Short answer: on an RJ12 serial port, wire only the two RS485 conductors to pins 1 and 6 and leave pins 2 through 5 with nothing on them. In one panel build, four spare conductors reaching the plug cut standalone communication to roughly 75% packet loss even though their far ends connected to nothing, and a cable carrying only the two signal conductors brought success back to about 99%.
The trap is that the fault looks like a grounding problem or a noisy drive. Shield grounding changes had no effect, a replacement cable of the same construction had no effect, and swapping the drive had no effect. The failure lived in the plug.
What you see when spare conductors are the fault
The pattern is distinctive, and each symptom points somewhere specific:
- Communication is fast and clean while a commissioning computer is connected to a second port, and collapses to heavy packet loss the moment you unplug it.
- Slowing the baud rate to the lowest setting does not recover the link.
- Re-grounding the shield, at either end or both, changes nothing.
- Swapping the drive or the controller changes nothing.
- The cable is a quality shielded multipair, yet the link behaves worse than a cheap untwisted pair.
If the first bullet matches, stop changing settings. A computer plugged into a second port can alter the common-mode reference and mask a marginal physical layer. Pull it and repeat the same transaction count before you touch anything else.
Why a floating conductor is not a dead conductor
A conductor attached to an interface pin acts as a coupled antenna whether or not its far end terminates anywhere. Noise from nearby drive cables couples into it capacitively and inductively, and it re-radiates into the two signal conductors running beside it inside the same jacket. Two spare conductors touching each other are worse still: they form a loop and can interconnect interface circuits that were never meant to be joined.
The same physics decides shield practice, which is why how you ground an RS485 shield inside a metal enclosure matters to the result. On a drive-heavy site, noise often rides the local earth, so grounding the shield at both ends can inject rather than drain it; the fix for that case is one-end termination. The same logic carries into DC systems, as the RS485 shield grounding in a battery-powered system article shows. Change one variable at a time and log packet success after each.
Check the plug before you check the protocol
Isolate the circuit, then work through the assembly:
- Confirm from the port drawing which pins carry the RS485 pair. Viewing orientation reverses apparent pin order, so identify contacts from the drawing rather than counting from an end.
- Count how many conductors actually land on the plug. Six conductors in a six-position plug means four spares are active antennas.
- Check whether the spares touch each other, the shield drain or the metal plug shell anywhere along their length.
- Verify continuity and polarity of the two signal conductors end to end; if the labels look wrong, match polarity rather than the A and B marking the way the VFD RS485 polarity article describes.
- Measure packet success with the commissioning computer removed, then make one change and measure again.
Rebuilding the cable that lost 75% of its packets
Here is the documented progression, from a build where a shielded cable with four twisted pairs fed an RJ12 port. The PLC and drive were identical throughout; only the conductor population at the plug changed.
| Cable state at the plug | Packet success | What it proves |
|---|---|---|
| Six conductors landed, four spares open at the far end | about 25% (75% loss) | Open far ends do not neutralize spares |
| The two conductors floating at both ends removed | about 60% | Fully floating conductors still contribute |
| The remaining four spares separated so none touch | about 90% | Contact between spares worsens coupling |
| Those four trimmed to about 1 in [25 mm], kept separate | about 96% | Shorter spares couple less |
| A purpose-built cable with only two conductors | about 99% | Removing the connections at the plug resolves it |
Read the table as a decision, not as a specification for your site: the percentages describe one installation's tests, and your loss rate will differ. The engineering conclusion transfers. Each step that removed or shortened conductors connected to the plug improved the link, and only a two-conductor cable removed the fault entirely.
Specifying the cable and the gland entry
Order a cable with exactly the conductors the port uses: two signal conductors plus, where your grounding plan calls for it, a dedicated third conductor or drain for the shield. A common industrial practice grounds the RS485 reference through a third conductor at one point, and the same reasoning appears in grounding an unused CT secondary in your control panel: land a reference at one point, once.
Inside a washdown panel, the cable entry is part of the fix. Land the shield on a clamp or terminal just inside the gland rather than letting the drain float back along the cable, as the shield grounding article describes. Keep the serial cable at least a few inches from drive output cables, cross them at right angles where they must meet, and check what the armored cable gland article says about entries, so the drive's radiated noise never shares a bundle with your RS485 pair. Use glands rated for the enclosure's environment; our washdown enclosures are rated NEMA 4X / IP66 by the manufacturer, not UL listed, and a mismatched gland is the weak link in that rating. If a field-cut hole in a custom stainless enclosure leaks after the cable goes in, the fix in sealing a wrongly drilled hole restores the seal without touching the wiring.
When the fault is something else
If two-conductor wiring leaves the link still dropping packets, the noise is arriving by another path. A VFD's switching noise commonly rides the local earth, and anything bonded to that earth can pick it up; a grounded sensor or an unbalanced shield can carry it onto your pair. The shield and CT grounding articles above walk the same isolation logic: measure with the earthing change in place before you replace hardware.
The decision
For an RJ12 RS485 port: wire pins 1 and 6 only, terminate the shield per your site's noise case, and buy or build cable with no spare conductors. If loss persists, isolate the earth path before you replace hardware. Cut the spares out of the plug first; it costs nothing and it is the fault most often hiding behind a convincing noise story.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Which RJ12 pins carry RS485 on this kind of PLC serial port?
On the port described in the source test, pins 1 and 6 carry the two RS485 signal conductors, and pins 2 through 5 must stay unconnected. Check the port drawing for your controller, because viewing orientation can reverse the apparent pin order and colour codes differ between cables.
Does cutting the spare conductors short at the far end fix the packet loss?
No. In the documented test, conductors on pins 2 to 5 still disturbed the link with their far ends open, and letting them touch drove loss to about 75%. Shortening the four conductors to about 1 in [25 mm] inside the plug raised success to about 96%, but only a plug wired to pins 1 and 6 alone gave about 99%.
Will a shielded multipair modem cable solve RS485 noise on an RJ12 port?
No. A shielded cable with four twisted pairs made the fault worse in the source test, because six conductors reached the plug. Fit a cable with only the conductors the port uses, terminate the shield at one end as your noise case dictates, and route it away from drive cables inside the enclosure.
How much spare conductor length is acceptable inside the plug?
Zero is the target. In the test sequence, removing two fully floating conductors lifted success from about 25% to about 60%, separating the remaining four lifted it to about 90%, trimming them to about 1 in [25 mm] reached about 96%, and a two-conductor cable reached about 99%.