Email us

Este artículo está en inglés. Ver el sitio en español

Cet article est en anglais. Voir le site en français

Dieser Artikel ist auf Englisch. Website auf Deutsch ansehen

Este artigo está em inglês. Ver o site em português

EMT as EGC in parallel feeders: upsize or let the raceway carry it

Make the EMT joints up properly and let the raceway carry the fault current: ten parallel raceways are ten parallel ground-fault paths, a combination that tests at or below the wire NEC Table 250.122 sizes. If you pull wire EGCs anyway, each raceway carries the full size — in the worked example below, growing the phases from 8 to 10 sets turns a 3/0 copper EGC into 250 kcmil in every one of the ten raceways.

NEMA4 Enclosure engineering team · Published November 9, 2026 · 6 min read

Short answer: make up every EMT coupling and connector properly and let the raceway carry the ground fault — the upsized wire EGCs in all ten sets are redundant copper. Ten parallel raceways are ten parallel ground-fault paths, and bonded steel raceway tests at or below the impedance of the wire that NEC Table 250.122 sizes. If you pull wire EGCs anyway, the rule bites harder, not softer: each raceway gets the full size for the feeder's overcurrent device, grown in proportion to its phase conductors. In the 1200 A feeder worked through below, that turns a 3/0 copper EGC into 250 kcmil in every one of ten raceways.

How a bonded steel raceway returns the fault current

The NEC lists metal raceways, EMT among them, as equipment allowed to serve as the equipment grounding conductor. That allowance rests on measured performance: decades of published impedance tests put bonded steel raceway at or below the table-sized wire on feeders of this size. Two properties earn it. The raceway surrounds its phase conductors, so the fault loop is concentric and its reactance is tiny — a wire pulled alongside the phases cannot match that geometry. The steel wall also carries more cross-section than the table's wire, which cuts resistance.

Your instinct about surface area is half the answer. Ten sets give ten parallel paths, and parallel impedances divide: two raceways roughly halve the impedance, ten cut it toward a tenth. Each path is a good one on its own, which is the other half. Steel wins on geometry, not on material — steel resists current more than copper, so the concentric loop and the extra cross-section do the work. Those same ten paths also share normal stray current between panels; the grounding and bonding guide shows what that looks like.

The code holds you to the joints, not the steel. NEC 250.96(A) requires metal parts meant to serve as equipment grounding conductors — raceways, enclosures, fittings — to be bonded together so they can safely conduct any fault current likely to be imposed on them. Made up wrench-tight, EMT couplings and connectors are part of that path. The grounding and bonding guide walks the full route from fault to source.

Why the wire EGC still grows with the phases

NEC Table 250.122 sizes a wire EGC from the rating of the overcurrent device ahead of it: 3 AWG copper for a 400 A device, 3/0 copper at 1200 A. The table pairs the wire with the fault current its circuit can deliver until that device clears. Upsize the phases for voltage drop and the same breaker now clears more current through a lower-impedance loop, so the NEC's proportional rule grows the wire EGC by the same percentage increase in circular mils as the phases.

The physics is heating, not impedance. Fault heating rises with current squared times time, and the wire EGC has to survive the full clearing interval. A 3/0 wire left at its old size behind 25% more phase copper runs hotter for longer before the breaker trips. The proportional rule keeps the wire's thermal margin matched to what the circuit can now deliver.

In parallel raceways the code puts a wire EGC in every raceway and sizes each one from the feeder's overcurrent device — you never split one EGC across the sets. And the wire rule never looks at the conduit: it sizes the wire as if the raceway were plastic, because the raceway is an alternative path, not a partner. Run both and each wire still has to do the whole job alone, which is why the wires come out redundant when the EMT is bonded properly. The same full-size-per-raceway logic shapes how you divide conductors inside the box; the backplate and DIN rail layout guide works the fill side.

A 1200 A feeder upsized from eight to ten sets of 1/0

The inputs, with their sources:

  • Overcurrent device: a 1200 A breaker, the feeder being built.
  • Base phases: 8 sets of 1/0 AWG copper at 150 A each (75 C column of the NEC ampacity table) — 8 x 150 A = 1200 A.
  • Voltage-drop fix: the calculation adds 2 sets, so the run becomes 10 sets of 1/0 AWG. The NEC's parallel-conductor rule starts paralleled sets at 1/0 AWG copper, so more sets is the fix.
  • Phase copper: 1/0 AWG is 105,600 circular mils (cmil), so 8 sets give 844,800 cmil and 10 sets give 1,056,000 cmil.

The rule in words: size the wire EGC from the overcurrent device with NEC Table 250.122, then grow it by the same percentage increase in circular mils as the phases.

  1. Base EGC: Table 250.122 at the breaker rating calls for 3/0 AWG copper, 167,800 cmil, in each raceway.
  2. Phase increase: 1,056,000 cmil / 844,800 cmil = 1.25, a 25% upsize.
  3. Upsized EGC: 167,800 cmil x 1.25 = 209,750 cmil.
  4. Round up to the next standard size: 250 kcmil, or 250,000 cmil.

