Short answer: bad-quality flags that appear only while a large motor starts are a transient-coupling problem in the copper, not a bad earth. Work four checks in order: the control-supply input tap, the shared sag on control power, the copper route past the motor feeder, and the shield terminations. A ground resistance below 2 ohms tells you nothing about any of them.
The symptom pattern is distinctive. Only some signals fail, only during the start, and the values come back on their own once the motor is running. That points at a short, high-energy event coupling into specific conductive paths, not at a configuration fault in the control system. Treat the duration and the affected-channel list as data: one start, one timestamp, and a note of the first diagnostic to appear.
Sort the failures by where validity is lost
Before touching field wiring, sort the affected signals by what the diagnostics say:
- Only selected copper-connected signals fail: the fault is in the field circuit, the cable route, the shield or the input channels. This is the common case for a motor-start event.
- All channels on one remote I/O station fail together: look at that station's power supply and its communication link, not the field wiring.
- Signals from several stations fail at once: look at the shared network, the controller or a common power source.
- Fibre-connected paths stay healthy while copper paths fail: the entry route is the copper itself.
A station-wide failure is a different article; the remaining sections cover the single-channel copper case, which is what a motor start usually produces.
Check the control-supply input tap first
This is the fastest check and it has caught real installations. A switch-mode supply set for a 240 V input while actually fed 120 V can appear to work, but it sits at half its design input with no margin left. A 10% sag on the 120 V bus takes it to 108 V, and undervoltage trip or ride-through windows on many supplies sit near that level. The result is a brief reset or output dip exactly during the start, and every channel fed by that supply goes bad at once or in bursts.
Compare the tap, selector or jumper position against the measured input voltage and the nameplate. Do it before you buy anything.
The sag arithmetic
Here is a worked example with the assumptions labelled, because the numbers depend on your source impedance.
Assume a 6.6 kV motor of 400 kW at a power factor of 0.85. Its full-load current is 400,000 W divided by (1.732 x 6,600 V x 0.85), which is about 41 A. A typical induction motor draws 6 times full-load current at start, so the inrush is roughly 246 A, or about 2,800 kVA at 6.6 kV.
Now put that on a source of 10 MVA with 8% impedance. The voltage sag on the 6.6 kV bus is approximately 8% x (2,800 / 10,000), which is 2.2%. Add the feeder cable impedance and the motor's own locked-rotor condition and the sag at the motor terminals reaches 10% or more during the start. On the plant side, a 10% sag on a 120 V control bus is 108 V. That is the number a mis-tapped supply cannot ride through.
So: if the diagnostics show a supply dip coincident with the quality transition, fix the supply configuration, the distribution or the source before you add power conditioning. A conditioner selected from measured input conditions and the connected load comes last, not first.
Capture the input and DC output of the affected supply across the whole start with a scope or a power-quality meter that records transients. A handheld meter taken before and after misses a 100 ms sag entirely. Use the installed monitoring points or a properly rated isolated instrument, and keep general-purpose test gear off the 6.6 kV circuit.
Trace the copper past the motor feeder
The starting current in the motor feeder produces both a strong magnetic field and a fast-edged voltage transient. Coupling rises with parallel run length, falls with separation, and needs a conductive path, which is why fibre-connected signals stay healthy while copper ones go bad. That asymmetry is your best diagnostic: compare one affected route with one unaffected route of the same signal type and find what differs.
- Identify every affected signal as copper or fibre from field device to the acquisition point.
- Trace the copper through trays, risers, junction boxes and cabinet entries.
- Mark every section that runs parallel to the motor supply cable or passes close to the motor frame.
- Check crossings and entries for shared routing or accidental loops.
As a screening value, keep 12 in [300 mm] between medium-voltage feeder conductors and copper signal cables in parallel runs, and cross at 90 degrees. Separation of 6 in [150 mm] doubles the coupling roughly three to four times compared with 12 in, and a parallel run of tens of metres in a shared tray can couple enough to disturb a 4-20 mA loop. Where a long parallel run is unavoidable, a grounded steel barrier between tray compartments is the accepted practice. The same logic applies at the cabinet: keep signal and power entries on opposite walls, as covered in tracing the current return path when VFD noise moves servo axes.
Software filtering is not a fix here. It can hide a value disturbance, but it cannot repair a dropped communication frame or a module that reset. Find the physical path first.
