Two VFDs in one enclosure: heat, openings and protection

Two small VFDs add about 120 W of heat, enough to push a close-fitting sealed box 40 K above ambient. Size the enclosure by heat rejection, use manufacturer-approved vents or real cooling, mount the controls outside on pushbuttons and a potentiometer, and replace a drive with damaged covers before it goes in.

NEMA4 Enclosure engineering team · Published November 25, 2026 · 6 min read

Short answer: put both drives in a hinged metal enclosure sized by heat, not by fit. Two small drives add roughly 120 W of loss at full load, which lifts a sealed stainless box about 40 K above ambient. Plan a manufacturer-approved vent or a larger box, keep the air at each drive's cooling inlet under 40 C (104 F), and take the operator controls out to external pushbuttons and a potentiometer instead of cutting keypad windows in the lid.

Can two drives share one enclosure at all?

Yes, two drives belong in one enclosure, and it is usually the better build: one gasketed door, one set of glands, one mounting panel, terminal blocks and a pair of branch protection devices. What the enclosure must do is protect the drives from knocks, hose water and fingers. It must still let each drive breathe along the airflow path its installation drawing calls for.

The mistake to avoid is choosing the box so both units just fit, then discovering the heat has nowhere to go. A close-fitting junction box with the drives on spacers and the base knockouts opened traps the heat in the same air volume as the drives' cooling inlets. How to size an electrical enclosure walks through the sizing sequence; this article focuses on the two-drive heat case.

How much heat do two small VFDs actually add?

A drive's heat loss is roughly 2 to 4 percent of its rated power at full load, a figure drive makers publish as total heat loss in their dimension tables, split between heat sink and internal losses. Small fraction though it sounds, it lands in a small box.

Take the example case: two 0.4 kW gearmotor drives on a mobile inclined conveyor. At a typical 3 percent loss for a drive of this size, each unit dissipates about 60 W, so the pair adds 120 W to the enclosure. Add the control power supply and terminal losses and call it 130 W of design load. Substitute your own drives' datasheet losses before you select anything. A 2.2 kW drive pair at 3 percent is 132 W instead of 120 W, so the method scales.

What size box keeps the air below 40 C?

For a sealed enclosure the steady-state rise is the heat load divided by the wall's heat transfer. Use the reference value for stainless, k = 3.7 W/m²K, and a common 20 x 16 x 8 in box:

  • Wall area: 2 × (0.51 × 0.41 + 0.51 × 0.20 + 0.41 × 0.20) m² ≈ 0.78 m²
  • Rise: ΔT = 130 W ÷ (3.7 W/m²K × 0.78 m²) ≈ 45 K
  • At 25 C ambient the inside air settles near 70 C, about 30 K over the 40 C most drive manuals allow at the cooling inlet.

That is the arithmetic behind the short answer: a close-fitting sealed box fails the drive's own ambient limit before anything feels hot to the hand. A lid that is merely warm after six hours of running says very little about the air at the heat sink inlets; measure or calculate it. The enclosure heat calculation guide shows the full worked method, and the site's heat calculator runs the same numbers from your load and box size.

Do I need forced ventilation or just a bigger box?

Either works, and the choice is air through the box versus wall area. With ventilation, the sizing rule from enclosure practice is airflow in CFM = 1.76 × watts ÷ ΔT. For 130 W and a 15 K design rise: 1.76 × 130 ÷ 15 ≈ 15 CFM. A manufacturer-approved vent pair or a small filtered fan kit of that size holds the internal air to 40 C in a 25 C room. The filter needs a place in the maintenance round, because clogging puts the rise back up.

Without ventilation, roughly double the surface area: a box near twice the wall area brings the rise to about 22 K, still tight at 25 C ambient and unusable in a hot shop. In a dusty or washed-down spot, sealed walls plus a larger box, or sealed walls plus an air-to-air heat exchanger, beat an open knockout every time. The fan vs air conditioner vs heat exchanger comparison sorts the options by dirt load and ambient.

One point the physics settles: opened knockouts are not a ventilation design. They defeat the enclosure's rated protection against hose water and dust, and air drifting past a spacer-mounted drive does not pass through the heat sink channel the installation drawing calls for. If the box carries a rating such as NEMA 4X / IP66 from its manufacturer, keep it by using that manufacturer's approved vents, glands and mounting hardware for the rating.

Keypad windows or external pushbuttons, which keeps the rating?