The result: ten raceways would each carry a 250 kcmil copper wire EGC — 250,000 cmil against the 105,600 cmil of the 1/0 phases beside it, 2.4 times the copper of the conductor it travels with.

That is the threshold to watch: whenever the wire EGC outsizes the phases it rides with, price the bonded raceway-only design first. Bond the EMT per NEC 250.96(A) and omit the wires; the raceway is the EGC in all ten sets. If the specification demands wire EGCs, all ten go in at 250 kcmil, full size, no sharing.

Where the raceway path breaks

Steel rarely fails; joints do. Each of these puts a series element in the path:

  • Couplings and connectors left finger-tight: the whole run is only as good as its worst joint.
  • Concentric knockouts: rings left in the wall do not guarantee metal-to-metal contact, and the code requires bonding around them — a bonding bushing or jumper finishes the path. The cutouts and glands guide covers knockout dimensions and fitting seating.
  • Paint and coatings under fitting seats: NEC 250.12 requires nonconductive coatings such as paint removed from threads and contact surfaces at grounding and bonding connections.
  • A section replaced with PVC or liquidtight: the metal path stops there, and everything downstream loses its EGC.
  • Corrosion at wet-location joints: oxide between set screw and wall adds impedance one joint at a time.

De-energize, lock out and verify absence of voltage before re-torquing fittings or punching new knockouts. Then prove the run: a continuity reading from the far-end box back to the source should sit well under 1 Ω for a feeder of a few hundred feet, and a bad joint shows up as a jump.

What it changes at the enclosure

The raceway hands the fault to the last enclosure, and the box has to accept it. Bond the enclosure through its fitting on bare metal; the grounding and bonding guide covers the bonding points and conductor sizes.

Mounting height matters when you work on those connections later: keep the highest breaker handle no more than 2.0 m (6 ft 7 in) above the floor and leave room for the door to swing 90 degrees, per the enclosure mounting guide. And when the design still pulls a wire out of a sealed outdoor box, keep the exit tight — the sizing rules in the enclosure sizing guide leave the bending space you need at the terminals.

What to specify, case by case

The run The call Size basis
Feeder fully in steel EMT, joints wrench-tight Raceway is the EGC; omit the wire EGCs NEC 250.96(A) bonding at every termination
Specification asks for wire EGCs One per raceway, each full size NEC Table 250.122 at the overcurrent device rating
Phases upsized for voltage drop Wire EGC grows by the same percentage of cmil 3/0 to 250 kcmil at a 25% upsize (the worked feeder)
Metal path interrupted by PVC, liquidtight or an insulated joint Restore bonding or pull the wire EGC Full Table 250.122 size in each raceway
Enclosure at the run's end Bond the box through its fitting on bare metal NEC 250.12 coatings; NEC 250.96(A)
Ground rod or the earth Left out of the fault path NEC 250.4(A)(5)

Decide by the path, not by habit. A feeder in bonded steel EMT needs no wire EGC whatever its phase count; a feeder with any nonmetallic break in the raceway, or a spec that names conductors, gets a full-size wire EGC in every raceway, grown with its phases. Size the box that terminates the run with the enclosure sizing guide before the conductors go in.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
12 × 10 × 6 in304 stainless12 x 10 x 6 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
20 × 16 × 8 in304 stainless20 x 16 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
24 × 20 × 8 in304 stainless24 x 20 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Can EMT be the only equipment grounding conductor on a parallel feeder?

Yes. The NEC lists steel raceways, EMT included, among the conductors and raceways that may serve as the equipment grounding conductor, and ten bonded sets give ten parallel fault paths. Published impedance tests put bonded steel raceway at or below the wire NEC Table 250.122 sizes — 3 AWG copper in each raceway for a 400 A feeder. The joints decide the result: make every coupling up wrench-tight and bond around concentric knockouts.

If you keep wire EGCs in parallel raceways, how are they sized?

Every raceway carries its own wire EGC, sized from the rating of the overcurrent device protecting the whole feeder — you never divide one conductor's cross-section across the sets. The worked feeder below starts at a 3/0 copper EGC in each raceway; growing the phases 25% pushes every one to 250 kcmil. Ten sets means ten full-size conductors, which is where bonded raceway-only saves the copper.

Does the ground rod or the earth return fault current if the conduit path fails?

No. NEC 250.4(A)(5) rules the earth out of the effective ground-fault current path, and the arithmetic agrees: on a 480Y/277 V system, 277 V across a 25 Ω electrode is about 11 A, nowhere near what trips a feeder breaker of this size. The bonded raceway loop sits at a few milliohms and delivers tens of kiloamperes, so the magnetic trip clears in a few cycles.

When do you have to add a wire EGC anyway?

Where the metal path is interrupted: a run replaced with PVC or liquidtight, an insulated joint, concentric knockouts left unbonded, or corroded set-screw couplings. Then pull the wire sized from NEC Table 250.122 at the feeder's overcurrent device, grown by the same percentage as any phase upsize, full size in every raceway — 3 AWG copper for a 400 A feeder before any upsize.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Build it from 12 × 10 × 6 inRequest a custom quote

NEMA 4X enclosures: sizes for this job

Keep reading

More on layout and installation

All articles

Buying guides

The guides behind this answer

All guides