Short answer: yes, when both drives always run together. The same main breaker can feed the panel and act as the 150 hp drive's branch protection, because the drive's instructions set a 550 A maximum breaker and a 500 A main sits under it. The 50 hp drive and the 24 VDC supply still get their own breakers, sized from their own instructions. Two checks decide the whole question: the breaker against each drive's listed maximum, and the breaker against the feeder conductors. The first passes at 500 A against 550 A. The second is where a 500 A choice gets expensive, because conductors sized to the combined input accept a 400 A device at most. The arithmetic below runs both checks at 480 V, then covers the panel listing, the smaller branch and the enclosure itself.
When the main can protect the drive too
A main breaker normally does one job: feed the panel and lock the machine out. When it connects straight to a drive's input terminals with no other device between, it is also that branch's protection. The NEC rules for adjustable-speed drives allow exactly this: branch short-circuit protection for a drive's converter follows the manufacturer's listed instructions instead of the general motor tables. Those instructions give you the maximum breaker rating and the acceptable device types.
Three conditions keep the arrangement sound. The breaker rating sits under the drive's listed maximum — here 500 A against a 550 A ceiling. The breaker type comes from the manual's list, because the drive's short-circuit current rating was tested with those devices. The breaker must also protect the feeder conductors, which the worked example below sizes. Whether the two drives start together or a second apart changes none of it; for a smaller two-drive cabinet, the same device-by-device question is worked out in the two-servo breaker and filter article.
Fit the main door-interlocked so opening the door drops the panel, with the interlock defeatable by a tool when the procedure calls for live testing. That handle is then the single lockout for the feeder and the 150 hp drive. Lock out and prove zero voltage before you reach inside. If the main trips at power-up, stagger the drive contactors by a second; a capacitor precharge pulse lasts a fraction of a second, and the inrush article on breakers and contactors covers sizing the devices against it.
The first check: the drive's listed maximum
Open the drive manual to the protection page. It lists a maximum breaker rating and, nearly always, the types you may fit — Class J fuses or named breaker series. Pick from that list at or below the maximum, because the drive's short-circuit current rating was proven with those exact devices. A control-panel design guide written to UL 508A states it as a marking rule: branch protection must not exceed the rating and type in the component's group-installation marking.
Check the fault budget while the manual is open. The panel's short-circuit current rating must reach the fault current available at its line terminals. If the drive is listed at 65 kA with the chosen breaker and your switchboard delivers 42 kA, you have margin. At 65 kA available you sit at the limit, and at 80 kA you move to a device combination from the manual's list with a higher rating.
The second check: the feeder conductors
The NEC sizes feeder conductors to drives at 125 percent of the rated input current, summed across the drives on the feeder. The main breaker then has to protect those conductors: a device may sit one standard size above the conductor ampacity, and standard sizes step 350, 400, 450, 500, 600 A. Read ampacities from the NEC ampacity table, 75 °C column, copper: 400 kcmil carries 355 A and 900 kcmil carries 520 A.
The two rules pull against each other when the main is oversized. A 500 A breaker clears the drive's 550 A ceiling with room to spare, yet 400 kcmil — the natural conductor for two drives of this class — tops out at a 400 A device. Either you downsize the main to match the conductor, or you buy the copper the larger device is allowed to protect. The worked example puts numbers on both routes.
Worked example: 150 hp and 50 hp at 480 V
Take a machine with a 150 hp drive, a 50 hp drive and a 24 VDC control supply, fed from 480 V three-phase. The input currents below are rating-plate style values; replace them with your drives' figures before anything is ordered.
- 150 hp drive rated input: 200 A
- 50 hp drive rated input: 55 A
- 24 VDC supply: 40 A output (960 W), 90% efficient, so 960 / 0.90 = 1067 W in, which at 480 V three-phase draws 1067 / (1.732 × 480) = 1.3 A
- Combined input: 200 + 55 + 1.3 = 256.3 A
| Check | Working | Result |
|---|---|---|
| Conductor minimum | 256.3 × 1.25 = 320 A | 400 kcmil copper, 355 A at 75 °C |
| Largest device on that conductor | one standard size above 355 A | 400 A |
| Feeder loading | that device against a 320 A minimum | 25% above the load rule |
| Drive ceiling | that device against 550 A | 150 A spare |
| Running load | 256.3 A on the main | 64% |
Every check passes, so the main feeds the panel and protects the 150 hp drive at the same time. If upstream gear fixes the main at 500 A, you keep it and buy the conductors it may protect: 900 kcmil copper carries 520 A at 75 °C, which covers that device. That is 2.25 times the copper area of 400 kcmil and a heavier pull through the raceway. Inside the cabinet, size the runs from the main to each device by the panel shop's UL 508A wiring procedure; the figures here govern the incoming feeder at the line terminals. If a second 50 hp drive joins later, the combined input rises to 311 A and the conductors step up with it.
The 50 hp branch and the 24 VDC supply
Give the 50 hp drive its own breaker: above its 55 A input, under the maximum its own manual lists, with a lockable handle. That handle is the drive's disconnect, so a technician can lock out one drive while the other keeps running — a 55 A branch locked out leaves the 200 A drive untouched. Give the 24 VDC supply its own breaker too; a 6 A, D-curve device on the primary rides the supply's inrush and still clears a fault. Work the smaller manual exactly like the big one: maximum rating, acceptable types, and the short-circuit rating they give the branch. The branch-by-branch selection method is spelled out in the guide to splitting VFD branch circuits.
