Short answer: keep the VFD motor cable unshielded only while it holds its own conduit or ladder from the drive to the motor. On a tray shared with telecom cables the answer flips: restore 12 in [300 mm] of separation, screen the cable continuously through every joint, or enclose it in bonded steel conduit. The worked example has a 360 ft [110 m] trench leg in its own conduit and a 66 ft [20 m] coil delivered at the wall. From the splice it runs 330 ft [100 m] of flexible pump cable down to a buried pump. That totals 755 ft [230 m] of motor circuit, and the drive manual's length limit must cover all of it, not the longest leg.
What the drive manual decides
The drive manual settles the cable question before the route does. Every drive maker publishes motor-cable requirements in its installation and grounding guides: permitted construction, the minimum screen, the maximum motor-cable length and the extra measures a long run needs. The grounding guides ask for a copper or aluminum screen over all cores, run continuously and clamped at both ends. An unshielded cable skips that screen requirement, so its acceptance rests on the length limit and the route alone.
Count the length the way the manual means it: from the drive terminals to the motor terminals, every leg included. The example adds 110 m + 20 m + 100 m = 230 m. The 20 m coil counts even while it waits coiled at the wall, and a coil of motor cable is also a coupling loop, so cut it to length at the drive instead of leaving it wound up. If the manual allows 300 m of unscreened cable, the circuit passes as built. If its screened figure is 150 m, the same circuit fails the moment screening becomes necessary. Treat those two limits as worked-example values, and read the real pair from the manual of the drive you are buying.
The limits exist because a drive output is a pulse train, not a sine wave. Each pulse reflects at the motor end, and on a long run the reflected pulse stacks on the incoming one. The pulse at the motor terminals can then approach twice the inverter's output pulse. A screen adds capacitance to ground on top of that, which is why many manuals list a shorter screened limit than the unscreened one. Where the manual calls for an output reactor, a dv/dt filter or a sine filter at your circuit length, that device goes on the order with the cable.
How the shared tray changes the answer
IEC 60364-4-44, the EMC part of the IEC installation rules, sorts circuits by electromagnetic level. Between a noisy circuit and a sensitive one it asks for one of three separations: distance, a bonded metal barrier, or wiring systems that keep the noise in. Drive installation guides turn that into the number to hold: about 12 in [300 mm] between a motor cable and signal cables in parallel runs. Cross the routes at right angles where a crossing is unavoidable.
Distance is what the separate conduits delivered in the example trench, and distance is what a shared ladder takes away. On a common tray the motor cable runs close alongside the telecom circuits for the whole parallel length, it is unscreened, and the coupling path into them runs open. The same cable that passed on the conduit route becomes the emitter on the ladder route. The cable name decides nothing here; the as-built layout does.
You have three ways back on a shared tray. A bonded metal divider rebuilds the barrier; a second tray or conduit run rebuilds the distance; a screened or conduit-enclosed motor circuit closes the noise in. A tray cover is the fourth idea people reach for, and it treats only the emission above the tray. The cable-to-cable coupling underneath it keeps working, which the tray cover or shield bonding article works through. If the sensitive cables carry Ethernet or fieldbus, the separation and shield fixes in the VFD-to-Ethernet interference article apply to the same geometry.
Where the screen has to be continuous
A screen is a construction job, not a cable purchase. It works only while it runs unbroken from the drive gland to the motor terminal box. At the outdoor splice to the flexible pump cable, fit a joint that clamps screen to screen. At the motor, land the screen in the gland or on the designated screen terminal. A screen that stops at a splice leaves a slot in the shield, and the cable radiates from that slot. Before you open that splice or the motor terminal box, isolate the drive output and verify absence of voltage; a long motor circuit holds charge after shutdown.
At the enclosure entry, clamp the screen 360 degrees around the conductors, in a screened gland or under a gland plate clamp. A pigtail run to a terminal gives up most of that screening above a few megahertz. The entry is where the whole screen earns its keep, so treat it as part of the screen rather than part of the box. The shielded motor cable grounding at the enclosure entry article shows the termination detail, and the earth continuity through a gland plate article sizes the bond the plate needs for fault current.
Specify the cutouts with the order, the way the cutouts, glands and HMI windows guide sets out, so the plate arrives drilled for the screened glands instead of field-cut. Once inside, keep the motor cable in its own duct, away from analog and communication wiring. Cross the two at right angles where a crossing is unavoidable. The panel cable segregation article gives the layout, and the instrument signal cable layout article covers the signal side.
Steel conduit as the screen
Continuous steel conduit, bonded at every coupling and at each enclosure entry, surrounds the conductors with the same low-impedance metal path back to the drive that a screen provides. That makes it the practical retrofit when the unshielded cable is already in the trench and the shared tray cannot be split. It works only as a complete system: metallic couplings throughout, bonding bushings or jumpers at every box, and a bond at both ends. One unbonded coupling or one plastic fitting opens the path again, and plastic conduit gives no screening at all.
