Short answer: earthing and grounding are the same connection to earth — "grounding" is the North American word, "earthing" the British and IEC word for it. The IEC protective conductor (PE) and the NEC equipment grounding conductor (EGC) are one wire doing one job. What separates the conductors inside your panel is function, and the word on a drawing tells you nothing about that: protective earth carries fault current until the breaker trips, a circuit reference fixes your zero point, and a shield bond gives interference a short path to the plate. This page sorts the words, then traces one bond end to end with the numbers.
Are earthing and grounding actually different connections?
No — they are two words for the same physical tie to earth: "grounding" in the NEC standards used across North America, "earthing" in the IEC standards of Britain, Europe, India and much of the Commonwealth.
The split is history, not engineering. A panel built to either code gets the same copper in the same places. A drawing that mixes the words is telling you who wrote each page, nothing more. Where the words cost you time is documentation: when PE, earth, ground and chassis appear interchangeably, stop reading labels and start tracing conductors to their terminations. The table maps the vocabulary both worlds put on drawings.
| On an IEC drawing | On a US drawing | What it is | What proves it |
|---|---|---|---|
| Earthing | Grounding | any tie of live parts or exposed metal to earth | the tests below |
| Protective conductor (PE) | Equipment grounding conductor (EGC) | the fault-current path back to the source | earth-loop impedance, milliohm continuity |
| Functional earth | signal ground, COM | the reference node for control and signal voltages | voltage to PE at its one bond point |
| Earthing conductor | Grounding electrode conductor | the tie from the main earth bar to the electrode | electrode resistance test |
| Earth electrode | Grounding electrode | rod, plate, ring or grid in the soil | 25 Ω cap for a single rod (NEC) |
One colour survives every translation: green with a yellow stripe. IEC 60446 reserves green-and-yellow for the protective conductor alone. NEC 250.119 matches it from the other side, allowing an insulated equipment grounding conductor of 6 AWG and smaller to be green, or green with one or more yellow stripes. When you see that pair on a wire, both systems read it the same way.
Which green/yellow wire is the protective earth in your panel?
The one that runs from exposed metal to the PE bar with the supply: enclosure body, door, mounting plate, gland plate, and the chassis of every drive and power supply land there, and the bar leaves the panel with the supply circuit.
Its job description is NEC 250.96(A) in plain words: metal parts meant to carry fault current — raceways, cable armour, enclosures — are bonded together so they conduct any fault likely to be imposed on them. Size the conductor from the rating of the overcurrent device ahead of it, using NEC Table 250.122; the grounding and bonding guide carries the sizing detail. Two details decide whether your PE is real rather than decorative:
- Coatings. NEC 250.12 asks for paint, lacquer and enamel removed from threads and contact surfaces at grounding connections. On a painted mounting plate that means bare metal under the ground-bar feet and every ring lug, or toothed hardware designed to bite through.
- Neutrals kept apart. NEC 250.6 keeps load current off metal parts, so the neutral lands on the isolated neutral terminal and grounds on the ground bus. A clamp ammeter reading amps on the ground bar of a healthy panel means a neutral is sharing it — chase that stray current before it cooks a lug.
What does an earth wire do in a panel besides fault protection?
Two other jobs: a circuit reference fixes the zero node for your 24 V DC control power, and a functional bond or cable shield gives interference a low-impedance place to drain. Different jobs, different tests.
A reference gets bonded deliberately, once — usually at the reference terminal of the power supply. Each extra bond invites load and noise current onto your reference, and circulating current is the classic reason a reference node moves when a drive loads. Shields follow their own rule: bond the drain of a VFD control cable at one end only, and land shields on their own bar so nobody mistakes them for PE. The full case for separate bars is in panel earth and shield earth: one system, separate bars. Whether the back panel alone can carry that second bar is its own question, and the answer depends on the panel-standard continuity limits your build must meet.
Why can't a ground rod clear a fault on its own?
Because soil is a poor conductor: the NEC caps a single rod at 25 Ω, so a 120 V fault to your enclosure drives 120 V ÷ 25 Ω = 4.8 A through the earth. That is 24% of a 20 A breaker's rating, and the thermal element carries it indefinitely.
Magnetic tripping happens far above rating. IEC 60898 sets the instantaneous bands, and the table turns them into the loop impedance your panel feed has to beat:
| Curve | Magnetic band | A 20 A device trips at | Loop budget at 120 V |
|---|---|---|---|
| B | 3-5 × In | 60-100 A | 2.0 Ω down to 1.2 Ω |
| C | 5-10 × In | 100-200 A | 1.2 Ω down to 0.6 Ω |
| D | 10-20 × In | 200-400 A | 0.6 Ω down to 0.3 Ω |
A Type C on a 120 V circuit needs the whole loop — transformer, supply cable, PE and back — at 1.2 Ω or less. NEC 250.4(A)(5) states the conclusion the arithmetic already showed: the earth is not the effective ground-fault current path. A rod beside the enclosure is an auxiliary electrode under NEC 250.54, yours to tie to the equipment grounding conductor. The fault still returns through the copper — a machine with its own ground rod needs its grounding bushing for exactly this reason.
