Short answer: design the signal reference for impedance, not resistance, and keep every reference bond short enough to measure in inches. An average-length ground conductor already presents about 4,000 Ω at 1 MHz, so the wire that clears your fault current beautifully is the wrong part to reference a 1 MHz noise current. Keep grounding runs under 250 ft [76 m]; past that, build a new single-point node and tie it once to the facility ground. The enclosure is where that design lives, so here is how to get it right at the box.
Why a ground wire stops being a reference
At 60 Hz, a copper conductor is roughly its resistance, and resistance is easy to love. At frequency, inductance takes over, and inductive reactance is X = 2πfL, climbing in step with frequency. A 1 µH bond — about a metre [3 ft] of ordinary wire with its terminations — is 0.06 Ω at 10 kHz and 63 Ω at 10 MHz. Stretch the conductor across a room and it gets worse from there.
Instrumentation grounding guidance, the practice anchored by IEEE 1050, makes the point at building scale: an average-length ground conductor presents the 4,000 Ω figure quoted above, and a typical conductor is in the order of 40,000 Ω at 10 MHz, where it serves no reference purpose. Ten times the frequency is ten times the impedance on any inductance, so your reference degrades exactly where your fastest electronics operate. The same guidance draws the line at 10 kHz: any conductor carrying above 10 kHz is selected for low inductance first, resistance second.
In a panel that means short, wide and straight. A flat bonding strap 1 in [25 mm] wide and under 5 in [130 mm] long — a 5:1 length-to-width ratio — is the accepted shape, because flattening the conductor spreads its magnetic field and lowers inductance. Length is the enemy, and every bend adds a little more.
What the code covers, and the part you design
Grounding for control and computer panels carries four jobs at once, and only the first three have code paragraphs behind them:
| Job | What it takes | Where it lands |
|---|---|---|
| Shock and fault protection | A low-resistance, high-ampacity return to the source | Equipment grounding conductor sized from the breaker ahead of it; NEC Table 250.122 gives 10 AWG copper for a 60 A device |
| Tight fault loop | Power conductors and their return run together | Route the grounding conductor with its circuit conductors |
| Static and transient bleed | A low-impedance path off every metal surface | Bonded mounting panel and enclosure shell |
| Signal reference | Low relative impedance between devices, at the frequencies you run | A local plane or bar, bonded in inches — your design |
The fault returns over a conductor, never through soil: NEC 250.4(A)(5) leaves the earth out of the effective ground-fault current path. NEC 250.96(A) has the metal parts that may carry fault current — raceways, cables, enclosures — bonded so they conduct it safely. NEC 250.12 requires paint, lacquer and enamel removed from threads and contact surfaces at those connections, and NEC 250.6 keeps neutral current off the metal by landing neutrals on an isolated terminal. All of it is safety; none of it speaks to megahertz noise. IEEE 142 is the grounding-method standard that complements the NEC, and IEEE 1050 is the instrumentation reference for shielding and grounding signal cable. When noise practice and safety rules disagree, safety decides.
The reference bond at the enclosure
Your mounting panel is the reference plane, and everything else is a matter of keeping it one. Bolt it to the box through paint-free contact, since paint behaves as insulation at a bonding surface, and carry the plane across the door with a strap, because a hinge is an intermittent conductor at best. Give the panel one bar for protective earths and a second bar for shields, joined at a single point — panel earth and shield earth on separate bars sets out the split, and two ground bars in one enclosure covers whether the back panel alone can carry both.
Land the incoming equipment grounding conductor on the earth bar, and reference your 24 V DC signal common to that bar at one stud, once. Keep power wiring and signal wiring in separate duct runs — a foot [300 mm] between drive power wiring and analog or serial wiring, with right-angle crossings where they must meet, is accepted panel practice. Bar placement, conductor colour and bond hardware fundamentals are in the enclosure grounding and bonding guide.
Past 250 ft, build a new node
For distributed control and computer systems, keep grounding runs under 250 ft [76 m]. When the layout refuses, create a new single-point node for the equipment inside that limit and connect the node once to the facility or system earth ground, the distributed-ground approach IEEE 1050 describes. Equipment that communicates goes on one earth wherever possible: current through the soil between separate earth points holds a standing potential difference between them, and a nearby lightning strike or power fault can make it hazardous.
If your panels are fed through an isolation transformer, the secondary neutral-to-ground bond is that single point, and delta-wye isolation transformer grounding and single-point bond page covers placing it. A rod beside the remote panel is an auxiliary electrode under NEC 250.54: you may connect it to the equipment grounding conductor, and it carries no duty in the fault path or the reference. Skip the dedicated conductor routed separately to a special earth point — that is the one arrangement the guidance rules out.
Communication links that cross nodes
Every signal cable is a possible coupling point, and the shield termination is usually the biggest one. Match the interface to the grounding topology:
| Link | Grounding decision |
|---|---|
| Nonisolated RS-232, RS-422, RS-423 | Power and ground both ends from the same source as the device providing the signal, so no loop forms |
| Optically isolated ports | Ground the peripheral to any grounding system of adequate integrity |
| Ethernet with low-frequency noise on the link | Ground-isolation devices at each node, breaking the loop inside the communications path |
| Coaxial cable | Keep the shield continuous end to end; every break admits high-frequency noise into the shielded environment |
| Fiber | No metallic path, so each node keeps its own reference |
For differential field buses, RS-485 signal common and shield: one conductor or two settles the conductor question, and grounding between enclosures with single-ended signals traces the loop itself. Fiber is the clean answer at distance: with one ground conductor entering a system and everything else on light, no loop is left to break. Segregate noise makers — drives, contactors, switching supplies — from computer and analog circuitry, because even small high-frequency noise can force downtime, lost function or spurious machine actions.