At the drive cabinet, bond the conduit to the enclosure itself rather than to a nearby rack. The motor cable entry: locking connector or conduit article compares the two entry methods, including the sealing each preserves. Keep each drive output in its own conduit too; the same-conduit cross-talk between drive outputs article shows what a shared run does.
What goes on the order
Specify the run as one package, so the cable, the glands, the plate and the filters arrive as a set that matches the manual.
| Item | What to specify | Basis |
|---|---|---|
| Motor cable construction | Screened cable once the route shares a tray: copper or aluminum screen over all cores, continuous | The drive maker's grounding guide |
| Circuit length | All legs counted to the motor: 110 m + 20 m + 100 m = 230 m in the example, against the manual's limit | The limit covers the whole motor circuit |
| Route separation | 12 in [300 mm] from signal and telecom cables, or a bonded metal divider on the shared tray | Drive installation guides |
| Splice to the pump cable | Screen-through joint, clamped screen to screen | A screen interrupted at a splice radiates |
| Enclosure entry | Screened gland with 360 degree clamp on a bonded gland plate | Pigtails lose screening above a few megahertz |
| Conduit option | Steel throughout, bonded bushings at every box and both ends | The conduit acts as the screen |
| Long-run filter | Output reactor, dv/dt filter or sine filter where the manual requires one at the circuit length | Reflected pulse and charging current at length |
| Enclosure | Wall-mount stainless junction box, cutouts specified for the screened glands, manufacturer-rated NEMA 4X / IP66; not UL listed | A sealed, bonded entry that preserves the rating |
For the enclosure row, you set the size and every cutout on a wall-mount stainless junction box. Send the gland count with each cable's outer diameter over the screen, and the plate arrives drilled to your drawing. Delivery is 10 business days, counted from your approval of the drawing for custom work. The outdoor splice enclosure lives in weather, which the outdoor stainless enclosures section covers. Within reach of salt spray, pick 316L, as the 304 vs 316L guide lays out.
The decision by layout
- Own conduit or own ladder, end to end, and no signal cables alongside: run the unshielded cable. Confirm the manual's unscreened limit covers the circuit as counted above, and keep each drive output in its own run.
- Shared tray with telecom or instrument cables, and the manual permits screened cable at that length: switch to screened cable, carry the screen through every splice, clamp it in screened glands at both ends, and add the filter the manual names at that length. The screened limit is usually the shorter figure, so check the circuit against it before you order.
- Shared tray and the cable must stay unshielded: enclose the shared section in bonded steel conduit, or fit a bonded metal divider or second ladder that restores the recommended separation. Either closes the coupling path the tray opened.
- Circuit longer than the manual allows for either construction: fit the manual's long-run filter, an output reactor, dv/dt filter or sine filter, or shorten the route. The length counts to the motor terminals, every leg included.
Whichever branch your route takes, the entry details travel with it: screened gland, bonded plate, separated duct runs inside the box. Those lines hold the EMC result at the enclosure, and they belong on the order next to the cable.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can an unshielded cable work as a VFD motor cable?
Yes, when both conditions hold. The drive manual must list an unscreened length limit that covers the whole motor circuit, and the route must keep the cable away from signal and telecom wiring. In the worked example, a manual that allows 300 m unscreened covers the 230 m circuit, while a 150 m screened figure would not; switching that route to screened cable then adds the manual's long-run filter.
How much separation does a motor cable need from signal cables?
About 300 mm [12 in] in parallel runs, the figure drive installation guides recommend, with right-angle crossings where the routes must meet. On a shared ladder the cables sit closer than that, so the barrier must come from construction: a bonded metal divider, a second ladder, or a screened or conduit-enclosed motor circuit. Inside the enclosure, run power and signal wiring in separate ducts and cross them at right angles.
Does the screen continue through the splice to the flexible pump cable?
Yes, and that joint is the one most often missed. Use a joint that clamps screen to screen, terminate the screen 360 degrees at the drive gland and at the motor, and remember that a pigtail to a terminal loses most of its screening above a few megahertz.
Is steel conduit as good as a screened motor cable?
The performance lives in the joints: one unbonded coupling or one plastic box in the run opens the path. Plastic conduit gives no screening at all.
Why is the screened-cable length limit often shorter?
The screen adds capacitance to ground, so the drive output charges more capacitance every switching cycle and the reflected pulse at the motor grows. For the same drive a manual might allow 300 m unscreened and 150 m screened. Take the pair from the manual of the drive you are buying, and put the filter it names at that length on the order with the cable.
Which gland and box hold the rating at the entry?
A screened cable gland with a 360 degree clamp, landing on a bonded gland plate, keeps the wall-mount stainless box's seal at the entry. Our wall-mount and junction boxes are rated NEMA 4X / IP66 by the manufacturer and not UL listed. Size each gland to the cable's outer diameter over the screen and send the cutout drawing with the order.