Personnel devices exist because the rod lets current live on: an RCD opens at 30 mA and a US Class A GFCI at 4-6 mA. Meanwhile the case sits near line potential. Across the conservative 1 kΩ of a wet hand-to-hand path, 120 V drives 120 mA — four times the RCD level, well inside the fibrillation region that device is set to avoid.
How do you test each earth connection in the box?
Trace it first, then test by function: milliohm continuity and an earth-loop test for the PE, a stable voltage-to-earth reading at its one bond point for the reference, and a before-and-after noise check for the shield. Lock the panel out and check for absence of voltage before touching the bars. Continuity testing runs dead; only the loop test, which needs the live supply path back to the transformer, runs energized.
- PE continuity. A bond tester pushing at least 10 A — the IEC 61439 panel-standard test — heats a half-crushed lug enough to show it, where a DMM at a few milliamps finds only a clean break. A sound strap with crimped lugs sits in the tens of milliohms; treat 0.1 Ω and above on a short bond as a joint to redo.
- PE loop. Measure at the panel feed with a loop tester and compare against the table above, keeping two to three times margin on current. The supply cable and the transformer share the loop with your panel.
- Reference. Read zero volts to PE at the single bond point, idle and loaded. A reading that moves with load means load current is sharing your reference.
- Shield. Confirm drain-to-bar continuity, then watch the drive's noise symptoms or the comms error count with the drain on and off the bar.
What should a good enclosure bond measure?
About 0.08 Ω door-to-ground-bar with the strap fitted, and a fault loop near 0.4 Ω — the numbers from this worked example, a 16 × 12 × 8 in stainless wall-mount box on a 120 V control supply fed through a 20 A Type C breaker.
The panel carries three green/yellow conductors to sort out: the supply PE on the ground bar, the 24 V DC reference bonded at one point, and the drive control cable's drain on the shield bar. The readings below are this example's; take your own.
- Earth loop at the feed: 0.4 Ω. Prospective fault current = 120 V ÷ 0.4 Ω = 300 A, three times the 100 A floor of the Type C band. Per IEC 60898, the breaker clears magnetically in under 0.1 s at that multiple. The loop passes with margin: 0.4 Ω against a 1.2 Ω budget.
- Door strap: 0.08 Ω fitted. With the strap removed the door reads 1.9 Ω through its hinges, and the number swings as the door moves. Hinges align doors; straps carry faults.
- Rod beside the wall: 38 Ω. Above the 25 Ω single-rod cap, so the fix is the NEC's own — drive a second rod. Clearing performance stays where it was, because clearing rides the 0.4 Ω loop and never the soil.
Decision, by function: the supply PE passes (loop 0.4 Ω, continuity in the tens of milliohms), the reference is correct as a single point, and the drain belongs on its own bar. Write the three functions on the as-built drawing — green/yellow insulation carries none of that information.
What earthing provisions do you order with the enclosure?
Put the bonds on the drawing: a ground boss or stud on body and door, a braided door strap crimped at both ends, a bond link across the gasketed gland plate, and a PE bar on the mounting plate. The gasket between a gland plate and the body breaks the metal path, so sizing the bond link across a gasketed gland plate belongs on the order, not in the field.
You set the grade, the width, height and depth, and every cutout; the stainless size finder shows what a wall-mount or HMI body offers, and the enclosure selector narrows it while environment and inside space are still being decided. Say where the bars go and how many conductors each carries, and ask for bare-metal landing spots at every bond. The finished box is delivered in 10 business days, counted from your order; for this custom work, from your approval of the drawing.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Is the neutral the same as earth because both tie to ground at the service?
They meet at one point at the service, and that is the whole of their relationship. The neutral carries load current every day; the protective conductor carries fault current for the milliseconds it takes the breaker to open. Land the neutral on its isolated terminal and the grounds on the ground bus, the split NEC 250.6 asks for. A clamp ammeter on the ground bar of a healthy panel should read zero.
Can a shield drain double as the protective earth?
No. An instrument cable drain is around 0.5 mm² [20 AWG] of tinned copper, sized to bleed interference, while the protective conductor is sized from the breaker ahead of it. A phase-to-frame fault would open the drain like a fuse and leave the enclosure live. Give shields their own bar and keep the PE bar for conductors that can carry the fault until the device trips.
Does the loop impedance arithmetic change at 230 V?
Only the division. A 20 A Type C breaker still needs 100 A at the bottom of its magnetic band, so at 230 V line-to-earth the budget is 230 ÷ 100 = 2.3 Ω. The 120 V panel in the example budgets 1.2 Ω. Keep a margin of two to three times on current, because the supply cable and transformer share the loop with your panel.
Why does an unbonded 0 V read tens of volts to earth?
Leakage through the filter capacitors inside a switch-mode supply. Its input filter ties each output terminal to the line through small Y-capacitors, so a floating reference sits at roughly half the supply voltage. A high-impedance meter reads something like 50-60 V AC to earth on a 120 V supply. Bond the reference to the PE bar at the one intended point and the reading falls to millivolts, with almost no current flowing.