How the UL 508A listing sees it
A panel like this is an industrial control panel by definition. NEC 409.2 defines it as two or more power or control circuit components in one enclosure, and UL 508A is the standard a panel shop lists such a panel to. NEC 409.110 adds the enclosure type number to the panel marking, next to the listing mark. The shop documents each branch device against the component instructions and the panel's short-circuit current rating, which is exactly the paperwork the double-duty main needs. The Code requires equipment to be installed in line with its instructions, so keep both drive manuals with the panel records. One distinction worth carrying to the job site: the listing mark belongs to the assembled panel, while the enclosure carries the manufacturer's rating — rated NEMA 4X / IP66 by the manufacturer; not UL listed.
Enclosure layout: handle height, door swing and heat
Two numbers shape the cabinet before the drives do. Mount the main so the centre of its grip, handle highest, sits no more than 2.0 m (6 ft 7 in) above the floor under NEC 240.24(A). Keep the working space in front: NEC 110.26(A) asks for at least 3 ft (900 mm) for 0-150 V to ground, more at 480 V to ground. Leave room for the doors to swing 90 degrees. The enclosure mounting guide works through both, and the one-drive sizing article pairs the clearances with heat.
Heat is the bigger number. Start from 97 percent drive efficiency as the planning figure, and replace it with each datasheet value. A 150 hp drive is 111.9 kW of shaft power: 111.9 / 0.97 = 115.4 kW in, so about 3.5 kW is lost. The 50 hp unit adds 1.2 kW and the 24 VDC supply wastes roughly 0.1 kW. Call it 4.8 kW the cabinet must reject. Drives and their electronics usually carry a 40 °C (104 °F) ambient rating unless the datasheet allows more. A bare stainless wall barely helps: a 2.0 × 1.2 × 0.6 m cabinet has about 8.6 m² of surface, and at 3.7 W/m²K the 5 K between a 35 °C ambient and a 40 °C target moves 3.7 × 8.6 × 5 = 160 W.
The remaining 4.6 kW needs an air-to-air heat exchanger or an air conditioner, sized by the drive cooling method; a lineup this size is laid out in the multi-drive sizing article.
What goes on the drawing
Send the one-line and the cutouts together through the enclosure builder, and the drawing that comes back is what you approve before the 10 business days start counting. The line items this arrangement fixes:
- Main breaker: 400 A, type from the 150 hp drive manual, door-interlocked, handle centre at most 2.0 m (6 ft 7 in)
- 150 hp branch: no separate device; the main does both jobs (500 A stays workable if the feeders grow to 900 kcmil)
- 50 hp branch: lockable breaker above 55 A and under its manual's maximum
- 24 VDC supply: 6 A, D-curve breaker on the primary
- Feeder conductors: 400 kcmil copper, 355 A at 75 °C, matching the main
- Cooling: sized to remove 4.8 kW, holding 40 °C inside at a 35 °C ambient
- Working space: 3 ft (900 mm) minimum in front, doors opening 90 degrees
The decision, case by case. Both drives always run together and the manual caps the drive at 550 A: one 400 A main feeds the panel and protects the 150 hp drive, and the 50 hp drive keeps its own lockable breaker. The small drive must sometimes run with the big one locked out: the devices stay the same, because each branch handle locks. The manual lists a lower ceiling than the main you planned: drop the main to the largest value that clears both checks. The main is fixed upstream at the larger size: keep it, and run 900 kcmil copper so the device protects conductors it is allowed to protect.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can one breaker feed two VFD drives and protect both?
Yes for one drive: the main doubles as the branch protection for whichever drive connects straight to it, when its rating sits under that drive's listed maximum — the 500 A worked case against a 550 A ceiling. The second drive keeps its own breaker, sized above its 55 A rated input and under its own manual's maximum, and that handle doubles as its lockout.
How big should the main breaker be?
Size it from the conductors as well as the drive. At 256.3 A of combined input, 125 percent is 320 A, which 400 kcmil copper carries at 355 A; the largest device allowed on those conductors is one standard size above that. It sits 150 A under the drive's 550 A ceiling, so it does both jobs. A larger main instead needs 900 kcmil copper, rated 520 A.
Does UL 508A allow a main breaker to do both jobs?
Yes, when the panel follows the drive manufacturer's instructions and component markings. NEC 409.2 defines the assembly as an industrial control panel, UL 508A is the listing standard, and NEC 409.110 puts the enclosure type number on the panel marking. The enclosure itself is rated by its manufacturer; it is not UL listed.
How much heat do two drives add inside the enclosure?
Plan on about 3.5 kW of loss from the 150 hp drive and 1.2 kW from the 50 hp unit, assuming 97 percent efficiency — replace that with each datasheet figure. Add roughly 0.1 kW for the 24 VDC supply and the cabinet must reject about 4.8 kW. A bare stainless wall sheds only about 160 W at a 5 K rise, so a heat exchanger or an air conditioner carries the load.
What if the 50 hp drive must run while the 150 hp drive is locked out?
Keep the same devices. The smaller drive's breaker is already its disconnect: a lockable handle on the 55 A branch lets a technician service the 200 A drive while the small drive runs, with the main staying closed on the panel. The double-duty arrangement only loses its point if the branch breaker is removed, and every case here keeps it.