Worked example: two panels, 300 ft apart
Take Panel A, a 24 x 24 x 8 in 304 wall-mount enclosure holding a PLC on a 60 A feed, and Panel B, a 16 x 16 x 8 in enclosure set up for a mini PC with the door cut for a 10.1 in panel PC, 300 ft [91 m] away on the same structure. They exchange one 0-10 V analog signal and one RS-232 line. Treat these as worked-example inputs and replace them with your feeder size, cable route and signal list.
The DC check passes. 300 ft of 12 AWG copper at about 1.6 Ω per 1000 ft is 0.48 Ω (300/1000 x 1.6 = 0.48). A 10 mA shift in the signal common develops 0.01 A x 0.48 Ω = 4.8 mV at the far end, invisible beside a 10 V signal. That is the calculation that persuades you at DC.
The high-frequency check fails. This run is longer than the average conductor behind the impedance figure quoted earlier, so that figure is the floor, not the ceiling. Assume a modest 10 mA of common-mode noise at that frequency sharing the conductor — one drive on the same steel can source far more. The developed voltage is 0.01 A x 4,000 Ω = 40 V between the two commons. An RS-232 receiver decides at ±3 V, so the noise sits about 13 times above its threshold, and against the 0-10 V analog signal it is four times full scale. The link goes down, or quietly reads wrong.
The fix: build the node at Panel B, tie it once to the facility ground, and cross the 300 ft on isolated links — optically isolated RS-232, an isolated repeater pair, or fiber for the analog channel too. Reference the 24 V DC common at one point at each panel, and bond each panel's plane to its node with a 1 in [25 mm] strap under 5 in [130 mm]. Panel A keeps its 10 AWG copper equipment grounding conductor for the 60 A feeder per NEC Table 250.122, sized for the fault and never the signal reference. Scope the common-mode voltage between the commons afterwards: millivolts where you measured tens of volts.
What to specify
Put the grounding design on the drawing with the cutouts:
| Your layout | What to order |
|---|---|
| One cabinet, signals internal | Earth bar and shield bar on the bonded mounting panel, door strap, green or green-with-yellow-stripe conductors at 6 AWG and smaller (NEC 250.119) |
| Panels within 250 ft [76 m] on one system | One shared node, reference bonds as short straps, nonisolated links allowed when both ends share the source |
| Panels past 250 ft | New single-point node at the far group, one tie to facility ground, isolated or fiber links across the gap |
| Washdown or outdoor remote station | A 316L box such as the 20 x 16 x 8 in, same reference rules, stainless strap hardware |
Our enclosures are rated NEMA 4X-type / IP66 by the manufacturer and not UL listed. You set the material, width, height, depth and every cutout, including ground-bar studs and door-strap fasteners, and the box is delivered in 10 business days from your approval of the drawing. The wall-mount range runs from 6 x 4 x 4 in to 60 x 36 x 16 in, and the enclosure selector narrows it by inside height, width, panel-to-door clearance and DIN module count.
Enclosures in this article
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 24 × 24 × 8 in | 304 stainless | 24 x 24 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 16 × 8 in | 304 stainless | 16 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 316L stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Why does a ground wire fail as a high-frequency signal reference?
Its inductance, not its resistance, sets the impedance, and inductive reactance grows in step with frequency, so ten times the frequency means ten times the impedance. That is why instrumentation grounding guidance selects any conductor carrying above 10 kHz for low inductance first, resistance second. Reference bonds are short, wide straps rather than long round wire.
What should I do when a grounding run exceeds 250 feet?
Create a new single-point ground node for the equipment within 250 ft [76 m] and connect that node once to the facility or system earth ground. Keep communicating equipment on that one earth, because separate earth points can develop hazardous potential differences during lightning or a nearby power fault. A conductor routed separately to its own special earth point is the one design the guidance rules out.
How should RS-232 or RS-422 devices on two panels be grounded?
Power and ground both ends from the same source as the device providing the signal, so no ground loop forms; optically isolated ports free the far device to use any grounding system of adequate integrity. In the worked example, 10 mA of common-mode noise through the average-conductor impedance put 40 V on a link whose receiver decides at 3 V, and isolation removes that path entirely.
Can the mounting panel serve as the signal reference plane?
Yes, when it is bonded: fasteners through paint-free contact per NEC 250.12, a strap across the door, and one ground bar for protective earths tied at a single point to the shield bar. Keep the panel-to-node bond a 1 in [25 mm] strap under 5 in [130 mm] long, a 5:1 length-to-width ratio, so it stays low-inductance.
Does a ground rod at the remote panel give a better reference?
No. NEC 250.54 treats a rod next to pole- or wall-mounted equipment as an auxiliary electrode that may connect to the equipment grounding conductor while carrying no duty, and NEC 250.4(A)(5) keeps earth out of the fault path. Reference quality comes from conductor geometry, short and wide, not from soil resistance.