Check shield terminations against the drawing
A 2 ohm earth reading and high-frequency bonding impedance are different quantities. At 1 MHz, a 3 m bonding conductor of roughly 3 microhenries presents about 19 ohms, so a bond that measures fine at power frequency can float at motor-start frequencies. The earth test says nothing about shield continuity, cabinet bonds or the voltage between two equipment locations during the start.
What matters is that each shield terminates the way the approved drawing shows. Where the design calls for single-ended grounding, the shield lands on ground at the designated end only and the other end stays isolated. An unplanned second contact at a gland, a tray or a junction box turns the shield into a conductor for the very transient you are trying to keep out. The both-ends and single-end decisions, and why motor cables differ from signal cables, are laid out in VFD motor cable shield grounding: both ends and why.
Work the check like this, with the circuit isolated and verified de-energized:
- Inspect shield continuity end to end, looking for cuts, damaged pigtails and shield-to-core faults.
- Confirm the designated grounding end against the drawing.
- Check the nominally isolated end and every intermediate junction for accidental chassis contact.
- Inspect cabinet and enclosure bonding separately from the signal shields; the panel-to-structure bond is its own subject, covered in grounding and bonding an electrical enclosure.
Signal cable junction points deserve a metal box with real bonding, not a plastic shell. Our stainless junction boxes, rated NEMA 4X / IP66 by the manufacturer and not UL listed, give you a bonded metal enclosure with a removable panel for shield terminations; see the stainless junction box sizes. For an outdoor termination point near the motor, the same boxes in 316L are the better pick; the trade-offs are in 316L wall-mount enclosures and the environment factors are summarized in outdoor and weatherproof enclosures.
One caution that belongs here: verify absence of voltage on the signal circuit and any auxiliary supply before you open a junction box or break a shield.
Fix one thing at a time and retest
Apply one controlled correction per start event, so the result tells you which mechanism was live:
- Correct any supply tap or selector mismatch before adding hardware.
- Repair loose control-power terminals, defective bonds, damaged shields and unintended shield contacts.
- Reroute or separate the copper runs your route comparison identified.
- Convert a confirmed copper link to fibre when the interface supports it and the copper path is the proven entry route.
- Add power conditioning only when a captured disturbance proves control power is the entry path.
Retest after each change with the same start conditions and the same diagnostic capture. When the same start produces no quality flags on any channel and the capture shows the supply holding within its ratings, the coupling path is closed. If the flags persist with the supply healthy, the shields correct, and 12 in [300 mm] of separation in place, the remaining suspects are the input channels themselves, and channel-level diagnostics will say so.
Most of these events end at step 1 or 3: a supply tapped for the wrong voltage, or copper running beside the feeder where it never should have been.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 6 × 6 × 4 in | 304 stainless | 6 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 8 × 6 × 4 in | 304 stainless | 8 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 10 × 8 × 4 in | 304 stainless | 10 x 8 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Does a ground resistance below 2 ohms rule out noise coupling during a motor start?
No. A fall-of-potential reading of 2 ohms describes a low-frequency earth condition. At the kilohertz-to-megahertz content of a motor-start transient, a few metres of bonding conductor add roughly 1 microhenry per metre, so a 3 m run is about 3 microhenries and roughly 19 ohms at 1 MHz. Measure bonding impedance with the transient in mind, not with an earth tester.
How much separation should signal cables keep from a motor feeder?
As a screening value, keep at least 12 in [300 mm] between 6.6 kV feeder conductors and copper signal cables in parallel tray runs, and cross at 90 degrees. If parallel runs longer than about 10 ft [3 m] are unavoidable, put a grounded steel barrier between the compartments; that is the accepted tray practice for separating power from signal circuits.
Can a power supply tapped for 240 V survive on a 120 V feed?
Sometimes, until the next sag. A supply set for 240 V while fed 120 V runs at half its design input, so a 10% sag takes it to 108 V, where undervoltage trip and ride-through windows are typically set. Set the tap or selector to the measured input voltage and retest with the same start.
Why do fibre-connected signals stay healthy while copper ones go bad?
Optical fibre carries no conductive path, so the induced voltage and current from the motor feeder have nowhere to enter. That asymmetry is itself diagnostic: when only the copper paths fail, the entry route is the copper, and rerouting, separation or shield repair is the fix.





