer or a scraped bright ring under every lug. The full chain from supply terminal to enclosure bond is the subject of the grounding and bonding guide.

The DIN rail clip locates the unit; the wire carries the fault. Mounting a switching power supply in an enclosure covers rail choice, spacing and torque.

Some low-wattage units are double-insulated and carry no PE terminal at all. There is nothing to land on those, so say so on the drawing. The next builder then stops hunting for a terminal that does not exist.

Backplate layout that keeps the split serviceable

Duct sizing comes before enclosure sizing. One wiring-duct maker caps every fill table at 50% of the duct's interior cross-section, citing NFPA 79-2012 section 13.5.2, and gives the reason: round cables leave air gaps between them, so 50% is all a duct actually holds. Design to that ceiling while the panel is new, not the day the integrator arrives.

Run the bottom horizontal duct the full width of the backplate so its cover bears on the vertical ducts at both ends. A long cover with one free end sags and pops open at the first bump.

Leave one free duct row around every terminal strip. A strip squeezed between packed ducts works on commissioning day and fails at your first change order, when a dozen new conductors need a home. Keep about 25% of duct volume as spare for exactly that day.

Rail sequencing, duct tees and terminal spacing are laid out in the backplate and DIN rail layout guide.

What to put on the order, and the decision by case

Layout decides the box in this order: supplies, ground bar, terminal strips, duct with its spare, then the enclosure around them. Our stainless wall-mount line spans outside sizes from 6 x 4 x 4 in to 60 x 36 x 16 in, in 304 for indoor panels and 316L for washdown and salt air, manufacturer-rated NEMA 4X / IP66; not UL listed. Width, depth and every cutout are built to your layout from one piece and delivered in 10 business days — counted from the order, or from your approval of the drawing for custom work. The stainless wall-mount and HMI enclosures size finder filters the line by size and grade. For a backplate beyond any stock size, custom enclosures cut to your layout take the drawing you have made.

Then the decision, by case:

  • One supply when the whole 24 V load sits at 80% of one unit or less and no safety instruction asks for separation. The worked panel's 11.5 A total on a 15 A unit lands at 77%: fine on paper, but one field fault now blanks the HMI and drops the safety relay.
  • Two supplies when the I/O alone outgrows one unit. Put field I/O on the larger unit and controller plus safety on the smaller.
  • Three supplies when you want field faults off the controller and the safety circuit on its own feed. That is the worked panel, and on plants with long field cable runs it is the build worth copying.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
12 × 10 × 6 in304 stainless12 x 10 x 6 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
20 × 16 × 8 in304 stainless20 x 16 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
24 × 20 × 8 in304 stainless24 x 20 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Why does a control panel have three 24 V DC power supplies?

Three reasons, in the order you meet them: a field fault must not drop the PLC and HMI, the safety relay's instructions call for a feed of their own, and the I/O total outgrows one unit. In the worked panel, 8 A of field load sits on a 10 A unit, 2.5 A of controller load on a 5 A unit, and a 1 A safety circuit on a 2.5 A unit; a fault that trips one leaves the other two running.

Can you parallel two 24 V DC supplies for more current?

Only when that model's datasheet names parallel operation for power boost. Most DIN-rail units run hiccup-mode protection, so two of them wired in parallel fight over the load and neither holds it steady. Split the load into groups instead, and size each group's unit at or below its working ceiling.

Does a power supply need a ground wire on a grounded metal backplane?

Yes, whenever the unit has a PE terminal: the DIN rail clip locates it and carries no fault current. Run green or green-yellow wire from the PE terminal to the ground bar, sized from the branch device ahead of it per NEC Table 250.122; a double-insulated unit with no terminal has nothing to land.

How much heat do three small supplies add compared with one large one?

None worth chasing. At 90% efficiency, the worked panel's 276 W of output turns into 30.7 W of loss whether one 15 A unit makes it or 10 A, 5 A and 2.5 A units share it. What changes is concentration, so keep 2 in [50 mm] of clear rail above and below each unit.

Should the three supplies' 0 V terminals be tied together?

Tie them at one point, usually a common terminal on the ground bar, so sensors, inputs and the HMI share a single 0 V reference. Keep an analog loop on its own isolated supply only when a device's instructions call for it, and mark the tie point on the panel drawing.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Build it from 12 × 10 × 6 inRequest a custom quote

NEMA 4X enclosures: sizes for this job

Keep reading

Related engineering answers

All articles

Buying guides

The guides behind this answer

All guides