External controls keep the rating; windows trade it for convenience. A cutout around each keypad is a hole in the protective boundary. It needs a rated gasketed operator or window, correct edge finishing and a size that still shields every terminal behind the faceplate. On a small box with two drive faces, that is two more openings to seal, maintain and justify to an inspector.

The cleaner build is a plain sealed lid: a start and stop pushbutton, an E-stop, and a 5 or 10 kΩ speed potentiometer for each drive, mounted in the door and wired to the drive's control terminals through glands. This costs a few control wires and keeps every opening a small, rated gland hole. The external fault reset push button article shows the wiring pattern for one such operator, and the cutouts, glands and HMI windows guide covers how to specify the holes so the rating survives them. It also solves the impact problem: a membrane keypad behind a lid-mounted button no longer takes the knocks a mobile conveyor collects.

What does the damaged drive cover change?

Replace or repair the drive before it goes in. A drive's own covers are part of its protection against contact with live parts and debris. An enclosure around a stripped unit does not restore missing plastic, and a finger-reach test is not a design. Pull the damaged unit, check its terminals, supports and heat sink for damage, and treat it as a replacement candidate if the internal parts are affected. When heat or damage means replacing the enclosure or its contents gives the decision points.

While it is out, add the protections the box then has to carry: a branch breaker or fuses for each drive line side sized to the drive's input current, a terminal block rail, and cable restraint so pulling forces land on the frame clamp, never on a drive terminal. How one breaker can protect two drives and the two-drive breaker and filter layout cover the protection side. The single-drive enclosure article covers clearances and heat for one unit if you ever split them. Wire duct fill stays at 50 percent of the duct cross-section, the figure duct makers publish citing NFPA 79, and the backplate and DIN rail layout guide shows how to arrange it.

What goes on the order?

Specify around the heat, then around the openings:

Item Decision for the two-drive conveyor case
Enclosure Hinged stainless wall-mount, deep enough for drive depth plus 2 in [50 mm] of wiring space; rated NEMA 4X / IP66 by the manufacturer; not UL listed
Heat 130 W design load; about 15 CFM of manufacturer-approved ventilation for a 15 K rise, or a box with roughly double the wall area sealed
Openings Gland holes sized to the cable, plus approved vents; no keypad windows
Controls Two start/stop pushbutton pairs, two speed potentiometers, one E-stop, all door-mounted and rated to the enclosure
Protection One branch breaker or fuse set per drive line side; terminals on rail; cable restraint at the frame
Drives Both with intact covers, datasheet heat loss figures on file

For a dry indoor shop with clean air, the ventilated small box wins on cost and size. For washdown, dust or outdoor sun, order the larger sealed stainless box and give up the vents. Then re-run the heat check at your worst summer ambient, because the 45 K rise example assumed 25 C; at 35 C ambient the same sealed box lands near 80 C inside, and that is a heat exchanger or air conditioner conversation, not a bigger passive box.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
20 × 16 × 8 in304 stainless20 x 16 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
16 × 12 × 8 in304 stainless16 x 12 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
24 × 20 × 8 in304 stainless24 x 20 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
30 × 24 × 10 in304 stainless30 x 24 x 10 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Do I need ventilation with two small drives in one box?

Usually yes. Two 0.4 kW drives add roughly 120 W of loss at full load. In a sealed stainless box of about 0.8 m2 of surface that is a 41 K rise. So 25 C ambient becomes about 66 C inside, well over the 40 C most drives allow at their cooling inlets. A manufacturer-approved vent pair moving about 14 CFM holds the rise to 15 K.

Can I cut a window in the lid so the drive keypads stay reachable?

You can, but every cutout must carry the same rating as the enclosure and seal against it, and the opening must not expose live terminals. A cleaner answer is a sealed lid with external pushbuttons, an E-stop and a speed potentiometer. Wire them to the drive control terminals through gland entries.

Do open knockouts count as ventilation?

They move some air, but an open hole defeats the enclosure's rated protection against hose water and dust. It also gives no controlled airflow through the drive heat sinks. Use the enclosure manufacturer's approved vent or fan-filter kit for the rating you need, about 14 CFM for a 120 W box at 15 K rise.

Can I put a drive with a broken cover inside a box and call it protected?

The outer cover of a drive is part of its protection against contact and debris, and a box around it does not restore what is missing inside. Check the drive for bent terminals, cracked supports and debris, and replace or repair it before it goes into any enclosure. A used unit with a damaged cover is a replacement candidate.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Build it from 20 × 16 × 8 inRequest a custom quote

Check the heat load in the calculator · Outdoor enclosures: sizes for this job